RAG-12 Series Gas Insulated Switchgears

Specification

莱福士电力电子设备(深圳)有限公司

>
R&A Power Eletronic Equipment (shenzhen) Co.,Ltd.

1, Introduction
The RAG - 12 type AC metal enclosed switchgear (hereinafter referred to as the Switchgears), RAG 12 (B) type AC metal enclosed switchgear (hereinafter referred to as the circuit breaker Switchgears), RAG 12 (F) type AC metal enclosed switchgear(hereinafter referred to Load Break Switch Switchgears), RAG 12 (R) type AC metal enclosed switchgear(hereinafter referred to as the Outgoing Switchgears) is produced by low pressure SF6 Gas to insulate and breaking the three-phase, 50Hz, AC Indoor Distribution Equipments.

The switchgear can be divided into one to five units of Integrated Gas compartment, Circuit Breaker Switchgear is composed of circuit breaker + disconnector, which it is equipped with vacuum circuit breaker and three position of disconnector. It uses the circuit breaker to control circuit, open and close the load and overload current, short circuit current. It uses the disconnector to provide reliable isolating distance for line side cable, when disconnector is in the grounding position that can make the line to be side grounding. Load breaker switch+current-limiting fuse, which it uses load break switch to control circuit, open and close load current, overload current, using the load switch + current-limiting fuse to control, open and close, insulate transformer and other distribution and transmission circuit, and also protect MV side transformers, and short circuit current and overload current of LV distribution circuit. According to primary system diagram, the RAG - 12 (B) , RAG - 12 (F) RAG - 12 (R) are combined to use for Ring network circuit, circuit breaker switchgear, load break switch switchgear, outgoing load break switch switchgear can also be used separately, they are used for 12kvV and below Secondary distribution system, are suitable for 12kV power supply line Ring or dual radiation, when a section of line failure occurs, the line after restructuring to cause fault section isolate fault segment, so as to restore the line power supply in time, that improve power supply to be reliability and utilization. It is suitable for cable feeder network of commercial and industrial area or high load of power supply in rural township high density area. Use safety, less affected by the climate, easy installation, maintenance, saving place, and it is very suitable for the in box-type substation. RAG - 12 series of SF6 Gas-insulated Switchgear is a new generation small size modular switchgear, each module has independent and complete function, it can be combined them in accordance with different design scheme, it is suitable for 12kV MV Distribution system.

2
第 一

2,Rated technical parameters 2.1 Products using the environment
The installation site The temperature environment (℃) Altitude (m) Air humidity (%) Earthquake intensity The horizontal acceleration Vertical acceleration ≤1000 The daily average of not more than 95%, on average less than 90% 8 degrees ≤0.4g ≤0.2g。 Indoor of the -25~+40

The use of the environment have special requirement and please in consultation with the company.

2.2 Composition and meaning of product model
RA G12 (□) / T □ --- □
Rated short time withstand current Rated current Spring mechanism Program code Rated voltage Gas Insulated R&A Power Eletronic Equipment (shenzhen) Co.,Ltd.

3
第 一

2.3 Rated operation parameters
Serial number 1 2 3 4 5 6 Technical parameters Name Rated voltage Rated frequency Rated current Rated short drop out current Rated transfer current Power fiequency withstand voltage Impulse voltage withstand Phase to phase/earth kV Between open contacts Phase to phase/earth Between open contacts Major loop Thermal current (effective value) Grounding 2s 4s switchswitch kA 20 / 20 25 20 / kV 48 75 85 20 25 Unit kV Hz A kA A 630 / / 125* 31.5* 1700 42 Unit F Unit R 12 50 630 20 / 1250 25 / Unit B

7

8

Ground connection loopconnectioncircuit Major loop 9 Move Or Steady Current, Pesk Value Grounding switch Ground connection loopconnection circuit Load switch Grounding switch

kA

17.4 50 50 43.5 50 50

/ / / / / / 630 31.5 10 6000 2000

17.4 50 50 43.5 50 50 / / / 10000 2000

21.8 63 63 54.5 63 63

kA

kA KA

10

Rated short-circuit making current (peak value)

11 12 13

Load switches rated closed-loop breaking current 5% Rated power load breaking current Load turn on ratings of cable charging breaking current Machinical life Load switch Earth connection switch

A A A In order

630 31.5 10 6000 2000

14

10000 3000

15

Rated operating sequence

O-0.3s-CO-180sCO

4
第 一

3,product structure
3.1 RAG-12(F) Load switch unit

The first plan drawing chart
370
P r e s s u r e g1 auge Load switch opera 2t i o n p a n e l

806

370
Pressure gauge

A B C

1700

The upper panel lock The grounding switch 4 operating hole Load switch o pe5 rating hole Cable vault door chain hole T h e c a b l e v a7 ult door Observation w 8indow

9 Load 10 L o a d

switch mechanism switch

806
670
806 320

11 12 13

Into (out of) bushing The pressure relief valve

Into (out of) cable hoop

1

370
Pressure gauge

14 C a b l e

1

Load switch operation panel 2

Load switch operation panel 2

A B C

1700

The upper panel lock The grounding switch operating hole 4 Load switch operating hole 5 Cable vault door chain hole The cable vault door 7

9 Load switch mechanism 10 Load switch 11 12
670
Into (out of) bushing The pressure relief valve

A B C

1700

The upper panel lock The grounding switch operating hole 4 Load switch operating hole 5 Cable vault door chain hole The cable vault door 7 Observation window

Observation window

8

13

Into (out of) cable

320

14 Cable hoop

9 Load switch mechanism 10 Load switch 11 12
670
Into (out of) bushing The pressure relief valve

8

13

Into (out of) cable

320

14 Cable hoop

Load switches cell structure diagram

5
第 一

3.2 RAG-12(R)

Combined electric unit

The first system drawing
370
Operation panel combined electrical appliance 2 Pressure gauge 1 The upper panel lock The grounding switch operating hole 4 Load switch operating hole 5 Cable vault door chain hole Cable hoop Fuse tripping indication The cable vault door
1 2 3 4 5 6 7 8 9 压力表 组合电器操作面板 上面板锁孔 接地开关操作孔 负荷开关操作孔 电缆室门连锁孔 电缆室门 观察窗 分闸按钮 10 11 12 13 14 15 16 17 18

806
熔断器脱扣指示 出线机构 负荷开关 熔断器脱扣连锁 进(出)线套管 泄压阀 进(出)线电缆 电缆抱箍 熔断器仓堵盖 19 20 21 22 23 24 25 26 熔断器仓 接地开关

11 12 13 18 19 20 14 15
670

Line device Load switch Fuse trip chain The fuse chamber cover The fuse chamber Grounding switch Into (out of) bushing The pressure relief valve

A B C

Observation window 8

1700

7

16 17

Into (out of) cable Cable hoop

320

combined electrical apparatus unit structure diagram

6
第 一

3.3 RAG-12(B) Circuit-breaker unit –lower isolation project

The first system drawing

370

806 1 Pressure gauge 2 Breaker operation panel 3 The upper panel lock 4 The grounding switch operating hole 5 Load switch operating hole 6 Cable vault door chain hole 7 The cable vault door 8 Observation window 9 Breaker operating mechanism 10 Breaker 11 Agency chain plate 12 Isolating switch mechanism 13 Isolating switch 14 Into (out of) bushing 15 The pressure relief valve 16 Into (out of) cable 17 Cable hoop

1 2

9 10

3 4 5
A B C

11 12

1700

13 14 15

7 8

670

16 17

320

Circuit-breaker unit structural representation(lower isolation)

3.4 RAG-12(B) circuit breaker Switchgears—upperisolation subuject
7
第 一

The first system drawing

370

806
1 Pressure gauge 2 Breaker operation panel

1 3 4 5 2 6
1700

12 13 11 9 13 14 15
650

3 The upper panel lock 4 5 6 7 8 9 10 Breaker 11 Agency chain plate 12 Isolating switch mechanism 13 Isolating switch 14 Into (out of) bushing 15 The pressure relief valve 16 Into (out of) cable 17 Cable hoop Load switch operating hole Cable vault door chain hole The cable vault door Observation window

8

16 17

320

The circuit breaker unitstructural representation(upper isolation)

8
第 一

A brief introduction to technical programme:
1, The first system drawing:

一次系统图 Primary System Diagram

introduction:
1) Load switching unit use 3 working position load switching、with Manually operated spring mechanism; 2) The circuit breaker use upper isolation project,with disconnector with three positions 、Manually operated spring mechanism ;
? ?

The circuit unir with Self-powered type microcomputer protective device ,have Protection tripping functions。 3) Every unit has DXN、fault indicator; 4) Gas tank shell use 304# tainless steel shell welded on,leak(age)rate yrs≤0.5%; 9
第 一

5) Outdoor Switchgears shelluse 304# tainless steel shell welded on,four door。

2,outside view

A B C

A B C

户外高压环网柜 Outside HV Ring Main Units

户外高压环网柜 Outside HV Ring Main Units

高压危险

高压危险

高压危险

10
第 一