Technical Information

Cerabar M PMC51, PMP51, PMP55
Process pressure measurement Pressure transmitter with ceramic and metal sensors; With analog electronics or communication via HART, PROFIBUS PA or FOUNDATION Fieldbus

Application The Cerabar M pressure transmitter is used for the following measuring tasks: ? Absolute pressure and gauge pressure measurement in gases, steams or liquids in all areas of process engineering and process measurement technology ? Level, volume or mass measurements in liquids ? High process temperature – without diaphragm seals up to 130°C (266°F) – with diaphragm seals up to 400°C (752°F) ? High pressure up to 400 bar (6000 psi) ? International usage thanks to a wide range of approvals

Your benefits ? Very good reproducibility and long-term stability ? High reference accuracy: up to ±0.15%, as PLATINUM version: ±0.075% ? Turn down up to 100:1 ? End-to-end modularity for differential pressure, hydrostatics and pressure (Deltabar M – Deltapilot M – Cerabar M), e.g. – replaceable display – universal electronics ? Easy commissioning without the need for an operating tool ? Easy and safe menu-guided operation – on-site via display module – via 4 to 20 mA with HART – via PROFIBUS PA – via FOUNDATION Fieldbus ? Device versions compliant with ASME-BPE

TI00436P/00/EN/15.11 No. 71134874

Cerabar M PMC51, PMP51, PMP55

Table of contents
Function and system design. . . . . . . . . . . . . . . . . . . . . 4
Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Level measurement (level, volume and mass) . . . . . . . . . . . . . . . . 6 Electrical differential pressure measurement with gauge pressure sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 System integration (except analog electronics) . . . . . . . . . . . . . . . . 6 Communication protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Total performance – PMP51 . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Total error - PMP51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Thermal change in the zero output and the output span – PMP51 and PMP55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Operating conditions (installation) . . . . . . . . . . . . . . 25
General installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . Measuring arrangement for devices without diaphragm seal – PMC51, PMP51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measuring arrangement for devices with diaphragm seal – PMP55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wall and pipe mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . "Separate housing" version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Oxygen applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PWIS cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ultrapure gas applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Applications with hydrogen . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 25 25 25 26 27 27 27 27

Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Measured variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Measuring range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Explanation of terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Signal range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Load - 4 to 20 mA analog and 4 to 20 mA HART . . . . . . . . . . . . 11 Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Dead time, Time constant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Dynamic behavior: current output (analog electronics) . . . . . . . . 12 Dynamic behavior: current output (HART electronics) . . . . . . . . 12 Dynamic behavior: digital output (HART electronics) . . . . . . . . . 12 Dynamic behavior: PROFIBUS PA . . . . . . . . . . . . . . . . . . . . . . . . 13 Dynamic behavior: FOUNDATION Fieldbus . . . . . . . . . . . . . . . . 13 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Data of the FOUNDATION Fieldbus interface . . . . . . . . . . . . . . . 14

Operating conditions (environment) . . . . . . . . . . . . . 28
Ambient temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . Storage temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Climate class . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vibration resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electromagnetic compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . Overvoltage protection (optional) . . . . . . . . . . . . . . . . . . . . . . . . 28 28 28 28 29 29 29

Operating conditions (process) . . . . . . . . . . . . . . . . . 30
Process temperature range PMC51 . . . . . . . . . . . . . . . . . . . . . . . 30 Process temperature limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Pressure specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Start-up current HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Cable specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Residual ripple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Influence of power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Mechanical construction . . . . . . . . . . . . . . . . . . . . . . 32
F31 aluminum housing dimensions . . . . . . . . . . . . . . . . . . . . . . 32 F15 stainless steel housing dimensions (hygienic) . . . . . . . . . . . . 32 Process connections PMC51 (with ceramic process isolating diaphragm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Process connections PMP51 (with metal process isolating diaphragm) 41 PMP55 basic device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Process connections PMP55 (with diaphragm seal) . . . . . . . . . . . 47 Wall and pipe mounting with mounting bracket . . . . . . . . . . . . 64 Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64 Material (not wetted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Material (wetted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

Performance characteristics – general . . . . . . . . . . . . 19
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Uncertainty of measurement for small absolute pressure ranges . . 19 Long-term stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Influence of orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Warm-up period . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Performance characteristics – ceramic process isolating diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Reference accuracy – PMC51 . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Total performance – PMC51 . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Total error - PMC51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Thermal change in the zero output and the output span – PMC51 . 22

Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Onsite operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hardware and software for onsite and remote operation . . . . . . . 69 71 72 73

Planning instructions for diaphragm seal systems . . . 74
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function and design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diaphragm seal filling oils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating temperature range . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 74 75 76

Performance characteristics – metal process isolating diaphragm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reference accuracy – PMP51, PMP55 . . . . . . . . . . . . . . . . . . . . 23 2

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Installation instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 78
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ex approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Suitability for hygienic processes . . . . . . . . . . . . . . . . . . . . . . . . Pharma (CoC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CRN approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pressure Equipment Directive (PED) . . . . . . . . . . . . . . . . . . . . . Drinking water approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 78 78 78 78 78 78 78

Ordering information . . . . . . . . . . . . . . . . . . . . . . . . 79
PMC51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMC51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMC51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMC51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP51 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PMP55 (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 80 81 83 85 86 87 88 89 90 91 92 93 94

Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Technical Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brief Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation/Control Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . 95 95 95 95 96

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Shutoff valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Siphon . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Welding necks and Weld-in tool flanges . . . . . . . . . . . . . . . . . . . Mounting bracket for wall and pipe mounting . . . . . . . . . . . . . . M12 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 97 98 98 98

Configuration data sheet (HART, PROFIBUS PA, FOUNDATION Fieldbus electronics) . . . . . . . . . . . . 99
Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99 Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Configuration data sheet (analog electronics) . . . . . 101
Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

3

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Function and system design
Device selection
Cerabar M – Product family PMC51 PMP51 PMP55

P01-PMC51xxx-16-xx-xx-xx-000

P01-PMP51xxx-16-xx-xx-xx-000

P01-PMP55xxx-16-xx-xx-xx-000

With capacitive measuring cell and ceramic process isolating diaphragm (Ceraphire?) Field of application Process connections – Gauge pressure and absolute pressure – Level – – – – – Thread EN flanges DN 25 – DN 80 ANSI flanges 1" – 4" JIS flanges 50 A – 100 A Flush-mounted hygienic connections

With piezoresistive measuring cell With diaphragm seal and metal welded process isolating diaphragm

– – – – –

Thread EN flanges DN 25 – DN 80 ANSI flanges 1" – 4" JIS flanges 25 A – 100 A Prepared for diaphragm seal mount

– Wide range of diaphragm seals

Measuring ranges

From –100/0 to 100 mbar (–1.5/0 to 1.5 psi) to –1/0 to 40 bar (–15/0 to 600 psi) Max. 60 bar (900 psi) –40 to +130 °C (–40 to +266°F) For a maximum of 60 minutes: +150 °C (+302 °F)

From –400/0 to 400 mbar (–6/0 to 6 psi) to –1/0 to 400 bar (–15/0 to 6000 psi) Max. 600 bar (9000 psi) –40 to +125°C (–40 to +257°F) –70 to 400 °C (–94 to +752 °F) depending on the filling oil

OPL 1 Process temperature range

Ambient temperature range

– Without LCD display: -40 to +85°C (–40 to +185 °F) – With LCD display: –20 to +70°C (–4 to +158°F) (extended temperature application range (-40 to 85°C (-40 to 185°F)) with restrictions in optical properties such as display speed and contrast) – Separate housing: –20 to +60°C (–4 to +140°F) – Diaphragm seal systems depending on the version – Up to ±0.15% of the set span – PLATINUM version: up to ±0.075% of the set span – 11.5 to 45 V DC (versions with plug-in connection 35 V DC) – For intrinsically safe device versions: 11.5 to 30 V DC 4 to 20 mA, 4 to 20 mA with superimposed HART protocol – – – – – – – PMP51, PMP55: NACE-compliant materials PMC51, PMP51, PMP55: inspection certificate 2.2 or 3.1 or other certificates 3A approval and EHEDG approval Specific firmware versions Initial device settings Separate housing Broad range of accessories – Process connections with minimum oil volume – Gas-tight, elastomer-free – Wide range of diaphragm seals – For extreme medium temperatures – Process connections with minimum oil volume – Completely welded versions Up to ±0.15% of the set span

Reference accuracy Supply voltage Output Options

Specialties

– Metal-free measurement with PVDF connection – Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops

1)

OPL = over pressure limit; depends on the lowest-rated element, with regard to pressure, of the selected components

4

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Measuring principle
Ceramic process isolating diaphragm used in PMC51 (Ceraphire?) Metal process isolating diaphragm used in PMP51 and PMP55

?

?

? ?

? ? ? ?

p
P01-PMC71xxx-03-xx-xx-xx-000

p
P01-PMP7xxxx-03-xx-xx-xx-000

Ceramic sensor 1 2 3 4 Air pressure (gauge pressure sensors) Ceramic substrate Electrodes Ceramic process isolating diaphragm

Metal sensor 1 2 3 4 Silicon measuring element, substrate Wheatstone bridge Channel with fill fluid Metal process isolating diaphragm

Ceramic process isolating diaphragm used in PMC51 (Ceraphire?) The ceramic sensor is a dry sensor, i.e. the process pressure acts directly on the robust ceramic process isolating diaphragm and deflects it. A pressure-dependent change in capacitance is measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The measuring range is determined by the thickness of the ceramic process isolating diaphragm. Advantages: ? Guaranteed overload resistance up to 40 times the nominal pressure ? Thanks to ultrapure 99.9% ceramic (Ceraphire?, see also "www.endress.com/ceraphire") – extremely high chemical stability, comparable with Alloy C – less relaxation – high mechanical stability ? Can be used in absolute vacuum ? Outstanding surface finish, Ra ≤0.3 μm (11.8 μin) Metal process isolating diaphragm used in PMP51 and PMP55 PMP51 The operating pressure deflects the process isolating diaphragm and a fill fluid transfers the pressure to a resistance bridge (semiconductor technology). The pressure-dependent change in the bridge output voltage is measured and evaluated. Advantages: ? Can be used for process pressure up to 400 bar (6000 psi) ? High long-term stability ? Guaranteed overload resistance up to 4 times the nominal pressure ? Significantly less thermal effect compared to diaphragm seal systems PMP55 The operating pressure acts on the process isolating diaphragm of the diaphragm seal and is transferred to the process isolating diaphragm of the sensor by a diaphragm seal fill fluid. The process isolating diaphragm is deflected and a fill fluid transfers the pressure to a resistance bridge. The pressure-dependent change in the bridge output voltage is measured and evaluated. Advantages: ? Depending on the version, can be used for process pressure up to 400 bar (6000 psi) and simultaneous extreme process temperatures ? High long-term stability ? Guaranteed overload resistance up to 4 times the nominal pressure

Endress+Hauser

5

Cerabar M PMC51, PMP51, PMP55

Level measurement (level, volume and mass)

Function and design

p h= r g
h

P01-PMx5xxxx-15-xx-xx-xx-000

Level measurement h p ρ g Height (level) Pressure Density of the medium Gravitation constant

Your benefits ? ? ? ? Choice of different level measuring modes in the device software Volume and mass measurements in any tank shapes by means of a freely programmable characteristic curve Choice of diverse level units Has a wide range of uses, even in the following cases: – in the event of foam formation – in tanks with agitators or screen fittings – in the event of liquid gases

Electrical differential pressure measurement with gauge pressure sensors

Cerabar M
FXN 520

?
Fieldgate FXA520 Multidrop-Connector FXN520

? ?

P01-PMX51xxx-14-xx-xx-xx-001

1 2

Shut-off valves e.g. filter

In the example given, two Cerabar M devices (each with a gauge pressure sensor) are interconnected. The pressure difference can thus be measured using two independent Cerabar M devices.

"
System integration (except analog electronics)

Caution! If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory. The device can be fitted with a tag name and a preset bus address, see → ? 79 ff "Ordering information" feature 895 "Identification:" version "Z1" and "Z2".

6

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Communication protocol

? 4 to 20 mA without communication protocol (analog electronics) ? 4 to 20 mA with HART communication protocol ? PROFIBUS PA – The Endress+Hauser devices meet the requirements of the FISCO model. – Due to the low current consumption of 11 mA ± 1 mA, the following number of devices can be operated on one bus segment if installing as per FISCO: – up to 8 Cerabar M for Ex ia, CSA IS and FM IS applications – up to 31 Cerabar M for all other applications, e.g. in non-hazardous areas, Ex nA, etc. Further information on PROFIBUS PA can be found in Operating Instructions BA00034S "PROFIBUS DP/ PA: Guidelines for planning and commissioning" and in the PNO Guideline. ? FOUNDATION Fieldbus – The Endress+Hauser devices meet the requirements of the FISCO model. – Due to the low current consumption of 16 mA ± 1 mA, the following number of devices can be operated on one bus segment if installing as per FISCO: – up to 6 Cerabar M for Ex ia, CSA IS and FM IS applications – up to 22 Cerabar M for all other applications, e.g. in non-hazardous areas, Ex nA, etc. Further information on FOUNDATION Fieldbus, such as requirements for bus system components can be found in Operating Instructions BA00013S "FOUNDATION Fieldbus Overview".

Endress+Hauser

7

Cerabar M PMC51, PMP51, PMP55

Input
Measured variable ? Analog electronics: Absolute pressure and gauge pressure ? HART electronics: Absolute pressure and gauge pressure, from which level (level, volume or mass) is derived PMC51 – with ceramic process isolating diaphragm (Ceraphire?) for gauge pressure
Range limit Smallest calibratable span (preset at the factory) 1 MWP 2 OPL 3 Vacuum resistance Version in the order code4

Measuring range
Nominal value

lower (LRL) [bar (psi)] 100 mbar (1.5 psi) 250 mbar (4 psi) 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi) 40 bar (600 psi) –0.1 (–1.5) –0.25 (–4) –0.4 (–6) –1 (–15) –1 (–15) –1 (–15) –1 (–15) –1 (–15)

upper (URL) [bar (psi)] +0.1 (+1.5) +0.25 (+4) +0.4 (+6) +1 (+15) +2 (+30) +4 (+60) +10 (+150) +40 (+600) [bar (psi)] 0.01 (0.15) 0.01 (0.15) 0.02 (0.3) 0.05 (1) 0.1 (1.5) 0.2 (3) 0.5 (7.5) 2 (30) [bar (psi)] 2.7 (40.5) 3.3 (49.5) 5.3 (79.5) 6.7 (100.5) 12 (180) 16.7 (250.5) 26.7 (400.5) 40 (600) [bar (psi)] 4 (60) 5 (75) 8 (120) 10 (150) 18 (270) 25 (375) 40 (600) 60 (900) [barabs (psiabs)] 0.7 (10.5) 0.5 (7.5) 0 0 0 0 0 0 1C 1E 1F 1H 1K 1M 1P 1S

PMC51 – with ceramic process isolating diaphragm (Ceraphire?) for absolute pressure
Nominal value Range limit Smallest span (factory calibration)1 MWP 2 OPL 3 Vacuum resistance Version in the order code4

lower (LRL)

upper (URL) [barabs (psiabs)] 2.7 (40.5) 3.3 (49.5) 5.3 (79.5) 6.7 (100.5) 12 (180) 16.7 (250.5) 26.7 (400.5) 40 (600) [barabs (psiabs)] [barabs (psiabs)] 4 (60) 5 (75) 8 (120) 10 (150) 18 (270) 25 (375) 40 (600) 60 (900) 0 0 0 0 0 0 0 0 2C 2E 2F 2H 2K 2M 2P 2S

[barabs (psiabs)] [barabs (psiabs)] [bar (psi)] 100 mbar (15 psi) 250 mbar (4 psi) 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi) 40 bar (600 psi) 1) 2) 0 0 0 0 0 0 0 0 +0.1 (+1.5) +0.25 (+4) +0.4 (+6) +1 (+15) +2 (+30) +4 (+60) +10 (+150) +40 (+600) 0.01 (0.15) 0.01 (0.15) 0.02 (0.3) 0.05 (1) 0.1 (1.5) 0.2 (3) 0.5 (7.5) 2 (30)

Recommended turn down: Max 10:1. Factory calibration turn down: Max 20:1, higher on request or configurable in the device. The MWP (maximum working pressure) for the measuring device depends on the lowest-rated element, with regard to pressure, of the selected components, i.e. the process connection (→ ? 32 ff) has to be taken into consideration in addition to the measuring cell (→ see Table above). Pay attention to the pressure-temperature dependence also. For the appropriate standards and other information, see → ? 31, "Pressure specifications" section. OPL: over pressure limit depends on the lowest-rated element, with regard to pressure, of the selected components Version in the order code → see also → ? 79 ff, feature 70 "Sensor range"

3) 4)

8

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP51 and PMP55 – metal process isolating diaphragm for gauge pressure
Nominal value Range limit Smallest calibratable span (preset at the factory) 1 MWP 2 OPL 3 Vacuum resistance 4 Silicone oil/ Inert oil Version in the order code5

lower (LRL) [bar (psi)] 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi) 40 bar (600 psi) 100 bar (1500 psi) 400 bar (6000 psi) –0.4 (–6) –1 (–15) –1 (–15) –1 (–15) –1 (–15) –1 (–15) –1 (–15) –1 (–15)

upper (URL) [bar (psi)] +0.4 (+6) +1 (+15) +2 (+30) +4 (+60) +10 (+150) +40 (+600) +100 (+1500) +400 (+6000) [bar (psi)] 0.02 (0.3) 0.05 (1) 0.1 (1.5) 0.2 (3) 0.5 (7.5) 2 (30) 5 (75) 20 (300) [bar (psi)] 4 (60) 6.7 (100) 13.3 (200) 18.7 (280.5) 26.7 (400.5) 100 (1500) 100 (1500) 400 (6000) [bar (psi)] 6 (90) 10 (150) 20 (300) 28 (420) 40 (600) 160 (2400) 400 (6000) 600 (9000) 0.01/0.04 (0.15/0.6) [barabs (psiabs)] 1F 1H 1K 1M 1P 1S 1U 1W

PMP51 and PMP55 – metal process isolating diaphragm for absolute pressure
Nominal value Range limit Smallest calibratable span (preset at the factory) 1 MWP 2 OPL 3 Vacuum resistance 4 Silicone oil/ Inert oil Version in the order code 5

lower (LRL) [barabs (psiabs)] 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi) 40 bar (600 psi) 100 bar (1500 psi) 400 bar (6000 psi) 1) 2) 0 0 0 0 0 0 0 0

upper (URL) [barabs (psiabs)] +0.4 (+6) +1 (+15) +2 (+30) +4 (+60) +10 (+150) +40 (+600) +100 (+1500) +400 (+6000) [bar (psi)] 0.02 (0.3) 0.05 (1) 0.1 (1.5) 0.2 (3) 0.5 (7.5) 2 (30) 5 (75) 20 (300) [barabs (psiabs)] [barabs (psiabs)] [barabs (psiabs)] 4 (60) 6.7 (100) 13.3 (200) 18.7 (280.5) 26.7 (400.5) 100 (1500) 100 (1500) 400 (6000) 6 (90) 10 (150) 20 (300) 28 (420) 40 (600) 160 (2400) 400 (6000) 600 (9000) 0.01/0.04 (0.15/0.6) 2F 2H 2K 2M 2P 2S 2U 2W

Recommended turn down: Max 10:1. Factory calibration turn down: Max 20:1, higher on request or configurable in the device. The MWP (maximum working pressure) for the measuring device depends on the lowest-rated element, with regard to pressure, of the selected components, i.e. the process connection (→ ? 32 ff) has to be taken into consideration in addition to the measuring cell ( → see Table above). Pay attention to the pressure-temperature dependence also. For the appropriate standards and other information, see → ? 31, "Pressure specifications" section. OPL: over pressure limit (= sensor overload limit) The vacuum resistance applies to the measuring cell at reference conditions. The pressure and temperature application limits of the selected filling oil must also be observed for the PMP55. → ? 75, "Diaphragm seal filling oils" section. Version in the order code → ? 79 ff, feature 70 "Sensor range"

3) 4) 5)

Endress+Hauser

9

Cerabar M PMC51, PMP51, PMP55

Explanation of terms

Explanation of terms: turn down (TD), set span and span based on zero point Case 1: ? ?Lower range value (LRV)? ≤ ?Upper range value (URV)? Example: ? Lower range value (LRV) = 0 bar ? Upper range value (URV) = 0.5 bar (7.5 psi) ? Nominal value (URL) = 1 bar (15 psi) Turn down: ? TD = URL / ?URV? = 2:1 Set span: ? URV – LRV = 0.5 bar (7.5 psi) This span is based on the zero point.

?=?
LRL = LRV 0 bar URV 0.5 bar URL +1 bar

? ?=?
P01-PMx7xxxx-05-xx-xx-xx-012

Example: 1 bar (15 psi) measuring cell

Case 2: ? ?Lower range value (LRV)? ≤ ?Upper range value (URV)? Example: ? Lower range value (LRV) = 0 bar ? Upper range value (URV) = 0.5 bar (7.5 psi) ? Nominal value (URL) = 1 bar (15 psi) Turn down: ? TD = URL / ?URV? = 2:1 Set span: ? URV – LRV = 0.5 bar (7.5 psi) This span is based on the zero point.

?=?
LRL –1 bar LRV 0 URV 0.5 bar URL +1 bar

? ? ?
P01-PMx7xxxx-05-xx-xx-xx-007.

Example: 1 bar (15 psi) measuring cell

Case 3: ? ?Lower range value (LRV)? ≥ ?Upper range value (URV)? Example: ? Lower range value (LRV) = –0.6 bar (–9 psi) ? Upper range value (URV) = 0 bar ? Nominal value (URL) = 1 bar (15 psi) Turn down: ? TD = URL / ?LRV? = 1.67:1 Set span: ? URV – LRV = 0.6 bar (–9 psi) This span is based on the zero point.

?=?
LRL –1 bar LRV –0.6 bar URV 0 URL +1 bar

? ? ?
P01-PMx7xxxx-05-xx-xx-xx-008

Example: 1 bar (15 psi) measuring cell 1 2 3 4 5 LRL URL LRV URV Set span Span based on zero point Nominal value i upper range limit (URL) Nominal measuring range Sensor measuring range Lower range limit Upper range limit Lower range value Upper range value

10

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Output
Output signal ? ? ? ? 4 to 20 mA analog, 2-wire 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire Digital communication signal PROFIBUS PA (Profile 3.02) Digital communication signal FOUNDATION Fieldbus

Signal range Signal on alarm

4 to 20 mA analog, 4 to 20 mA HART: 3.8 to 20.5 mA As per NAMUR NE 43 ? 4 to 20 mA Analog: – Signal overshoot: > 20.5 mA – Signal undershoot: < 3.8 mA – Min Alarm (3.6 mA) ? 4 to 20 mA HART Options: – Max. alarm: can be set from 21 to 23 mA (factory setting: 22 mA) – Hold measured value: last measured value is held – Min. alarm: 3.6 mA ? PROFIBUS PA: can be set in the Analog Input block, Options: Last Valid Out Value (factory setting), Fail-safe Value, Status Bad ? FOUNDATION Fieldbus: can be set in the Analog Input block, Options: Last Good Value, Fail-safe Value (factory setting), Wrong Value

Load - 4 to 20 mA analog and 4 to 20 mA HART

RLmax [W] 1456 1239 804 369

? ?
20 30 U – 11.5 V 0.023 A
P01-xxxxxxxx-05-xx-xx-xx-002

11.5

40 45

U [V]

RLmax ?
Load diagram 1 2 RLmax U

Power supply 11.5 to 30 V DC for intrinsically safe device versions Power supply 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and for uncertified device versions Maximum load resistance Supply voltage

Note! When operating via a handheld terminal or via a PC with an operating program, a minimum communication resistance of 250 Ω must be taken into account. Resolution ? Current output: 1 μA ? Display HART: can be set (factory setting: presentation of the maximum accuracy of the transmitter)

Endress+Hauser

11

Cerabar M PMC51, PMP51, PMP55

Dead time, Time constant
I 100 % 90 % 63 %

t1

t2 t3

t

P01-xxxxxxxx-05-xx-xx-xx-036

Presentation of the dead time and the time constant

Dynamic behavior: current output (analog electronics)

Type max. max. max. PMC51 PMP51 PMP55

Dead time (t1) [ms] 60 40

Time constant T63 (= t2) [ms] 40 40

Time constant T90 (= t3) [ms] 50 50

PMP51 + influence of the diaphragm seal

Dynamic behavior: current output (HART electronics)

Type max. max. max. PMC51 PMP51 PMP55

Dead time (t1) [ms] 50 50

Time constant T63 (= t2) [ms] 85 75

Time constant T90 (= t3) [ms] 200 185

PMP51 + influence of the diaphragm seal

Dynamic behavior: digital output (HART electronics)

Dead time, time constant (T63) A typical configuration for the PLC of 2 to 3 values per second results in the following total dead time:
Type min. PMC51 max. min. PMP51 max. max. PMP55 1010 1085 1145 PMP51 + influence of the diaphragm seal 1010 210 1095 285 1160 345 Dead time (t1) [ms] 210 Dead time (t1) [ms] + Time constant T63 (= t2) [ms] 295 Dead time (t1) [ms] + Time constant T90 (= t3) [ms] 360

Reading cycle ? Acyclic: max. 3/s, typical 1/s (depends on command # and number of preambles) ? Cyclic (Burst): max. 3/s, typical 2/s The Cerabar M commands the BURST MODE function for cyclic value transmission via the HART communication protocol. Cycle time (Update time) Cyclic (Burst): min. 300 ms Response time ? Acyclic: min. 330 ms, typical 590 ms (depends on command # and number of preambles) ? Cyclic (Burst): min. 160 ms, typical 350 ms (depends on command # and number of preambles)

12

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Dynamic behavior: PROFIBUS PA
min.

Type

Dead time (t1) [ms] 85

Dead time (t1) [ms] + Time constant T63 (= t2) [ms] 170 1270 160 1260

Dead time (t1) [ms] + Time constant T90 (= t3) [ms] 235 1335 220 1320

PMC51 max. min. PMP51 max. max. PMP55 1185 PMP51 + influence of the diaphragm seal 1185 85

Reading cycle ? Cyclic: max. 30/s (dependent on the number and type of function blocks used in a closed-control loop) ? Acyclic: typical 25/s Cycle time (update time) min. 100 ms The cycle time in a bus segment in cyclic data communication depends on the number of devices, on the segment coupler used and on the internal PLC cycle time. Response time ? Cyclic: approx. 8 to 13 ms (depends on Min. Slave Interval) ? Acyclic: approx. 23 to 35 ms (depends on Min. Slave Interval) Dynamic behavior: FOUNDATION Fieldbus
min. PMC51 max. min. PMP51 max. max. PMP55 1095 1170 1230 PMP51 + influence of the diaphragm seal 1095 95 1180 170 1245 230 Type Dead time (t1) [ms] 95 Dead time (t1) [ms] + Time constant T63 (= t2) [ms] 180 Dead time (t1) [ms] + Time constant T90 (= t3) [ms] 245

Reading cycle ? Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control loop) ? Acyclic: typical 5/s Cycle time (update time) Cyclic: min. 100 ms Response time ? Cyclic: max. 20 ms (for standard bus parameter settings) ? Acyclic: typical 70 ms (for standard bus parameter settings) Damping A damping affects all outputs (output signal, display). ? Via on-site display, handheld terminal or PC with operating program, continuous from 0...999 s ? Via DIP-switch on the electronic insert, switch position "on" (= set value) and "off" (= damping switched off) ? Factory setting: 2 s

Endress+Hauser

13

Cerabar M PMC51, PMP51, PMP55

Data of the FOUNDATION Fieldbus interface

Basic data
Device Type Device Revision DD Revision CFF Revision ITK Version ITK Certification Driver No. Link-Master (LAS) capable Link Master / Basic Device selectable Number of VCRs Number of Link Objects in VFD Number of FB-Schedule Objects 0x1019 01 (hex) 0x01021 0x000102 5.2.0 IT067700 Yes Yes; Factory setting: Basic Device 44 50 40

Virtual communication references (VCRs)
Permanent Entries Client VCRs Server VCRs Source VCRs Sink VCRs Subscriber VCRs Publisher VCRs 44 0 5 8 0 12 19

Link settings
Slot time Min. inter PDU delay Max. response delay 4 12 40

Transducer Blocks
Block TRD1 Block Content Contains all parameters related to the measurement Output values ? ? ? ? ? Pressure or level (channel 1) Process temperature (channel 2) Measured pressure value (channel 3) Max. pressure (channel 4) Level before linearization (channel 5)

Diagnostic Block Contains diagnostic information Display Block Contains parameters to configure the onsite display

Error code via DI channels (channel 10 to 15) No output values

14

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Function blocks
Block Content Number Execution time of blocks 1 Functionality enhanced

Resource Block The Resource Block contains all the data that uniquely identify the device. It is an electronic version of a nameplate of the device. Analog Input Block 1 Analog Input Block 2 Digital Input Block Digital Output Block The AI Block receives the measuring data from the Sensor Block, (selectable via a channel number) and makes the data available to other function blocks at its output. Enhancement: digital outputs for process alarms, fail safe mode.

2

25 ms

enhanced

This block contains the discrete data of the Diagnose 1 Block (selectable via a channel number 10 to 15) and provides them for other blocks at the output. This block converts the discrete input and thus initiates an action (selectable via a channel number) in the DP Flow Block or in the im TRD1 Block. Channel 20 resets the counter for max. pressure transgressions value and Channel 21 resets the Totalizer. 1

20 ms

standard

20 ms

standard

PID Block

The PID Block serves as a 1 proportional-integral-derivative controller and is used almost universally for closed-loop-control in the field including cascade and feedforward. Input IN can be indicated on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_CONTENT). This block is designed to permit simple use of popular 1 measurement math functions. The user does not have to know how to write equations. The math algorithm is selected by name, chosen by the user for the function to be performed. The Input Selector Block facilitates the selection of up 1 to four inputs and generates an output based on the configured action. This block normally receives its inputs from AI Blocks. The block performs maximum, minimum, average and ‘first good’ signal selection. Inputs IN1 to IN4 can be indicated on the display. The selection is performed in the Display Block (DISPLAY_MAIN_LINE_1_CONTENT). The Signal Characterizer Block has two sections, each with an output that is a non-linear function of the respective input. The non-linear function is generated by a single look-up table with 21 arbitrary x-y pairs. 1

40 ms

standard

Arithmetic Block

35 ms

standard

Input Selector Block

30 ms

standard

Signal Characterizer Block

40 ms

standard

Integrator Block

The Integrator Block integrates a variable as a 1 function of the time or accumulates the counts from a Pulse Input Block. The block may be used as a totalizer that counts up until reset or as a batch totalizer that has a setpoint, where the integrated or accumulated value is compared to pre-trip and trip settings, generating a binary signal when the setpoint is reached.

35 ms

standard

Additional function block information: Instantiate Function Block Number of instantiate blocks YES 14

Endress+Hauser

15

Cerabar M PMC51, PMP51, PMP55

Power supply
Electrical connection Note! ? When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings. → ? 95 ff, "Safety Instructions" and "Installation/Control Drawings" sections. ? According to IEC/EN61010 a suitable disconnector has to be installed for the device ? HART: Overvoltage protection HAW569Z for the non-hazardous area and for ATEX II 1/2 G Exi can be ordered as an option (see "Ordering information" section). ? Protective circuits against reverse polarity, HF influences and overvoltage peaks are installed. ? The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the power supply.

1 7

- +
6 2 5 4

3
P01-xMx5xxxx-04-xx-xx-xx-004

Electrical connection 1 2 3 4 5 6 7 External grounding terminal Internal grounding terminal Supply voltage → ? 18 4...20 mA for HART devices For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be configured anywhere along the bus line via menu operation. Terminals For HART devices: test terminals, see section "Taking 4 to 20 mA test signal"

4 to 20 mA Analog, 4 to 20 mA HART Taking 4 to 20 mA test signal A 4 to 20 mA test signal may be measured via the test terminals without interrupting the measurement. PROFIBUS PA For further information on the network structure and grounding, and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning" and the PNO Guideline. Cable specifications: Use a twisted, shielded two-wire cable, preferably cable type A Note! For further information on the cable specifications, see Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092

16

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP). FOUNDATION Fieldbus The digital communication signal is transmitted to the bus via a 2-wire connection. The bus also provides the power supply. For further information on the network structure and grounding and for further bus system components such as bus cables, see the relevant documentation, e.g. Operating Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus Guideline. Cable specifications: Use a twisted, shielded two-wire cable, preferably cable type A Note! For further information on the cable specifications, see Operating Instructions BA00013S "FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP). Devices with valve connector

+ –



+

+ –
P01-xMx5xxxx-04-xx-xx-xx-005

Left: electrical connection for devices with a valve connector Right: view of the connector at the device

Material: PA 6.6 Devices with Harting plug Han7D

+
+ –



7 8 1 2 5 3 4 6

Han7D

+ –
P01-xMD7xxxx-04-xx-xx-xx-000

Left: electrical connection for devices with Harting plug Han7D Right: view of the plug connector at the device

Material: CuZn

Endress+Hauser

17

Cerabar M PMC51, PMP51, PMP55

Devices with M12 plug PIN assignment for M12 connector
PIN 1 Meaning Signal + Not assigned Signal – Earth

4 1

3
+ 2



2 3 4
A0011175

nc

Endress+Hauser offers the following accessories for devices with an M12 plug: Plug-in jack M 12x1, straight ? Material: body PA; coupling nut CuZn, nickel-plated ? Degree of protection (fully locked): IP67 ? Order number: 52006263 Plug-in jack M 12x1, elbowed ? Material: body PBT/PA; coupling nut GD-Zn, nickel-plated ? Degree of protection (fully locked): IP67 ? Order number: 71114212 Cable 4x0.34 mm? (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft) ? Material: body PUR; coupling nut CuSn/Ni; cable PVC ? Degree of protection (fully locked): IP67 ? Order number: 52010285 Devices with 7/8" plug PIN assignment for 7/8" connector
PIN 1 Meaning Signal – Signal + Not assigned Earth

1 2

– 3

nc

2 3 4
A0011176

+ 4

External thread: 7/8 - 16 UNC ? Material: housing / body CuZn, nickel-plated ? Protection: IP68 ? Order number: 52010285 Cable gland
Approval Standard, II1/2G Exia, IS ATEX II1/2D, II1/2GD Exia, II3G Ex nA Type Plastic M20x1.5 Metal M20x1.5 (Ex e) Clamping area 5 to 10 mm (0.2 to 0.39 in) 7 to 10.5 mm (0.28 to 0.41 in)

Terminals For wire cross-sections of 0.5 to 2.5 mm? (20 to 14 AWG). Supply voltage Note! ? When using the measuring device in hazardous areas, installation must comply with the corresponding national standards and regulations and the Safety Instructions or Installation or Control Drawings.

18

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

? All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas. → ? 95 ff, "Safety Instructions" and "Installation/Control Drawings" sections. 4 to 20 mA, 4 to 20 mA HART
Type of protection ? Intrinsically safe ? Other types of protection ? Devices without certificate Supply voltage 11.5 ... 30 V DC 11.5 ... 45 V DC (Versions with plug-in connection 35 V DC)

PROFIBUS PA ? Version for non-hazardous areas: 9 to 32 V DC FOUNDATION Fieldbus ? Version for non-hazardous areas: 9 to 32 V DC Start-up current HART Current consumption 12 mA or 22 mA (selectable) ? PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 ? FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21 → ? 79 ff, feature 50 "Electrical connection". ? Endress+Hauser recommends using twisted, shielded two-wire cables. ? Terminals for wire cross-sections 0.5 to 2.5 mm2 (20 to 14 AWG) ? Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) No influence on 4 to 20 mA signal up to ± 5 % residual ripple within the permitted voltage range [according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)] ≤ 0.001% of URL/1 V

Cable entry Cable specification

Residual ripple

Influence of power supply

Performance characteristics – general
Reference operating conditions ? ? ? ? ? ? ? ? ? ? ? ? As per IEC 60770 Ambient temperature TA = constant, in the range of: +21 to +33°C (+70 to +91°F) Humidity ? = constant, in the range of: 5 to 80 % RH Ambient pressure pA = constant, in the range of: 860 to 1060 mbar (12.47 to 15.37 psi) Position of the measuring cell: constant, in range: ±1° horizontally Input of LOW SENSOR TRIM and HIGH SENSOR TRIM for lower range value and upper range value Span based on zero point Material of the process isolating diaphragm PMC51: Al2O3 (aluminum-oxide ceramic, Ceraphire?) Material of the process isolating diaphragm PMP51 and PMP55: AISI 316L Filling oil PMP51 and PMP55: silicone oil Supply voltage: 24 V DC ± 3 V DC Load with HART: 250 Ω

Uncertainty of measurement for small absolute pressure ranges

The smallest expanded uncertainty of measurement that can be returned by our standards is: ? 0.4% of the measured value in the range of 1 to 30 mbar ? 1% of the measured value in the range < 1 mbar.

Endress+Hauser

19

Cerabar M PMC51, PMP51, PMP55

Long-term stability

PMC51 PMC51 with thread or flange

Measuring range < 1 bar (15 psi) > 1 bar (15 psi)

Long-term stability of URL / 1 year ±0.2 % ±0.1 %

PMC51 with hygienic process connection

< 1 bar (15 psi) > 1 bar (15 psi)

±0.35 % ±0.2 %

PMP51 < 1 bar (15 psi) > 1 bar to 10 bar (15 to 150 psi) 40 bar (600 psi) 100 bar (1500 psi) 400 bar (6000 psi)

Long-term stability of URL / 1 year ±0.2 % ±0.1 % ±0.1 % ±0.1 % ±0.1 %

Influence of orientation
3
90 °

?

?

90

°

P01-PMD55xxx-17-xx-xx-xx-001

Measuring error in mbar (psi)
? Axis of the diaphragm perpendicular ? Diaphragm points up PMC51 PMP51 with process connections 1/2" thread and silicone oil PMP51 with process connections > thread 1/2" and flanges Calibration position, no measuring error < +0.2 mbar (0.003 psi) < +4 mbar (0.06 psi) < +10 mbar (0.145 psi) This value is doubled for inert oil. ? Diaphragm points down < -0.2 mbar (0.003 psi) < -4 mbar (0.06 psi) < -10 mbar (0.145 psi) This value is doubled for inert oil.

Note! Position-dependent zero point shift can be corrected at the device. → ? 25, "General installation instructions" section and → ? 76 ff, "Installation instructions" section. Warm-up period ? ? ? ? 4 to 20 mA analog: ≤1.5 s 4 to 20 mA HART: ≤5 s PROFIBUS PA: ≤8 s FOUNDATION Fieldbus: ≤20 s (after a TOTAL-reset ≤45 s)

20

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Performance characteristics – ceramic process isolating diaphragm
Reference accuracy – PMC51 The reference accuracy comprises the non-linearity according to limit point setting, hysteresisand non-reproducibility as per IEC 60770. The data refer to the calibrated span.
Gauge pressure sensors Measuring cell 100 mbar (1.5 psi) 250 mbar (4 psi), 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) 40 bar (600 psi) Standard reference accuracy Platinum reference accuracy

? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 20:1 = 0.20 % ? TD > 10:1 to TD 13:1 = ±0.1 % ? TD > 20:1 = ±(0.05 + 0.0075 x TD) ? TD > 13:1 = ±0.015 x TD ? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD > 10:1 to TD 20:1 = 0.20 % ? TD > 20:1 = ±(0.1 + 0.005 x TD) ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 20:1 = ±0.1 % ? TD > 20:1 = ±0.005 x TD

? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 20:1 = 0.20 % ? TD > 10:1 to TD 13:1 = ±0.1 % ? TD > 20:1 = ±(0.05 + 0.0075 x TD) ? TD > 13:1 = ±0.0075 x TD

Absolute pressure sensors Measuring cell 100 mbar (1.5 psi) Standard reference accuracy ? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD > 10:1 to TD 13:1 = 0.20 % ? TD > 13:1 = ±0.0015 x TD ? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD > 10:1 to TD 20:1 = 0.20 % Platinum reference accuracy ? TD 1:1 to TD 5:1 = ±0.075 % ? TD > 5:1 = ±0.0015 x TD ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 13:1 = ±0.1 %

250 mbar (4 psi) 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi) 40 bar (600 psi)

? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 20:1 = 0.20 % ? TD > 10:1 to TD 20:1 = ±0.1 % ? TD > 20:1 = ±(0.05 + 0.0075 x TD) ? TD > 13:1 = ±0.0075 x TD ? TD 1:1 to ≤ TD 10:1 = 0.15 % ? TD 1:1 to ≤ TD 10:1 = ±0.075 % ? TD > 10:1 to TD 20:1 = 0.20 % ? TD > 10:1 to TD 13:1 = ±0.1 % ? TD > 20:1 = ±(0.05 + 0.0075 x TD) ? TD > 13:1 = ±0.0075 x TD

Total performance – PMC51

The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as well as the thermal change in the zero point. All specifications apply to the temperature range –10 to +60°C (+14 to +140°F).
Signal output Measuring cell % URL ±0.575 x TD ±0.5 x TD ±0.775 x TD ±0.7 x TD

HART, PROFIBUS PA, 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) FOUNDATION 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) Fieldbus 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) Analog (4 to 20 mA) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi)

Endress+Hauser

21

Cerabar M PMC51, PMP51, PMP55

Total error - PMC51

The total error comprises the long-term stability and the total performance. All specifications apply to the temperature range –10 to +60°C (+14 to +140°F) and Turndown 1:1.
Signal output Measuring cell % URL 1 year

PMC51 with thread or flange

HART, PROFIBUS PA, FOUNDATION Fieldbus Analog (4 to 20 mA)

100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi)

±0.55 ±0.47 ±0.75 ±0.67

PMC51 with hygienic process connection

HART, PROFIBUS PA, FOUNDATION Fieldbus Analog (4 to 20 mA)

100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi)

±0.925 ±0.7 ±1.125 ±0.9

Thermal change in the zero output and the output span – PMC51
Signal output

PMC51 with thread or flange

Measuring cell

% of the calibrated measuring span –40 to -20°C (–40 to –4°F) –10 to +60°C (+14 to +140°F) ±0,2 + 0,275 x TD ±0,1 + 0,15 x TD ±0.4 + 0.275 x TD ±0.3 + 0.15 x TD –20 to +100°C (–4 to +212°F) ±(0,4 + 0,425 x TD) ±(0,225 + 0,525 x TD) ±0.7 + 0.425 x TD ±0.525 + 0.525 x TD

HART, PROFIBUS PA, FOUNDATION Fieldbus

100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi)

±(0,6 + 0,45 x TD) ±0,5 + 0,35 x TD ±(0,6 + 0,45 x TD) ±0,5 + 0,35 x TD

Analog (4 to 20 mA)

PMC51 with hygienic process connection
Signal output Measuring cell % of the calibrated measuring span –10 to +60°C (+14 to +140°F) HART, PROFIBUS PA, FOUNDATION Fieldbus 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) 100 mbar (1.5 psi), 250 mbar (4 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi) ±(0,4 + 0,275 x TD) ±(0,3 + 0,15 x TD) ±(0,4 + 0,275 x TD) ±(0,3 + 0,15 x TD) –20 to +130°C (–4 to +266°F) ±(0,7 + 0,425 x TD) ±(0,525 + 0,525 x TD) ±(0,7 + 0,425 x TD) ±(0,525 + 0,525 x TD)

Analog (4 to 20 mA)

22

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Performance characteristics – metal process isolating diaphragm
Reference accuracy – PMP51, PMP55 The reference accuracy comprises the non-linearity according to limit point setting, hysteresisand non-reproducibility as per IEC 60770. The data refer to the calibrated span. Gauge pressure sensors/absolute pressure sensors
PMP51 and PMP55 without capillary Measuring cell 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) Standard reference accuracy ? TD 1:1 = ±0.15 % ? TD >1:1 = ±0.15 % x TD ? TD 1:1 to TD 5:1 = ±0.15 % ? TD >5:1 = ±0.03 % x TD ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 = ±0.015 % x TD ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.075 % x TD + 0.05 ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.005 % x TD + 0.1) ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.075 % x TD + 0.05) ? TD 1:1 to TD 5:1 = ±0.15 % ? TD >5:1 = ±(0.03 % x TD) Platinum reference accuracy Not available ? TD 1:1 to TD 2.5:1 = ±0.075 % ? TD >2.5:1 = ±0.03 % x TD ? TD 1:1 to TD 5:1 = ±0.075 % ? TD >5:1 = ±0.015 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 13.3:1 = ±0.1 % ? TD >13.3:1 = ±0.0075 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 20:1 = ±0.1 % ? TD >20:1 = ±0.005 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 13.3:1 = ±0.1 % ? TD >13.3:1 = ±0.0075 % x TD ? TD 1:1 to TD 5:1 = ±0.15 % ? TD >5:1 = ±(0.03 % x TD)
1)

4 bar (60 psi)

10 bar (150 psi), 40 bar (600 psi)

100 bar (1500 psi)

400 bar (6000 psi)

1)

Only PMP51, PMP55 with direct diaphragm seal mounting

Gauge pressure sensors/absolute pressure sensors
PMP55 with capillary Measuring cell 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) Standard reference accuracy ? TD 1:1 = ±0.15 % ? TD >1:1= ±0.15 % x TD ? TD 1:1 to TD 3.75:1 = ±0.15 % ? TD >3.75:1 = ±0.04 % x TD ? TD 1:1 to TD 3.75:1 = ±0.15 % ? TD >3.75:1 = ±0.04 % x TD ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.0075 % x TD + 0.05) ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.005 % x TD + 0.1) ? TD 1:1 to TD 10:1 = ±0.15 % ? TD >10:1 to TD 20:1 = ±0.20 % ? TD >20:1 = ±(0.075 % x TD + 0.05) ? TD 1:1 to TD 5:1 = ±0.15 % ? TD >5:1 = ±(0.03 % x TD) Platinum reference accuracy Not available ? TD 1:1 to TD 2:1 = ±0.1 % ? TD >2:1 = ±0.04 % x TD ? TD 1:1 to TD 2.5:1 = ±0.1 % ? TD >2.5:1 = ±0.04 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 13.3:1 = ±0.1 % ? TD >13.3:1 = ±0.0075 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 20:1 = ±0.1 % ? TD >20:1 = ±0.005 % x TD ? TD 1:1 to TD 10:1 = ±0.075 % ? TD 10:1 to TD 13.3:1 = ±0.1 % ? TD >13.3:1 = ±0.0075 % x TD ? TD 1:1 to TD 5:1 = ±0.15 % ? TD >5:1 = ±(0.03 % x TD)
1)

4 bar (60 psi)

10 bar (150 psi), 40 bar (600 psi)

100 bar (1500 psi)

400 bar (6000 psi)

1)

Only PMP51, PMP55 with direct diaphragm seal mounting

Endress+Hauser

23

Cerabar M PMC51, PMP51, PMP55

Total performance – PMP51

The "Total performance" specification comprises the non-linearity including hysteresis, non-reproducibility as well as the thermal change in the zero point. All specifications apply to the temperature range –10 to +60°C (+14 to +140°F) and Turndown 1:1.
Measuring cell PMP51 PMP51 with gold/rhodium-coated process isolating diaphragm % of URL 400 mbar (6 psi) 1 bar (15 psi) 2 bar (30 psi) 4 bar (60 psi) 10 bar (150 psi), 40 bar (600 psi), 100 bar (1500 psi) 400 bar (6000 psi) ±0.30 ±0.25 ±0.4 ±0.34 ±1.25 ±0.75 ±0.45 ±0.3 ±0.25 ±0.4

Total error - PMP51

The total error comprises the long-term stability and the total performance. All specifications apply to the temperature range –10 to +60°C (+14 to +140°F) and Turndown 1:1.
Measuring cell 400 mbar (6 psi) ≥1 bar to 100 bar (15 psi to 1500 psi) 400 bar (6000 psi) % of URL/year ±0.44 ±0.35 ±0.5

Thermal change in the zero output and the output span – PMP51 and PMP55

Note! When using a PMP55, the influence from the respective diaphragm seal must also be taken into account (→ ? 74 ff "Planning instructions for diaphragm seal systems"). PMP51 and PMP55 (basic device)
Measuring cell –10 to +60 °C (+14 to +140°F) –40 to –10°C, +60 to +85°C (–40 to +14°F, +140 to +185°F)

% of the calibrated measuring span 400 mbar (6 psi), 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), 10 bar (150 psi), 40 bar (600 psi), 100 bar (1500 psi) 400 bar (6000 psi)

±(0.34 + 0.15 x TD)

±(0.4 + 0.25 x TD)

±(0.3 + 0.35 x TD)

±(0.3 + 0.7 x TD)

24

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Operating conditions (installation)
General installation instructions ? The position-dependent zero point shift can be corrected: – directly at the device via operating keys on the electronic insert – directly at the device via operating keys on the display (except analog electronics) – via digital communication if the cover is not open (except analog electronics) Note! In hazardous areas, comply strictly with the safety instructions when the housing cover is closed and open. ? Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. See also → ? 25, "Wall and pipe mounting" section. ? Use flushing rings for flange and cell diaphragm seals if medium buildup or clogging can be expected at the diaphragm seal connection. The flushing ring can be inserted between the process connection and the diaphragm seal. Thanks to the two lateral flushing bore holes, material buildup in front of the process isolating diaphragm can be rinsed away and the pressure chamber can be ventilated. ? To guarantee the leak-tightness of the transmitter, Endress+Hauser recommends that only genuine cable glands be used (also available as spare parts). Cerabar M transmitters without diaphragm seals are mounted as per the norms for a manometer (DIN EN 837-2). We recommend the use of shutoff devices and siphons. The orientation depends on the measuring application. Pressure measurement in gases ? Mount Cerabar M with shutoff device above the tapping point so that any condensate can flow into the process. Pressure measurement in steams ? Mount Cerabar M with siphon above the tapping point. ? Fill the siphon with liquid before commissioning. The siphon reduces the temperature to almost the ambient temperature. Pressure measurement in liquids ? Mount Cerabar M with shutoff device below or at the same level as the tapping point. Level measurement ? Mount Cerabar M below the lowest measuring point (zero point of the measurement). ? Do not mount the device at the following positions: In the filling curtain, in the tank outlet or at a point in the container which could be affected by pressure pulses from an agitator or a pump. ? The calibration and functional test can be carried out more easily if you mount the device downstream of a shutoff device. Measuring arrangement for devices with diaphragm seal – PMP55 Wall and pipe mounting ? → ? 74, "Planning instructions for diaphragm seal systems" section.

Measuring arrangement for devices without diaphragm seal – PMC51, PMP51

For installing the device on pipes or walls, Endress+Hauser provides a mounting bracket which is included in the scope of supply or can be ordered as a separate accessory (part no. 71102216). For the dimensions, see → ? 64.

Endress+Hauser

25

Cerabar M PMC51, PMP51, PMP55

"Separate housing" version

With the "separate housing" version, you are able to mount the housing with the electronics insert at a distance from the measuring point. This version allows for trouble-free measurement: ? Under particularly difficult measuring conditions (at installation locations that are cramped or difficult to access) ? If extreme cleaning of the measuring point is required ? If the measuring point is exposed to vibrations ? For space-saving installations You can choose between different cable versions: ? PE (2 m (6.6 ft), 5 m (16 ft) and 10 m (33 ft)) ? FEP (5 m (16 ft)). → ? 79 ff, feature 600, "Separate housing". For the dimensions, → ? 64.

?
FEP cable: IP 69K IP 66/68 NEMA 4/6P PE cable: IP 66/68 NEMA 4/6P

?
IP xx (see chapter “Ordering information”)

? ?
r ? 120 mm

P01-PMx5xxxx-11-xx-xx-en-002

In the case of the "separate housing" version, the sensor is delivered with the process connection and cable ready mounted. The housing and a mounting bracket are enclosed as separate units. The cable is provided with a socket at both ends. These sockets are simply connected to the housing and the sensor. 1 2 3 4 Process connection with sensor Cable, both ends are fitted with a socket Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter) Housing with electronic insert

Degree of protection for the process connection and sensor with the use of ? FEP cable: – IP 69K – IP 66 NEMA 4/6P – IP 68 (1.83 mH2O for 24 h) NEMA 4/6P ? PE cable: – IP 66 NEMA 4/6P – IP 68 (1.83 mH2O for 24 h) NEMA 4/6P Technical data of the PE and FEP cable: ? Minimum bending radius: 120 mm (4.72 in) ? Cable extraction force: max. 450 N (101 lbf) ? Resistance to UV light Use in hazardous area: ? Intrinsically safe installations (Ex ia/IS) ? FM/CSA IS: for Div.1 installation only Reduction in installation height If the separate housing is used, the mounting height of the process connection is reduced compared to the dimensions of the standard version (see graphic).

26

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

r ? 120 mm F31 F15

r ? 120 mm

r ? 120 mm

44

29

17

36

?54.1

?

?

?

P01-xMx5xxxx-06-xx-xx-xx-000

Oxygen applications

Oxygen and other gases can react explosively to oils, grease and plastics. As a result, the following are some of the precautions that must be taken: – All components of the system, such as measuring devices, must be cleaned in accordance with the BAM (DIN 19247) requirements. – Depending on the materials used, a certain maximum temperature and maximum pressure must not be exceeded for oxygen applications. The devices suitable for gaseous oxygen applications are listed in the following table with the specification pmax.
Ordering code for devices1) cleaned for oxygen applications PMC51 2) – devices with sensors, nominal value < 10 bar (150 psi) PMC51 2) – devices with sensors, nominal value ≥ 10 bar (150 psi) PMP51 PMP55 2) pmax for oxygen applications Tmax for oxygen applications 60°C (140°F) 60°C (140°F) 85°C (185°F)

Over pressure limit (OPL) of sensor3, 4 40 bar (600 psi) Depends on the lowest-rated element, with regard to pressure, of the selected components: over pressure limit (OPL) of sensor 3, process connection (1.5 x PN) or fill fluid (160 bar (2320 psi))

1) 2) 3) 4)

Only device, not accessory or enclosed accessory Feature 570 "Service" version "HB" → ? 79 ff "Ordering information", feature 70 "Sensor range" PMC51 with PVDF thread or PVDF flange pmax = 15 bar (225 psi)

PWIS cleaning

Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops → ? 83 feature 570 "Service", version "HC". Endress+Hauser also provides devices which have been cleaned of oil and grease for special applications, such as for ultrapure gas. No special restrictions regarding the process conditions apply to these devices. → ? 79 ff, "Ordering information PMC51", feature 570 "Service" version "HA". → ? 86 ff, "Ordering information PMP51", feature 570 "Service" version "HA".

Ultrapure gas applications

Applications with hydrogen

With regard to materials in which hydrogen formation takes place, hydrogen atoms can diffuse through the metal process isolating diaphragm. This can result in incorrect measurement results. Endress+Hauser offers process isolating diaphragms with a gold/rhodium coating for such instances. → ? 85 ff "Ordering information PMP51" and → ? 89 ff "Ordering information PMP55", feature 170 "Membrane Material" version "M".

Endress+Hauser

81

27

Cerabar M PMC51, PMP51, PMP55

Operating conditions (environment)
Ambient temperature range
Version Without LCD display With LCD display
1)

PMC51

PMP51 –40°C to +85°C (–40°F to +185°F) –20°C to +70°C (–4°F to +158°F) –25°C to +85°C (–13°F to +185°F)

PMP55

With M12 plug , elbowed With separate housing Diaphragm seal systems 1)

–20°C to +60°C (–4°F to +140°F) (installation without insulation) ? ?

? → ? 74

Extended temperature application range (–40°C to +85°C (–40°F to +185°F)) with restrictions in optical properties such as display speed and contrast

Note! For high-temperature applications, either a PMP55 with a temperature isolator or with a capillary can be used. If vibrations also occur in the application, Endress+Hauser recommends you use a PMP55 with a capillary. If a PMP55 with a temperature isolator or capillary is used, we recommend a suitable bracket for mounting (see "Wall and pipe mounting" section on → ? 25). For devices for use in hazardous areas, see Safety Instructions, Installation or Control Drawing. (→ ? 95 ff, "Safety Instructions" and "Installation/Control Drawings" sections) Storage temperature range

Version Without LCD display With LCD display With M12 plug , elbowed With separate housing Diaphragm seal systems

PMC51

PMP51 –40°C to +90°C (–40°F to +194°F) –40°C to +85°C (–40°F to +185°F) –25°C to +85°C (–-13°F to +185°F)

PMP55

–40°C to +60°C (–40°F to +140°F) ? ?

? → ? 74

Degree of protection

? → ? 79 ff, feature 50 "Electrical connection". ? Separate housing (→ ? 26) Class 4K4H (air temperature: –20 to 55°C (–4 to +131°F), relative humidity: 4 to 100%) satisfied as per DIN EN 60721-3-4 (condensation possible).

Climate class

28

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Vibration resistance

Device/Additional option

Test standard

Vibration resistance guaranteed for 3 to 18 Hz: ±4 mm (0.16 in); 25 to 500 Hz: 5 g in all 3 planes guaranteed for 10 to 60 Hz: ±0.35 mm (0.01 in); 60 to 2000 Hz: 2 g in all 3 planes guaranteed for 10 to 60 Hz: ±0.15 mm (0.01 in); 60 to 500 Hz: 2 g in all 3 planes

Devices without mounting GL VI-7-2 bracket ? Part 7: Guidelines for the Performance of Type Approvals ? Chapter 2: Test Requirements for Electrical / Electronic Equipment and Systems IEC 61298-3 IEC 60068-2-6

Devices with mounting bracket

IEC 61298-3 IEC 60068-2-6

Note! For high-vibration applications, either a PMC51/PMP51 with a separate housing or a PMP55 with a capillary can be used. We recommend a suitable bracket for mounting (see "Wall and pipe mounting" section on → ? 25). Electromagnetic compatibility ? Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and NAMUR Recommendation EMC (NE21). Details can be found in the Declaration of Conformity (in the Download area of "www.de.endress.com", "search area - Approvals and Certificates", "Manufact. Declaration"). ? Maximum deviation: < 0.5 % of span NAThe device can be fitted with overvoltage protection, see → ? 79 ff "Ordering information" feature 610 "Accessory mounted:" version "NA". The overvoltage protection is mounted at the factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in length (take additional length into account when installing). The device is connected as illustrated in the following graphic. For details refer to TI00103R/09/EN, XA00036R/09/A3 and KA00161R/09/A6. Wiring

Overvoltage protection (optional)

Incoming connection cables
+

?

-

Unit to be protected

+

?

-

Red Black

+

-

Connection cables Shield grounding ? without ? direct HAW569Z

P01-xMx5xxxx-04-xx-xx-en-006

Endress+Hauser

29

Cerabar M PMC51, PMP51, PMP55

Operating conditions (process)
Process temperature range PMC51
1

Tp °C
150 140
2

Ta
TP

130 120 110 100 ... 20 10 0 -10-10 0 -20 -30 -40
P01-xxxxxxxx-05-xx-xx-xx-014

Ta
10 20 30 40 50 60 70 80 90

-50

-40

-30

-20

°C

Ta = Ambient temperature; Tp = Process temperature; ? und ? see following chapter.

Process temperature limits

PMC51 (with ceramic process isolating diaphragm) ? ?: –40 to +130°C (–40 to +266°F) ? ?: For a maximum of 60 minutes: +150 °C (+302 °F) ? Observe the process temperature range of the seal. See also the following table.

Version for Seal feature 190 in the order code A A B F H G J K L M N P S 1) 2)
1)

Notes Thread or flange cleaned for O2 application FDA , 3A Class I, USP Class VI FDA , 3A Class I, KTW, AFNOR, BAM FDA
2) 2) 2) 2)

Process temperature range Hygienic process connection -5 to +150 °C (+23 to +302°F) -20 to +125 °C (-4 to +257°F) -15 to +150 °C (+5 to +302°F) -5 to +150 °C (+23 to +302°F) +5 to +150 °C (+41 to +302°F) -20 to +85 °C (-4 to +185°F)

FKM Viton FKM Viton FKM Viton NBR NBR, Low temperature HNBR EPDM EPDM FFKM Kalrez 6375 FFKM Kalrez 7075 FFKM Kalrez 6221 Fluoroprene XP40 VMQ Silicone FDA 2), USP Class VI

-20 to +100°C (-4 to +212°F) -5 to +60°C (+23 to +140°F) -5 to +100°C (+23 to +212°F) -10 to +100°C (-14 to +212°F) -40 to +100°C (-40 to +212°F) -25 to +100°C (-13 to +212°F) -40 to +100°C (-40 to +212°F) +5 to +100°C (+41 to +212°F) +5 to +100°C (+41 to +212°F) -5 to +100°C (+23 to +212°F) +5 to +100°C (+41 to +212°F) -35 to +85°C (-31 to +185°F)

FDA , 3A Class II, USP Class VI, DVGW, KTW, W270, WRAS, ACS, NSF61 -

FDA 2), USP Class VI, 3A Class I FDA 2)

With feature 570 "Service", version "HB - Cleaned for oxygen service" Suitable for foods FDA 21 CFR 177.2600

30

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Applications with jumps in temperature Extreme jumps in temperature can result in temporary measuring errors. Temperature compensation takes effect after several minutes. Internal temperature compensation is faster the smaller the jump in temperature and the longer the time interval involved. For further information please contact your local Endress+Hauser Sales Center. PMP51 (with metal process isolating diaphragm)
Description Process connections with internal process isolating diaphragm Process connections with flush-mounted process isolating diaphragm, G 1 A, G 1 1/2 A, G 2 A, 1 NPT, 1 1/2 NPT, 2 NPT, M 44 x 1.25, EN/DIN, ANSI and JIS flanges Process connections with flush-mounted process isolating diaphragm, G 1/2 A, M 20x1.5 Temperature operating range -40 to +125°C (-40 to +257°F) -40 to +100°C (-40 to +212°F)

-20 to +85°C (-4 to +185°F)

PMP55 (with diaphragm seal) ? Depending on the diaphragm seal and filling oil from -70°C (-94°F) up to +400°C (+752°F). Observe the temperature application limits → ? 74. Note! ? Do not use diaphragm seals with 0.09 mm (0.0035 in) PTFE foil on AISI 316L for vacuum applications, upper temperature limit +204°C (+399°F). ? For oxygen applications, observe → ? 27, "Oxygen applications" section. Pressure specifications ? The maximum pressure for the measuring device depends on the lowest-rated element with regard to pressure. See the following sections: – → ? 8 ff, "Measuring range" section – "Mechanical construction" section. The MWP (maximum working pressure) is specified on the nameplate. This value refers to a reference temperature of +20°C (68°F), or 100°F (38°C) for ANSI flanges, and may be applied to the device for an unlimited time. Observe temperature dependency of the MWP. ? The pressure values permitted at higher temperatures can be found in the following standards: – EN 1092-1: 2001 Tab. 18 1 – ASME B 16.5a – 1998 Tab. 2-2.2 F316 – ASME B 16.5a – 1998 Tab. 2.3.8 N10276 – JIS B 2220. ? The test pressure corresponds to the over pressure limit of the device (over pressure limit OPL = 1.5 x MWP 2) and may be applied for only a limited time period in order to avoid permanent damage. ? The Pressure Equipment Directive (EC Directive 97/23/EC) uses the abbreviation "PS". The abbreviation "PS" corresponds to the MWP (maximum working pressure) of the measuring device. ? In the case of sensor range and process connection combinations where the OPL (over pressure limit) of the process connection is smaller than the nominal value of the sensor, the device is set at the factory, at the very maximum, to the OPL value of the process connection. If you want to use the entire sensor range, select a process connection with a higher OPL value (1.5 x PN; PN = MWP). ? In oxygen applications, the values for "pmax and Tmax for oxygen applications" as per → ? 27, "Oxygen applications" may not be exceeded. ? Avoid steam hammering! Steam hammering can cause zero point drift. Recommendation: Residue (such as condensation or drops of water) can remain at the process isolating diaphragm after CIP cleaning and lead to local steam hammering if immediately steam is introduced. In practice, drying the process isolating diaphragm (e.g. by blowing off excess moisture) has proven to be a successful way of avoiding steam hammering.
1) 2) With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical. The equation does not apply for PMP51 and PMP55 with a 40 bar (600 psi) - or a 100 bar (1500 psi) - measuring cell.

Endress+Hauser

31

Cerabar M PMC51, PMP51, PMP55

Mechanical construction
F31 aluminum housing dimensions
115 94

?
14.3 103

H

P01-F31xxxx-06-00-xx-xx-000

Front view, left-hand side view, top view ? The cover with viewing window is 15 mm (0.59 in) higher than the cover without viewing window. → For installation height H for housing with viewing window, see the specific process connection. Housing weight → ? 64

F15 stainless steel housing dimensions (hygienic)

100

?
19 H

76

P01-F15xxxx-06-00-xx-xx-000

Front view, top view. ? The cover with viewing window is 19 mm (0.75 in) higher than the cover without viewing window. → For installation height H for housing with viewing window, see the specific process connection. Housing weight → ? 64

Process connections PMC51 (with ceramic process isolating diaphragm)

Thread, internal process isolating diaphragm

?

G 1/2A

?
H

G 1/2A G 1/4

?

G 1/2A 11.4 mm

17 20

13

?3 ?6 G 1/2

G 1/4 ?17.5 G 1/2

?11.4 ?17.5 G 1/2
P01-PMC71xxx-06-09-xx-xx-001

Process connections PMC51, thread ISO 228 Installation height H → ? 33. 1 Thread ISO 228 G 1/2 A EN 837; Material version GCJ: AISI 316L, version GCC: Alloy C276 Version GCF: PVDF (max.: 15 bar (217.5 psi), –10 to +60 °C (+14 to +140 °F)), mount version"GCF" with a mounting bracket only ( → ? 25); weight: 0.63 kg (1.39 lbs) Thread ISO 228 G 1/2 A G 1/4 (female); Material version GLJ: AISI 316L, version GLC: Alloy C276; weight: 0.63 kg(1.39 lbs)

2

32

3

Endress+Hauser

17 20

17 20

?8

H

H

Cerabar M PMC51, PMP51, PMP55

3

Thread ISO 228 G 1/2 A hole 11.4 mm (0.45 in); Material version GMJ: AISI 316L, version GMC: Alloy C276; weight: 0.63 kg(1.39 lbs)

? 1/2 MNPT

1/4 FNPT

? 1/2 MNPT

11.4 mm

? 1/2 MNPT

3 mm

? 1/2 FNPT
H
1/2 NPT ?26.5
P01-PMC71xxx-06-09-xx-xx-002

H

H

H

25

25

?11.4 1/4 NPT 1/2 NPT
Process connections PMC51, thread ANSI Installation height H → ? 33. 1 2 3

?11.4 1/2 NPT

?3 1/2 NPT

4

Thread ANSI 1/2 MNPT 1/4 FNPT; Material version RLJ: AISI 316L, version RLC: Alloy C276; weight: 0.63 kg (1.39 lbs) Thread ANSI 1/2 MNPT hole 11.4 (0.45 in); Material version RKJ: AISI 316L; version RKC: Alloy C276; weight: 0.63 kg(1.39 lbs) Thread ANSI 1/2 MNPT hole 3 mm (0.12 in); Material version RJF: PVDF (max.: 15 bar (225 psi), –10 to +60 °C (+14 to +140 °F)) mount with mounting bracket only (→ ? 25); weight: 0.63 kg (1.39 lbs) Thread ANSI FNPT 1/2 Material version R1J: AISI 316L, version R1C: Alloy C276; weight: 0.63 kg(1.39 lbs)

?

G 1/2

?
H

R 1/2

25

20

3

?3 ?5

?11.4 R 1/2

G 1/2
P01-PMC71xxx-06-09-xx-xx-003

Process connections PMC51, thread JIS Installation height H → ? 33. 1 2 Version GNJ: thread JIS B0202 G 1/2 (male), material: AISI 316L; weight: 0.63 kg (1.39 lbs) Version GOJ: thread JIS B0203 R 1/2 (male), material: AISI 316L; Weight: 0.63 kg (1.39 lbs)

Installation height H for devices with threaded connection and internal process isolating diaphragm
F31 housing 154 mm (6.06 in) F15 housing 146 mm (5.75 in)

Endress+Hauser

23

?8

13.2

H

25

33

Cerabar M PMC51, PMP51, PMP55

Thread, flush-mounted process isolating diaphragm

? G 1 1/2
SW 60 60 AF

?

G2 SW 60 60 AF

G 1 1/2 ?55

G2 ?68

? 1 1/2 NPT
SW 60 60 AF

?

33.5 H

25 28

H

30

2 NPT SW 60 60 AF

? M44x1.25
SW 60 60 AF

27 H

33.5

H

30

1 1/2 NPT

2 NPT ?68

?40.5 M44x1.25
P01-PMC71xxx-06-09-xx-xx-005

Process connections PMC51, → Installation height, see table below. 1 2 3 4 5 Thread ISO 228 G 1 1/2 A; Material version GVJ: AISI 316L; weight: 0.63 kg (1.39 lbs) Thread ISO 228 G 2 A; Material version GWJ: AISI 316L; weight: 0.63 kg (1.39 lbs) Thread ANSI 1 1/2 MNPT; Material version U7J: AISI 316L; weight: 0.63 kg (1.39 lbs) Thread ANSI 2 MNPT; Material version U8J: AISI 316L; weight: 0.63 kg (1.39 lbs) Thread DIN 13 M 44x1.25; Material version G4J: AISI 316L; weight: 0.63 kg (1.39 lbs)

Installation height H for devices with threaded connection and flush-mounted process isolating diaphragm
F31 housing 201 mm (7.91 in) F15 housing 193 mm (7.6 in)

34

Endress+Hauser

11

22

H

Cerabar M PMC51, PMP51, PMP55

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527

g2

2

26 (1.024)

g k D
P01-PMC71xxx-06-09-xx-xx-006

Process connection PMC51, EN/DIN flange with raised face (flush-mounted process isolating diaphragm) Installation height H → ? 37.

Flange Version Material Nominal diameter Nominal pressure Shape 1 Diameter D [mm] CNJ CPJ CQJ CXJ CFF CRP CZJ CSP 1) 2) 3) 4) AISI 316L AISI 316L AISI 316L AISI 316L PVDF
3 4

Boltholes Thickness Raised face b [mm] 18 18 18 20 18 20 24 24 g [mm] 68 78 88 102 102 102 138 138 4 4 4 4 4 4 8 8 Quantity Diameter g2 [mm] 14 18 18 18 18 18 18 18 Hole circle k [mm] 85 100 110 125 125 125 160 160 [kg] 1.4 2.0 2.4 3.2 2.9 3.2 5.5 5.5 Flange weight 2

DN 25 DN 32 DN 40 DN 50 DN 50 DN 50 DN 80 DN 80

PN 10-40 PN 10-40 PN 10-40 PN 10-40 PN 10-16 PN 25-40 PN 10-40 PN 25-40

B1 (D) B1 (D) B1 (D) B1 (D) B1 (D) B1 (D) B1 (D) B1 (D)

115 140 150 165 165 165 200 200

ECTFE

AISI 316L ECTFE
4

Designation as per DIN 2527 in brackets Housing weight → ? 64 OPL.: 15 bar (225 psi) Process temperature range: –10 to +60 °C (+14 to +140 °F) ECTFE coating on AISI 316L (1.4404/1.4435). When operating in hazardous areas, avoid electrostatic charging of the plastic surfaces.

Endress+Hauser

b

H

35

Cerabar M PMC51, PMP51, PMP55

ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF

0.06 1.6

g k D
P01-PMC71xxx-06-09-xx-xx-007

Process connection PMC51, ANSI flange with raised face RF (flush-mounted process isolating diaphragm) Installation height H → ? 37.

Flange Version Material Nominal diameter Class Diameter D [in] ACJ ANJ AEJ AQJ AFJ AFN AFF ARJ AGJ AGN AGF ASJ AHJ AHN ATJ 1) 2) 3) 4) AISI 316/316L AISI 316/316L AISI 316/316L AISI 316/316L AISI 316/316L ECTFE PVDF
4 2 2 3 2 2 2 2 2

Boltholes Thickness b [in] / [mm] 0.56 / 14.2 0.69 / 17.2 0.69 / 17.5 0.81 / 20.6 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.88 / 22.4 0.94 / 23.9 0.94 / 23.9 0.94 / 23.9 1.12 / 28.4 0.94 / 23.9 0.94 / 23.9 1.25 / 31.8 Raised face g [in] / [mm] 2 / 50.8 2 / 50.8 2.88 / 73.2 2.88 / 73.2 3.62 / 91.9 3.62 / 91.9 3.62 / 91.9 3.62 / 91.9 5 / 127 5 / 127 5 / 127 5 / 127 6.19 / 157.2 6.19 / 157.2 6.19 / 157.2 4 4 4 4 4 4 4 8 4 4 4 8 8 8 8 Quantity Diameter g2 [in] / [mm] 0.62 / 15.7 0.75 / 19 0.62 / 15.7 0.88 / 22.4 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.88 / 22.4 0.75 / 19.1 0.75 / 19.1 0.88 / 22.4 Hole circle k [in] / [mm] 3.12 / 79.2 3.5 / 88.9 3.88 / 98.6 4.5 / 114.3 4.75 / 120.7 4.75 / 120.7 4.75 / 120.7 5 / 127 6 / 152.4 6 / 152.4 6 / 152.4 6.62 / 168.1 7.5 / 190.5 7.5 / 190.5 7.88 / 200.2 [kg] 0.9 1.4 1.0 2.6 2.4 2.4 0.5 3.2 4.9 4.9 0.9 6.8 7.1 7.1 11.6 Flange weight 1

[lb./sq.in] 150 300 150 300 150 150 150 300 150 150 150 300 150 150 300

[in] / [mm] 4.25 / 108 4.88 / 123.9 5 / 127 6.12 / 155.4 6 / 152.4 6 / 152.4 6 / 152.4 6.5 / 165.1 7.5 / 190.5 7.5 / 190.5 7.5 / 190.5 8.25 / 209.5 9 / 228.6 9 / 228.6 10 / 254

1 1 1 1/2 1 1/2 2 2 2 2 3 3 3

AISI 316/316L AISI 316/316L ECTFE PVDF
4 3

AISI 316/316L AISI 316/316L ECTFE
3

2 2

3 4 4

AISI 316/316L

2

4

Housing weight → ? 64 Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated) ECTFE coating on AISI 316/316L (1.4404/1.4435). When operating in hazardous areas, avoid electrostatic charging of the plastic surfaces. OPL.: 15 bar (225 psi) Process temperature range: –10 to +60 °C (+14 to +140 °F)

36

b

H

g2

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF

2

g k D
P01-PMC71xxx-06-09-xx-xx-008

Process connection PMC51, JIS flange with raised face RF (flush-mounted process isolating diaphragm), material: AISI 316L → Installation height H, see table below.

Flange Version Nominal diameter Nominal pressure Diameter D [mm] KFJ KGJ KHJ 1) 50 A 80 A 100 A 10 K 10 K 10 K 155 185 210 Thickness b [mm] 16 18 18 Raised face g [mm] 96 127 151

Boltholes Quantity Diameter g2 [mm] 4 8 8 19 19 19 Hole circle k [mm] 120 150 175 [kg] 2.0 3.3 4.4 Flange weight 1

Housing weight, see → ? 64

Installation height H for devices with flange
F31 housing 201 mm (7.91 in) F15 housing 193 mm (7.6 in)

Endress+Hauser

b

H

g2

37

Cerabar M PMC51, PMP51, PMP55

Hygienic process connection, flush-mounted process isolating diaphragm

1

DIN11851 DN40
D4 K

2

DIN11851 DN50

D1 D2 K

H

7.5 10 (0.39) (0.3)

11 (0.43)

H

D3 D3 D2 D1
3 1

DIN11864 DN40
D4 K
4

DIN11864 DN50
D1 D2 K

H 7.5 (0.3)

D2

H 10 (0.39)

11 (0.43)

D3 D3 D1
5

Tri-Clamp 2"
D2 K

6

Tri-Clamp 3"
D2 K

H 7 (0.28)

D3 d D1 mm (in)

H

D3 d D1
P01-PMC51xxx-06-00-00-xx-000

Hygienic process connections, material: AISI 316L (1.4435) Surface roughness of the surfaces in contact with the medium Ra 0.76 μm (30 μin). Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra 0.38 μm (15 μin), electropolished; to be ordered using feature 570 "Service", version "HK" in the order code.

Pos. 1 2 3 4 5 6

Version MZJ MRJ NCJ NDJ TDJ TFJ

Nominal pressure PN 25 25 16 16 40 40

Outer-? D1 56 (2.2) 68 (2.68) 54.9 (2.16) 66.8 (2.63) 64 (2.52) 91 (3.58)

Outer-? D2 48 (1.89) 61 (2.4) 48 (1.89) 61 (2.4) 61 (2.4) 76.7 (3.02)

Internal-? D3 38 (1.5) 42 (1.65) 38 (1.5) 42 (1.65) 42 (1.65) 42 (1.65)

Outer-? D4 60 (2.36) 60 (2.36) -

Seal-? d 56.5 (2.22) 83.5 (3.29)

Hole circle K1) 52 (2.05) 52 (2.05) 52 (2.05) 52 (2.05) 52 (2.05) 52 (2.05)

Height H 41.5 (1.63) 19.8 (0.78) 45.35 (1.79) 23.2 (0.91) 19.8 (0.78) 19.8 (0.78)

Weight [kg/lbs] 0.652 (1.44) 0.276 (0.61) 0.656 (1.45) 0.288 (0.64) 0.171 (0.38) 0.539 (1.19)

mm (in) 1) 4 x M5 thread

38

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

1

Varivent F DN25-32
D2 K

2

Varivent N DN40-162

D1 D2 K

H 12,3 (0.48)

D3 D1
3 1

D3

NEUMO BioControl
D1 K k

4

DRD DN50
D1 K 61 (2.4) k

H

D3 D2 D3 D2
5

h

APV Inline
D1 K ?59,5 (2.34) k

D3 D2 mm (in)
P01-PMC51xxx-06-00-00-xx-001

Hygienic process connections, material: AISI 316L (1.4435) Surface roughness of the surfaces in contact with the medium Ra 0.76 μm (30 μin). Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra 0.38 μm (15 μin), electropolished; to be ordered using feature 570 "Service", version "HK" in the order code.

Pos. 1 2 3 4 5

Version TQJ TRJ S4J TIJ TMJ

Nominal pressure PN 40 40 40 25 40

Outer-? D1 66 (2.6) 84 (3.31) 90 (3.54) 105 (4.13) 100 (3.94)

Outer-? D2 60 (2.36) 75 (2.95) 49.9 (1.96) 65 (2.56) 69 (2.72)

Internal-? D3 38 (1.5) 42 (1.65) 38 (1.5) 42 (1.65) 42 (1.65)

Hole circle K 52 (2.05)2) 52 (2.05)2) 90 (3.54)3) 84 (3.31)4) 82 (3.23)5)

h H

Hole circle k1) 52 (2.05) 52 (2.05) 52 (2.05)

Height H 42 (1.65) 19.8 (0.78) 52.5 (2.07) 23.8 (0.94) 19.8 (0.78)

Height h 17 (0.67) 16 (0.63) 12.5 (0.49)

0.459 (1.01) 0.426 (0.94) 1.34 (2.95) 0.619 (1.36) 0.519 (1.14)

mm (in) 1) 2) 3) 4) 5) 4 x M5 thread 4 x M5 thread 4 x ?9 (0.35); 4 screws DIN912 M8 x 45 are enclosed (material (A4-80)) 4 x ?11.5 (0.45) 6 x ?8.6 (0.34) + 2 x M8 thread; 8 x 45° (=360)

Endress+Hauser

h H

Weight [kg/lbs]

12,3 (0.48) H

39

Cerabar M PMC51, PMP51, PMP55

Universal adapter

b
3

? ?
mm (in)
P01-PMC51xxx-06-00-00-xx-002

?43.5 (1.71)

Material: b = top section AISI 316L (1.4404), a = bottom section AISI 316L (1.4435); Endress+Hauser supplies the slotted nut in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material number 1.4307).. Surface roughness of the surfaces in contact with the medium Ra 0.76 μm (30 μin). Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra 0.38 μm (15 μin), electropolished; to be ordered using feature 570 "Service", version "HK" in the order code.

Ver Process sion connection approval UPJ EHEDG, 3A

Material of the shape seal ? (changeable)

Material of the measuring cell seal ? (not changeable)

Measuring cell seal approval

a

H
Nominal Pressure PN

Weight [kg/lbs]

Silicone EPDM (Order version "K") (Spare part order no.: 52023572) EPDM EPDM (Order version "J") (Spare part order no.: 71100719)

FDA1) 3A Class II, USP Class VI. DVGW, KTW, W270, WRAS, ACS, NSF61 10 FDA1)

0.74 (1.63)

UNJ

EHEDG

1)

Suitable for foods FDA 21 CFR 177.2600

Installation height H, devices with universal adapter
F31 housing 196 mm (7.72 in) F15 housing 189 mm (7.44 in)

40

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Process connections PMP51 (with metal process isolating diaphragm)

Thread, internal process isolating diaphragm

?

G 1/2A

? G 1/2A
H

G 1/4

? G 1/2A
H

11.4

?11.4
20 3 13 17 20

?11.4
17 20 10 8
?11.4 1/2 NPT ?38
P01-PMP51xxx-06-09-xx-xx-001

?3.2 ?6

G 1/4 ?17.5 G 1/2 A

3

?17.5 G 1/2 A

?17.5 G 1/2 A

P01-PMP71xxx-06-09-xx-xx-000

Process connections PMP51, thread ISO 228 Installation height H → ? 41. 1 2 3 Thread ISO 228 G 1/2 A EN 837; Material version GCJ: AISI 316L, version GCC: Alloy C276; weight: 0.6 kg (1.32 lbs) Thread ISO 228 G 1/2 A G 1/4 (female); Material version GLJ: AISI 316L, version GLC: Alloy C276; weight: 0.6 kg (1.32 lbs) Thread ISO 228 G 1/2 A hole 11.4 mm (0.45 in); Material version GMJ: AISI 316L, version GMC: Alloy C276; weight: 0.6 kg (1.32 lbs)

? 1/2 MNPT

1/4 FNPT

? 1/2 MNPT
H

? 1/2 FNPT
H 7
1/2 NPT

?11.4 ?21.4

H

?21.4

25

25

H 20

1/4 NPT 1/2 NPT

Process connections PMP51, thread ANSI Installation height H → ? 41. 1 2 3 Thread ANSI 1/2 MNPT 1/4 FNPT; Material version RLJ: AISI 316L, version RLC: Alloy C276; weight: 0.6 kg (1.32 lbs) Thread ANSI 1/2 MNPT hole: 400 bar (6000 psi) = 11.4 mm (0.45 in) Material version RKJ: AISI 316L, version RKC: Alloy C276; weight: 0.6 kg (1.32 lbs) Thread ANSI 1/2 FNPT; Material version R1J: AISI 316L, version R1C: Alloy C276/2.4819; Weight: 0.7 kg (1.54 lbs)

Installation height H for devices with threaded connection and internal process isolating diaphragm
F31 housing Height H 169 mm (6.65 in) F15 housing 150 mm (5.91 in)

Endress+Hauser

15

41

Cerabar M PMC51, PMP51, PMP55

Thread, flush-mounted process isolating diaphragm

?
?18.4

G 1/2A

? G 1A
H 3.5 3
?30

3.5
?30 G 1A ?36 ?39

H 14
dM = ?28

2

dM = ?17.5
G 1/2A ?23.6 ?26.5

2

18

3

?

G 1 1/2A

?
H 26 8

G 2A

q M 20x1.5
H
?17.7

3.5

1

31

2

2

dM = ?28 ?36 G 1 1/2A ?55
Thread ISO 228 Installation height H → ? 43. 1 2 3 4 5

dM = ?28 ?56.3 G2A ?68

dM = ?17.5 M20x1.5 ?23.6 ?26.5

P01-PMx5xxxx-06-xx-xx-xx-001-package1

Thread ISO 228 G 1/2 A DIN 3852 (viton seal included); Material version GRJ: AISI 316L, version GRC: : Alloy C276; weight: 0.4 kg (0.88 lbs) Thread ISO 228 G 1 A (viton seal included); Material version GTJ: AISI 316L; weight: 0.7 kg (1.54 lbs) Thread ISO 228 G 1 1/2 A Material version GVJ: AISI 316L; weight: 1.1 kg (2.43 lbs) Thread ISO 228 G 2 A Material version GWJ: AISI 316L; weight: 1.5 kg (3.31 lbs) Thread DIN13 M20x1.5 Material version G1J: AISI 316L; weight 0.4 kg (0.88 lbs)

Note! Endress+Hauser offers a pressure sensor dummy for the welding neck with order number 52002643. Order number for pressure sensor dummy: 52005082
– Welded neck Order number: 52002643

AF 27

G? ?26

?50
max. pressure resistance 100 bar

O-Ring 14 x 1.78 Viton or NBR
Version G0J: Thread ISO 228 G1/2; weight: 0.4 kg (0.88 lbs)

P01-PMx5xxxx-06-xx-xx-en-003

42

Endress+Hauser

13 21

Viton seal

21

G?

2

14

3

H

Cerabar M PMC51, PMP51, PMP55

m

1 MNPT

n
H

1 1/2 MNPT

o
H

2 MNPT

dM = ?28 1 NPT 1 1/2 NPT

23

dM = ?28 2 NPT

dM = ?28

P01-PMx5xxxx-06-xx-xx-xx-002-package1

Process connections PMP51 thread ANSI Installation height H see following table. 1 2 3 Thread ANSI 1 MNPT; Material version U5J: AISI 316L; weight: 0.7 kg (1.54 lbs) Thread ANSI 1 1/2 MNPT; Material version U7J: AISI 316L; weight: 1.0 kg (2.21 lbs) Thread ANSI 2 MNPT Material version U8J: AISI 316L; weight: 1.3 kg (2.86 lbs)

Installation height H for devices with threaded connection and flush-mounted process isolating diaphragm
Description G 1/2 G1 G 1 1/2 A G2A 1 MNPT 1 1/2 MNPT 2 MNPT M 20x1.5 F31 housing 163 mm (6.42 in) 167 mm (6.57 in) 163 mm (6.42 in) 162 mm (6.38 in) 162 mm (6.38 in) 169 mm (6.65 in) 199 mm (7.83 in) 163 mm (6.42 in) F15 housing 148 mm (5.83 in) 152 mm (5.98 in) 148 mm (5.83 in) 147 mm (5.79 in) 147 mm (5.79 in) 150 mm (5.91 in) 144 mm (5.67 in) 148 mm (5.83 in)

Endress+Hauser

33.5

27

H

43

Cerabar M PMC51, PMP51, PMP55

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527

g2

2

dM = ?28 60 g k D (m)

b

h H

P01-PMP71xxx-06-09-xx-xx-008

Process connection PMP51, EN/DIN flange with raised face, material AISI 316L H: device height = height of device without flange h + flange thickness b Height H → ? 45.

Flange 1 Version Nominal diameter Nominal pressure Shape
2

Boltholes Diameter D [mm] Thickness b [mm] 18 18 18 20 24 Raised face g [mm] 68 78 88
4 4 4

Width of the raised face (m) [mm] 4 9 14 -

Quantity

Diameter

Hole circle

Flange weight 3

g2 [mm] 4 4 4 4 8 14 18 18 18 18

k [mm] 85 100 110 125 160 [kg] 1.2 1.9 2.2 3.0 5.5

CNJ CPJ CQJ CXJ CZJ 1) 2) 3) 4)

DN 25 DN 32 DN 40 DN 50 DN 80

PN 10-40 PN 10-40 PN 10-40 PN 25/40 PN 10-40

B1 (D) B1 (D) B1 (D) B1 (D) B1 (D)

115 140 150 165 200

102 138

The roughness of the surface in contact with the medium is Ra 0.8 μm (31.5 μin). Lower surface roughness available on request. Designation as per DIN 2527 in brackets Housing weight → ? 64 With these process connections the sealing surface is smaller than described in the standard. Due to a smaller sealing surface a special seal must be used. Contact a seal manufacturer or your local Endress+Hauser Sales Center.

44

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF

g2

2

dM = ?28 60 g k D

(m)

b

h H

P01-PMP71xxx-06-09-xx-xx-009

Process connection PMP51, ANSI flange with raised face RF (see table below) H: device height = height of device without flange h + flange thickness b.. For height H → ? 45.

Flange 1 Version Material Nominal Class/ diaNominal meter pressure Diameter Thickness Diameter of raised face b [in] / [mm] g [in] / [mm]

Boltholes Width of Quanti the raised ty face (m) [in] / [mm] Diameter Hole circle Flange weight 2

D [in] ANSI flanges ANJ AEJ AQJ AFJ ARJ AGJ ASJ AHJ ATJ 1) 2) 3) 4) AISI 316/316L 3 1 AISI 316/316L 3 1 1/2 AISI 316/316L 3 1 1/2 AISI 316/316L 3 2 AISI 316/316L 3 2 AISI 316/316L 3 3 AISI 316/316L 3 3 AISI 316/316L 3 4 AISI 316/316L 3 4 300 lb./sq.in 150 lb./sq.in 300 lb./sq.in 150 lb./sq.in 300 lb./sq.in 150 lb./sq.in 300 lb./sq.in 150 lb./sq.in 300 lb./sq.in 4.88 / 124 5 / 127 6.12 / 155.4 6 / 152.4 7.5 / 190.5 7.5 / 190.5 8.25 / 209.5 9 / 228.6 10 / 254 [in] / [mm]

g2 [in] / [mm]

k [in] / [mm] [kg]

0.69 / 17.5 2.76 4 / 50.8 0.69 / 17.5 2.88 4 / 73.2 0.81 / 20.6 2.88 4 / 73.2 0.75 / 19.1 3.62 / 91.9 0.88 / 22.3 3.62 / 91.9 0.94 / 23.9 5 / 127 1.12 / 28.4 5 / 127 0.94 / 23.9 6.19 / 157.2 1.25 / 31.8 6.19 / 157.2

0.2 / 5 0.52 / 6.6 0.52 / 6.6 -

4 4 4 4 8 4 8 8 8

0.75 / 19.1 3.5 / 88.9 0.62 / 15.7 3.88 / 98.6 0.88 / 22.4 4.5 / 114.3

1.3 1.5 2.6

0.75 / 19.1 4.75 / 120.7 2.4 0.75 / 19.1 5 / 127 0.75 / 19.1 6 / 152.4 3.2 4.9

0.88 / 22.4 6.62 / 168.1 6.7 0.75 / 19.1 7.5 / 190.5 7.1

0.88 / 22.4 7.88 / 200.2 11.6

The roughness of the surface in contact with the medium is Ra 0.8 μm (31.5 μin). Lower surface roughness available on request. Housing weight → ? 64 Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated) With these process connections the sealing surface is smaller than described in the standard. Due to a smaller sealing surface a special seal must be used. Contact a seal manufacturer or your local Endress+Hauser Sales Center.

Height H for devices with flange
F31 housing Height H 165 mm (6.5 in) F15 housing 150 mm (5.91 in)

Endress+Hauser

45

Cerabar M PMC51, PMP51, PMP55

Prepared for diaphragm seal mount

? ? ?

h

?2.5 ?7.95
P01-PMP71xxx-06-09-xx-xx-013

Version XSJ: prepared for diaphragm seal mount 1 2 3 Hole for fill fluid Bearing Setscrew with a hexagonal recess 4 mm (0.16 in)

5
F31 housing Height H

F15 housing 175 mm (6.89 in)

190 mm (7.48 in)

PMP55 basic device

?
h

?

P01-PMP75xxx-06-09-xx-xx-012

PMP55 basic device with diaphragm seal 1 2 PMP55 basic device Diaphragm seal, here e.g. flange diaphragm seal

F31 housing Height H 190 mm (7.48 in)

F15 housing 175 mm (6.89 in)

46

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Process connections PMP55 (with diaphragm seal)

Note! ? The weights of the diaphragm seals are given in the tables. See → ? 64 for the weight of the housing. ? The following drawings are schematic diagrams. In other words, the dimensions of a diaphragm seal supplied may deviate from the dimensions given in this document. ? When using high-temperature oils the design can deviate significantly. ? Observe the information in the "Planning instructions for diaphragm seal systems" section → ? 74 ff. ? For further information please contact your local Endress+Hauser Sales Center. Diaphragm seal cell structure (Pancake)

dM
D
P01-FMD78xxx-06-09-xx-xx-000

Process connection PMP55, material AISI 316L

Flange Version Nominal Nominal Max. diameter pressure 1 diameter D [mm] UIJ UJJ UKJ DN 50 DN 80 DN 100 [in] ULJ UMJ URJ 1) 2 3 4 PN 16-400 102 PN 16-400 138 PN 16-400 162 [lb/sq.in] 150-2500 150-2500 150-2500 [in (mm)] 4.01 (102) 5.35 (136) 6.22 (158)

Diaphragm seal Thickness Max. diameter of the process isolating diaphragm b [mm] 20 20 20 [in (mm)] 0.79 (20) 0.79 (20) 0.79 (20) dM [mm] 59 89 89 [in (mm)] 2.32 (59) 3.50 (89) 3.50 (89) [kg] 2.6 4.6 6.2 [kg] 2.6 4.6 6.2 Weight of two diaphragm seals

The specified nominal pressure applies to the diaphragm seal. The maximum pressure for the measuring device is dependent on the lowest-rated element, with regard to pressure, of the selected components. See also → ? 31, "Pressure specifications" section.

Endress+Hauser

b

47

Cerabar M PMC51, PMP51, PMP55

Thread, flush-mounted process isolating diaphragm

SW AF

SW AF

h

x1

dM d1

x1

h

dM

G d2
Process connections PMP55, left: thread ISO 228, right: thread ANSI

NPT d2
P01-PMP75xxx-06-09-xx-xx-003

Threaded connection Version Material Thread Nomin Diamet Diamet Screw-in Across al er er length flats pressur e PN d1 [mm] GTJ GVJ GWJ U5J U7J U8J 1) 316L G1 G1 1/2 A G2 1 MNPT 1 1/2 MNPT 2 MNPT 400 400 400 400 400 400 30 44 56 d2 [mm] 39 55 68 48 60 78 x1 [mm] 211 30 30 28 30 30 41 50 65 41 41 65 SW/AF

Diaphragm seal Max. diaphrag m diameter dM [mm] 30 42 50 24 36 38 Height Diaphra gm seal weight h [mm] 19 20 20 37 20 35 [kg] 0.4 0.9 1.9 0.6 0.9 1.8

28 mm (1.1 in) in conjunction with high-temperature oil

48

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Pipe diaphragm seal (RDM) as per ISO2852

h

L
P01-FMD78xxx-06-09-xx-xx-001

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Nominal diameter ISO2852

Nominal pressure

Nominal diameter

Diameter D [in]

Diameter d2 [mm] 50.5 50.5 64 25 25

Height h [mm] 67 67 79 --67

D d2
Face-to-face length L [mm] 126 126 100 138.5 116

Diaphragm seal weight [kg] 1.7 1.0 1.7 0.6 0.9

SBJ SCJ SDJ SIJ SJJ

DN 25 DN 38 DN 51 DN 10 DN 16

PN40 PN40 PN40 PN40 PN40

1" 1 1/2" 2" 3/4" 3/4"

22.5 35.5 48.6 10.3 15.7

Pipe diaphragm seal (RDM) as per DIN 11851, Threaded adapter

h

L
P01-PMP55xxx-06-xx-xx-xx-000

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Nominal diameter DIN11851

Nominal pressure

Diameter D [in]

Thread G [mm]

Height h [mm] 65 68 75 78

Face-to-face length L [mm] 114 126 146 156

G

D

Diaphragm seal weight [kg] 1.0 1.3 1.9 2.8

SSJ STJ SUJ SZJ

DN 25 DN 32 DN 40 DN 50

PN40 PN40 PN40 PN25

26 32 38 50

Rd 52 x 1/6 Rd 58 x 1/6 Rd 65 x 1/6 Rd 78 x 1/6

Endress+Hauser

49

Cerabar M PMC51, PMP51, PMP55

Pipe diaphragm seal (RDM) as per DIN11864-1

G d

L
P01-PMx5xxxx-06-xx-xx-xx-022

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Nominal diameter DIN11864-1

Nominal pressure

Diameter d [in]

Thread G [mm]

Face-to-face length L [mm] 128 160 170

Diaphragm seal weight

[kg] 1.3 2.0 3.0

VAJ VCJ VDJ

DN 25 DN 40 DN 50

PN40 PN40 PN25

26 38 50

Rd 52 x 1/6 Rd 65 x 1/6 Rd 78 x 1/6

Aseptic pipe fitting, DIN 11864-1 Form A; pipe DIN 11866-1

20

dM d G

30

P01-PMP55xxx-06-xx-xx-xx-001

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Threaded adapter Version Nominal diameter Nominal pressure Diameter Thread

Diaphragm seal Max. diaphragm diameter dM [mm] Rd 65 x 1/6 Rd 78 x 1/6 35 45 [kg] 1.5 2.3 Weight Diaphragm seal

d [mm] NCJ NDJ DN 40 PN 16 DN 50 67 55

G

50

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Aseptic flange connection, DIN 11864-2 Form A; pipe DIN 11866-1

10

dM d K D

30

P01-PMP55xxx-06-xx-xx-xx-002

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Collar flange Version Nominal diameter Nominal pressure Hole circle diameter K [mm] NFJ NXJ NZJ DN 32 DN 40 DN 50 PN 16 59 65 77 Seal diameter Outer diameter d [mm] 47.7 53.7 65.7 D [mm] 76 82 94

Diaphragm seal Max. diaphragm diameter dM [mm] 25 35 45 [kg] 1.5 1.7 2.2 Diaphragm seal weight

Tri-Clamp ISO 2852

h

dM C7
P01-FMD78xxx-06-09-xx-xx-005

Process connection PMP55, material: AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Nominal diameter ISO 2852

Nominal diameter DIN 32676

Nominal diameter [in]

Diameter

Max. diaphragm diameter dM [mm] 24 34 48 73

Height

Diaphragm seal weight [kg] 0.32 1.0 1.1 1.2

C7 [mm] 50.5 50.5 64 91

h [mm] 37 30 30 30

TCJ TJJ
1 1

DN 25 DN 38 DN 51 DN 76.1

DN 25 DN 40 DN 50 –

1 1 1/2 2 3

TDJ TFJ 1)

Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra ≤ 0.38 μm (15 μin), electropolished; to be ordered using feature 570 "Service", version "HK" in the order code.

Endress+Hauser

51

Cerabar M PMC51, PMP51, PMP55

Varivent N for pipes

H 30

dM max.

D
P01-PMx5xxxx-06-xx-xx-xx-019

Process connection PMP55, material AISI 316, 3A, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Description

Nominal pressure

Diameter

Max. diaphragm diameter dM [mm] 30

Max. installation height H [mm]

Diaphragm seal weight

D [bar] TQJ TRJ 1 Type F for tubes DN 25 - DN 32 PN 40 Type N for tubes DN 40 - DN 162 68 [mm] 50

[kg] 0.6

250 64 0.8

1)

Diaphragm seal versions optionally in conformity with ASME-BPE for use in biochemical processes, wetted surfaces Ra ≤ 0.38 μm (15 μin), electropolished; to be ordered using feature 570 "Service", version "HK" in the order code.

DRD DN50 (65 mm)

41

23.6

dM max. =50 ?65–1.2 ?84 ?105

4 x ?11.5

P01-FM78xxx-06-09-xx-xx-002

Process connection PMP55, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Material

Nominal pressure

Diaphragm seal weight [kg]

TIJ

AISI 316L

PN 25

0.75

52

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

SMS nozzles with coupling nut

h m

dM

G D
P01-PMP75xxx-06-09-xx-xx-009

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version Nominal diameter

Nominal Diamete Adapter pressure r height

Thread

Height

f
Height

Max. diaphrag m diameter dM [mm] 24 36 48

Diaphrag m seal weight

D [in] T6J T7J TXJ 1 1 1/2 2 [bar] PN 25 PN 25 PN 25 [mm] 54 74 84

f [mm] 3.5 4 4

G

m [mm]

h [mm] 42.5 57 62

[kg] 0.25 0.65 1.05

Rd 40 – 1/6 Rd 60 – 1/6 Rd 70 – 1/6

20 25 26

APV-RJT nozzles with coupling nut

h m

dM

G D
P01-PMP75xxx-06-09-xx-xx-010

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Version

Nomina l diamete r

Nomina Diamet l er pressur e PN D [mm] 77 72 86

Adapter height

Thread

Height

f
Height

Max. Diaphrag diaphragm m seal diameter weight dM [mm] 21 28 38 [kg] 0.45 0.75 1.2

f [mm] 6.5 6.4 6.4

G

m [mm]

h [mm] 42.6 42.6 42.6

[in] T0J T1J T2J 1 1 1/2 2

[bar] PN 40 PN 40 PN 40

1 13/16 – 1/8" 22 2 5/16 – 1/8" 2 7/8 – 1/8" 22 22

Endress+Hauser

53

Cerabar M PMC51, PMP51, PMP55

APV-ISS nozzles with coupling nut

h

m

SW/AF

dM

G D
P01-PMP75xxx-06-09-xx-xx-011

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Versi Nomin on al diamet er

Nomi Diamet Adapter Thread nal er height pressu re D f [mm] 4 4 4 1 1/2" – 1/8" 2" – 1/8" 2 1/2" – 1/8" G

Height Across flats

f
Height

Max. Diaphra diaphragm gm seal seal weight dM [mm] 24 34 45 [kg] 0.4 0.6 1.1

m [mm] 30 30 30

AF

h [mm]

[in] T3J T4J T5J 1 1 1/2 2

[bar] PN 40 PN 40 PN 40

[mm] 54.1 72 89

46.8 62 77

50 50 50

Taper adapter with coupling nut, DIN 11851

30

m

dM D G
P01-PMx5xxxx-06-xx-xx-xx-020

Process connection PMP55, material AISI 316L, 3A, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Taper adapter Version Nomina l diamete r

Slotted nut

f
Diaphragm seal Height Max. diaphragm diameter m [mm] Rd 58 x 1/6" Rd 65 x 1/6" Rd 78 x 1/6" Rd 95 x 1/6" 21 21 22 35 dM [mm] 32 38 52 66 81 250 Max. installat ion height H [mm] [kg] 1.9 2.0 1.1 2.0 2.55 Diaphra gm seal weight f [mm] 10 10 11 12 12 G Rd 110 x 1/4" 30

Nomin Diameter Adapter Thread al height pressu re D [mm]

MIJ MZJ MRJ MSJ MTJ

DN 32 DN 40 DN 50 DN 65 DN 80

PN 40 PN 40 PN 25 PN 25 PN 25

50 56 68.5 86 100

54

H

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Threaded adapter, DIN 11851

h

dM d1 G
P01-FMD78xxx-06-09-xx-xx-008

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Threaded adapter Version Nominal diameter Nominal pressure Diameter d1 [mm] NKJ NLJ NMJ DN 50 DN 65 DN 80 PN 25 PN 25 PN 25 54 71 85 Rd 78 x 1/6" Rd 95 x 1/6" Thread G

Diaphragm seal Height Max. diaphragm Diaphragm diameter seal weight h [mm] 35 40 dM [mm] 52 66 81 [kg] 0.9 1.7 2.0

Rd 110 x 1/4" 40

NEUMO BioControl
d2

h

dM max.

d

d3 d1 D
P01-PMx5xxxx-06-xx-xx-xx-021

Process connection PMP55, material AISI 316L, surface roughness of the surfaces in contact with the medium Ra ≤ 0.8 μm (31.5 μin) as standard. Lower surface roughness, see feature 570 "Service" version HK.

Threaded adapter Version Nominal diameter Nomin al pressu re Diamet er diamet er D [mm] S4J DN 50 PN 16 90 Hole circle Diameter Diamet er Height

Diaphragm seal Max. diaphragm diameter dM [mm] 40 [kg] 1.1 Diaphrag m seal weight

d1 [mm] 70

d2 [mm] 4x?9

d3 [mm] 50

h [mm] 27

Endress+Hauser

55

Cerabar M PMC51, PMP51, PMP55

EN/DIN flanges, connection dimensions as per EN 1092-1/DIN 2527 and DIN 2501-1

40

g2

dM g k D

f

b

P01-PMP75xxx-06-09-xx-xx-002

Process connection PMP55, EN/DIN flange with flush-mounted process isolating diaphragm, material AISI 316L

Flanges Version Nominal diameter Nominal pressure Shape
1

Boltholes Diameter Thick ness Raised face Quantity Diameter Hole circle

Diaphragm seal Max. diaphragm diameter Diaphragm seal weight

D [mm] CNJ QIJ QJJ QSJ CPJ CQJ CXJ PDJ QOJ QMJ QVJ CZJ PPJ PQJ 1) DN 25 DN 25 DN 25 DN 25 DN 32 DN 40 DN 50 DN 50 DN 50 DN 50 DN 50 DN 80 DN 80 DN 100 PN 10-40 PN 63-160 PN 250 PN 400 PN 10-40 PN 10-40 PN 10-40 PN 63 PN 100-160 PN 250 PN 400 PN 10-40 PN 100 PN 100 B1 (D) E E E B1 (D) B1 (D) B1 (D) B2 (E) E E E B1 (D) B2 (E) B2 (E) 115 140 150 180 140 150 165 180 195 200 235 200 230 265

b [mm] 18 24 28 38 18 18 20 26 30 38 52 24 32 36

g

f

g2 [mm] 4 4 4 4 4 4 4 4 4 8 8 8 8 8 14 18 22 26 18 18 18 22 26 26 30 18 24 30

k [mm] 85 100 105 130 100 110 125 135 145 150 180 160 180 210

dM [mm] 32 28 28 28 34 48 59 59 59 59 59 89 89 89 [kg] 2.1 2.5 3.7 7.0 1.9 2.2 3.0 4.6 6.2 7.7 14.7 5.3 8.9 13.7

[mm] [mm] 66 68 68 68 77 87 102 102 102 102 102 138 138 175 3 2 2 2 2.6 2.6 3 3 3 3 3 3.5 4 5

Designation as per DIN 2527 in brackets

56

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

EN/DIN flanges with extended diaphragm seal, connection dimensions as per EN 1092-1/DIN 2527 and DIN 2501-1

40

g2

f

dM d3 g k D
P01-PMP75xxx-06-09-xx-xx-015

Process connection PMP55, EN/DIN flange with flush-mounted process isolating diaphragm, material AISI 316L

Flanges Version Nominal diameter Nominal pressure Shape 1 Diameter Thick ness b [mm] 20 24

Boltholes Raised face Quantity Diameter Hole circle k [mm] 125 160

L

b
Diaphragm seal Max. diaphragm diameter dM [mm] 47 72 [kg]
2) 2)

Diaphragm seal weight

D [mm] FDJ 2) FEJ 2) 1) 2) DN 50 DN 80 PN 10-40 PN 10-40 B1 (D) B1 (D) 165 200

g

f

g2 [mm] 4 8 18 18

[mm] [mm] 102 138 3 3.5

Designation as per DIN 2527 in brackets Available with 50 mm (1.97 in), 100 mm (3.94 in) or 200 mm (7.87 in) extended diaphragm seal, for extended diaphragm seal diameter and weight see the following table

Version

Nominal diameter

Nominal pressure

Extended diaphragm seal length (L) [mm]

Extended diaphragm seal diameter d3 [mm] 48.3 76

Diaphragm seal weight [kg] 3.2 / 3.8 / 4.4 6.2 / 6.7 / 7.8

FDJ FEJ

DN 50 DN 80

PN 10-40 PN 10-40

50 / 100 / 200 50 /100 / 200

Endress+Hauser

57

Cerabar M PMC51, PMP51, PMP55

ANSI flanges, connection dimensions as per ANSI B 16.5, raised face RF

40

g2

400 – 2500 lb/sq.in 0.25 in (6.4 mm)

150, 300 lb/sq.in 0.06 in (1.6 mm)

dM g k D

b

P01-PMP75xxx-06-09-xx-xx-001

Process connection PMP55, ANSI flange, material AISI 316/316L (Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated))

Flange Version Nominal diameter Class Diameter Thickness Raised face

Boltholes Quantity Diameter Hole circle

Diaphragm seal Max. diaphragm diameter dM [in] / [mm] 1.26 / 32 1.26 / 32 1.26 / 32 1.26 / 32 1.26 / 32 1.89 / 48 1.89 / 48 2.32 / 59 2.32 / 59 2.32 / 59 2.32 / 59 2.32 / 59 3.50 / 89 3.50 / 89 3.50 / 89 3.50 / 89 [kg] 1.2 1.3 1.4 3.2 4.6 1.5 2.6 2.2 3.4 4.3 10.3 15.8 5.1 7.0 7.2 11.7 Diaphrag m seal weight

D [in] ACJ ANJ A0J A2J A4J AEJ AQJ AFJ ARJ A1J A3J A5J AGJ ASJ AHJ ATJ 1 1 1 1 1 1 1/2 1 1/2 2 2 2 2 2 3 3 4 4 [lb./sq.in] 150 300 400/600 900/1500 2500 150 300 150 300 400/600 900/1500 2500 150 300 150 300 [in] / [mm] 4.25 /108 4.88 / 124 4.88 / 124 5.88 / 149.4 6.25 / 158.8 5 / 127 6.12 / 155.4 6 / 152.4 6.5 / 165.1 6.5 / 165.1 8.5 / 215.9 9.25 / 235 7.5 / 190.5 8.25 / 209.5 9 / 228.6 10 / 254

b [in] / [mm] 0.56 / 14.2 0.69 / 17.5 0.69 / 17.5 1.12 / 28.4 1.38 / 35.1 0.69 / 17.5 0.81 / 20.6 0.75 / 19.1 0.88 / 22.4 1 / 25.4 1.5 / 38.1 2 / 50.8 0.94 / 23.9 1.12 / 28.4 0.94 / 23.9 1.25 / 31.8

g [in] / [mm] 2 / 50.8 2 / 50.8 2 / 50.8 2 / 50.8 2 / 50.8 2.88 / 73.2 2.88 / 73.2 3.62 / 91.9 3.62 / 91.9 3.62 / 91.9 3.62 / 91.9 3.62 / 91.9 5 / 127 5 / 127 4 4 4 4 4 4 4 4 8 8 8 8 4 8

g2 [in] / [mm] 0.62 / 15.7 0.75 / 19.1 0.75 / 19.1 1 / 25.4 1 / 25.4 0.62 / 15.7 0.88 / 22.4 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 1 / 25.4 1.12 / 28.4 0.75 / 19.1 0.75 / 19.1 0.75 / 19.1 0.88 / 22.4

k [in] / [mm] 3.12 / 79.2 3.5 / 88.9 3.5 / 88.9 4 / 101.6 4.25 / 108 3.88 / 96.6 4.5 / 114.3 4.75 / 120.7 5 / 127 5 / 127 6.5 / 165.1 6.75 / 171.5 6 / 152.4 6 / 152.4 7.5 / 190.5 7.88 / 200.2

6.19 / 157.2 8 6.19 / 157.2 8

58

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

ANSI flanges with extended diaphragm seal, connection dimensions as per ANSI B 16.5, raised face RF

40

g2

400 – 2500 lb/sq.in 0.25 in (6.4 mm)

150, 300 lb/sq.in 0.06 in (1.6 mm)

dM d3 g k D
P01-PMP75xxx-06-09-xx-xx-016

Process connection PMP55, ANSI flange with extended diaphragm seal, material AISI 316/316L (Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated))

Flange Version Nominal diameter Class Diameter D [in] FMJ 1) FNJ 1) FWJ 1) FOJ 1) FXJ 1) 1) 2 3 3 4 4 [lb./ sq.in] 150 150 300 150 300 [in] / [mm] 6 / 152.4 7.5 / 190.5 Thickness b [in] / [mm] g [in] / [mm] Raised face

Boltholes Quantity Diameter Hole circle

L

b
Diaphragm seal Max. diaphragm diameter dM [in] / [mm] 1.85 / 47 2.83 / 72 2.83 / 72 3.50 / 89 3.50 / 89 [kg]
1) 1) 1) 1) 1)

Diaphragm seal weight

g2 [in] / [mm] 4 4 8 8 8

k [in] / [mm]

0.75 / 19.1 3.62 / 91.9 0.94 / 23.9 5 / 127

0.75 / 19.1 4.75 / 120.7 0.75 / 19.1 6 / 152.4 0.88 / 22.4 6.62 / 168.1 0.75 / 19.1 7.5 / 190.5 0.88 / 22.4 7.88 / 200.2

8.25 / 209.5 1.12 / 28.4 5 / 127 9 / 228.6 10 / 254 0.94 / 23.9 6.19 / 157.2 1.25 / 31.8 6.19 / 157.2

Available with 2 in, 4 in, 6 in or 8 in extended diaphragm seal, for extended diaphragm seal diameter and weight see the following table

Version

Nominal diameter [in]

Class [lb./sq.in] 150 150 300 150 300

Extended diaphragm seal length (L) in (mm) 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2)

Extended diaphragm seal diameter d3 in (mm) 1.9 (48.3) 2.99 (75.9) 2.99 (75.9) 3.7 (94) 3.7 (94)

Diaphragm seal weight [kg] 3.0 / 3.4 / 3.9 / 4.4 6.0 / 6.6 / 7.1 / 7.8 7.9 / 8.5 / 9.0 / 9.6 8.6 / 9.9 / 11.2 / 12.4 13.1 / 14.4 / 15.7 / 16.9

FMJ FNJ FWJ FOJ FXJ

2 3 3 4 4

Endress+Hauser

59

Cerabar M PMC51, PMP51, PMP55

JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF

g2

40

dM g k D
P01-PMP75xxx-06-09-xx-xx-000

Process connection PMP55, JIS flange with raised face RF, material AISI 316L

Flange 1 Versi on Nomin al diamet er Nomin Diamet Thick al er ness pressur e D [mm] KCJ KEJ KFJ KGJ KHJ 1) 2) 25 A 40 A 50 A 80 A 100 A 10 K 10 K 10 K 10 K 10 K 125 140 155 185 210 b [mm] 14 16 16 18 18 Diamete r of raised face g [mm] 67 81 96 127 151 Height of raised face f [mm] 1 2 2 2 2

f

Boltholes Quanti Diamet Hole ty er circle

b

Diaphragm seal Max. Diaphra diaphra gm seal gm weight2 diamet er dM [mm] 32 48 59 89 89 [kg] 1.5 2.0 2.3 3.3 4.4

g2 [mm] 4 4 4 8 8 19 19 19 19 19

k [mm] 90 105 120 150 175

The roughness of the surface in contact with the medium, including the raised face of the flanges (all standards) made of Hastelloy C, Monel or tantalum, is Ra 0.8 μm. Lower surface roughness available on request. Housing weight → ? 64

60

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Thread 1/2 NPT and 1 NPT, separator

?118

?118

76

19

26

SW 27 27 AF ?30

1 NPT SW 36 36 AF ?52
P01-PMP75xxx-06-09-xx-xx-008

Process connection PMP55, version "UGJ" and "UHJ", threaded, material AISI 316L, seal Viton

Version

Measuring range

Description

Nominal pressure

Diaphragm seal weight [kg]

UGJ UHJ

≤ 250 bar ≤ 250 bar

1/2 NPT 1 NPT

PN 250 PN 250

4.75 5.0

Thread ISO 228 G 1/2 A and ANSI 1/2 MNPT, separator

?72.6

?72.6

70

15

1/2 NPT

27

SW 30 AF 30 ?18.4

14

17

3

?4 ?6 G 1/2A
Process connection PMP55, version "UBJ" and "UCJ", welded, material AISI 316L

?11.4 1/2 - 14 NPT
P01-PMP75xxx-06-09-xx-xx-004

Version

Measuring range

Description

Nominal pressure

Diaphragm seal weight [kg]

UBJ UCJ

≤ 160 bar ≤ 160 bar

ISO 228 G 1/2 A ANSI 1/2 MNPT

PN 160 PN 160

1.43 1.43

Endress+Hauser

21.5

20

14

SW 30 AF 30

70

44.5

12

94.5

61

Cerabar M PMC51, PMP51, PMP55

100

100

90

?
SW22 22 AF 6 G?

89

?
SW22 22 AF
1/2 NPT

P01-PMP75xxx-06-09-xx-xx-013

Process connection PMP55, left version "UDJ" threaded, with threaded connection ISO 228 G 1/2 B, right version "UEJ" with threaded connection ANSI 1/2 MNPT 1 PTFE seal as standard max. 260°C (500°F) (higher temperatures on request)

Version

Measuring range

Description

Nominal pressure

Diaphragm seal weight [kg]

UDJ UEJ

≤ 40 bar ≤ 40 bar

ISO 228 G 1/2 B ANSI 1/2 MNPT

PN 40 PN 40

1.43 1.43

?115

?115

84

SW 36

SW 36

19

17

SW 22

?2.5 1/2 NPT

?4 ?6 G 1/2A
P01-PMP75xxx-06-09-xx-xx-007

Process connection PMP55, version "UDJ" and "UEJ", threaded, with integrated seal lip, material AISI 316L

Version

Measuring range

Description

Nominal pressure

Diaphragm seal weight [kg]

UDJ UEJ

> 40 bar > 40 bar

ISO 228 G 1/2 A ANSI 1/2 MNPT

PN 400 PN 400

4.75 4.75

62

Endress+Hauser

3

20

92.5

Cerabar M PMC51, PMP51, PMP55

Universal adapter

b
?43.5

a

H

P01-PMP55xxx-06-xx-xx-xx-003

Material: b = top section AISI 316L (1.4404), a = bottom section AISI 316L (1.4435); Surface roughness of the surfaces in contact with the medium Ra ≤ 0.76 μm (30 μin) as standard. Lower surface roughness available on request. Process connection PMP55, version UPJ 1: universal adapter incl. silicone molded seal, EHEDG, 3A Class I, FDA 21 CFR 177.2600, USP Plastic Class VI-70C; Order no.: 52023572

Installation height H, devices with universal adapter
F31 housing Universal adapter 196 mm (7.72 in) F15 housing 189 mm (7.44 in)

1)

Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material number 1.4307).

Endress+Hauser

63

Cerabar M PMC51, PMP51, PMP55

Wall and pipe mounting with mounting bracket

69

112

127

?

?

122 158

52

140 175

70

63

86

95

114

?

?

?52
P01-xMx5xxxx-06-xx-xx-xx-004

F31 housing dimensions. Housing weight → ? 64. ? Cover without viewing window. ? Cover with viewing window. F15 housing dimensions. Housing weight → ? 64. ? Cover without viewing window. ? Cover with viewing window.

Weight

Housing
F31 (aluminum) With electronic insert and local display With electronic insert without local display 1.1 kg (2.43 lbs) 1.0 kg (2.21 lbs) F15 (stainless steel) 0.8 kg (1.76 lbs) 0.7 kg (1.54 lbs) Weight of housing + 0.5 kg (1.10 lbs). Weight of sensor + 0.5 kg (1.10 lbs). Separate housing

Process connections ? Process connections PMC51 (with ceramic process isolating diaphragm): → ? 32 ff ? Process connections PMP51 (with metal process isolating diaphragm): → ? 41 ff ? Process connections PMP55 (with diaphragm seal): → ? 47 ff

64

?6

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Material (not wetted)

Housing

14 13 15

16

1

2 6 9 10 12 11 7
P01-xMxx3xxx-14-xx-xx-xx-002

8 5 4

3

Front view, left-hand side view, top view

Item number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Component part F31 housing, RAL 5012 (blue) Cover, RAL 7035 (gray) Cover seal Sight glass Sight glass seal External ground terminal Nameplates Attachement for tie-on label Pressure compensation filter Pressure compensation filter, O-ring Sealing ring Snap ring Seal of cable gland and blind plug Cable gland Blind plug

Material Die-cast aluminum with protective powder-coating on polyester base Die-cast aluminum with protective powder-coating on polyester base EPDM Mineral glass Silicone (VMQ) AISI 304 (1.4301) Plastic film AISI 304 (1.4301)/ AISI 316 (1.4401) PA6 GF10 Silicone (VMQ) EPDM PC Plastic EPDM/NBR Polyamide (PA) or CuZn nickel-plated PBT-GF30 FR for dust ignition-proof, Ex d, FM XP and CSA XP: AISI 316L (1.4435) Clamp AISI 316L (1.4435), screw A4

16

Cover clamp

Endress+Hauser

65

Cerabar M PMC51, PMP51, PMP55

14 1 7 6 2 3 5 13 12 11 10 9 8 4

P01-xMxx3xxx-14-xx-xx-xx-002

Front view, left-hand side view, top view

Item number 1 2 3 4

4

5 6 7 8 9 10 11 12 13 14

Component part F15 housing Cover Cover seal Sight glass for non-hazardous area, ATEX Ex ia, NEPSI Zone 0/1 Ex ia, IECEx Zone 0/1 Ex ia, FM NI, FM IS, CSA IS Sight glass for ATEX 1/2 D, ATEX 1/3 D, ATEX 1 GD, ATEX 1/2 GD, ATEX 3 G, FM DIP, CSA dust ignition-proof Sight glass seal External ground terminal Attachement for tie-on label Pressure compensation filter Pressure compensation filter, O-ring Nameplates Cable gland Seal of cable gland and blind plug Sealing ring Screw

Material AISI 316L (1.4404) Silicone with PTFE coating Polycarbonate (PC)

Mineral glass Silicone (VMQ) AISI 304 (1.4301) AISI 304 (1.4301)/ AISI 316 (1.4401) PA6 GF10 Silicone (VMQ) lasered Polyamide (PA), for dust ignition-proof: CuZn nickel-plated NBR/Silicone/EPDM EPDM A4-50

66

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Connecting parts

4

4

1 5 6 2 3 7 8 1 9

6 5

P01-PMx5xxxx-06-xx-xx-xx-026

Item number Component part 1 Connection between the housing and process connection 2 Mounting bracket 3 4 5 Seal for cable from separate housing 6 Gland for cable from separate housing: Screws: 7 PE cable for separate housing

Material AISI 316L (1.4404) Bracket AISI 304 (1.4301), AISI 304L (1.4306) Screw and nuts A2-70 Half-shells: AISI 304L (1.4306) FKM, EPDM AISI 316L (1.4404) A2 or A4 Abrasion-proof cable with strain-relief Dynema members; shielded using aluminum-coated film; insulated with polyethylene (PE-LD), black; copper wires, twisted, UV-resistant Abrasion-proof cable; shielded using galvanized steel wire netting; insulated with fluorinated ethylene propylene (FEP), black; copper wires, twisted, UV-resistant AISI 316L (1.4404)

8

FEP cable for separate housing

9

Process connection adapter for separate housing

Filling oil See "Ordering information" (→ ? 79) Miscellaneous: ? Diaphragm seal capillary: AISI 316 Ti (1.4571) ? Protective hose for diaphragm seal capillary: AISI 304 (1.4301)

Endress+Hauser

67

Cerabar M PMC51, PMP51, PMP55

Material (wetted)

Note! The wetted device components are listed in the "Mechanical construction" (→ ? 32 ff) and "Ordering information" (→ ? 79 ff) sections. TSE Certificate of Suitability (Transmissible Spongiform Encephalopathy) The following applies to all process wetted device components: ? They do not contain any materials derived from animals. ? No auxiliaries or operating materials derived from animals are used in production or processing. Process connections ? "Clamp connections" and "Hygienic process connections" (see also "Ordering information" section): AISI 316L (DIN/EN material number 1.4435) ? Endress+Hauser supplies process connections with threaded connections and DIN/ EN flanges made of stainless steel as per AISI 316L (DIN/EN material number 1.4404 (AISI 316) or 14435). With regard to their stability-temperature property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN 1092-1 Tab.18. The chemical composition of the two materials can be identical. ? Some process connections are also available in the material Alloy C276 (DIN/EN material number 2.4819). See the information in the "Mechanical construction" section. Process isolating diaphragm ? PMC51: Al2O3 aluminum-oxide ceramic, Ceraphire? (FDA 21 CFR 186.1256, USP Class VI), ultrapure 99.9 % (→ see also www.endress.com/ceraphire) ? PMP51: – AISI 316L (DIN/EN material number 1.4435) – AISI 316L with gold-rhodium coating – Alloy C276 (DIN/EN material number 2.4819) ? PMP55: – AISI 316L (DIN/EN material number 1.4435) – AISI 316L with gold-rhodium coating – AISI 316L with 0.09 mm PTFE foil (not for vacuum applications) – AISI 316L with 0.25 mm PTFE foil (not for vacuum applications, only for non-hazardous areas) – Alloy C276 (DIN/EN material number 2.4819) – Monel – Tantalum Seals See ordering information, → ? 79 ff

68

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Human interface
Operating elements Local display (optional) for devices with HART, PROFIBUS PA or FOUNDATION Fieldbus electronics A 4-line liquid crystal display (LCD) is used for display and operation. The local display shows measured values, dialog texts as well as fault and notice messages in plain text, thereby supporting the user at every stage of operation. The liquid crystal display of the device can be turned in 90° stages. Depending on the orientation of the device, this makes it easy to operate the device and read the measured values. Functions: ? 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA HART as current display; or for PROFIBUS PA as graphic display of the standardized value of the AI Block; for FOUNDATION Fieldbus as graphic display of the transducer output in relation to the set pressure range. ? Three keys for operation ? Simple and complete menu guidance as parameters are split into several levels and groups ? Each parameter is given a 3-digit ID number for easy navigation ? Possibility of configuring the display to suit individual requirements and preferences, such as language, alternating display, contrast setting, display of other measured values such as sensor temperature etc. ? Comprehensive diagnostic functions (fault and warning message etc.)

Measured value display Device tag Value

Header line Main line Information line
– + E

Symbol Unit

Bargraph Operating keys Operating menu

Parameter with selection list Direct Access Code

Selection options

Freely editable parameter

Value that can be edited
P01-Mxxxxxxx-07-xx-xx-en-002

Endress+Hauser

69

Cerabar M PMC51, PMP51, PMP55

Local display (optional) for devices with analog electronics A 4-line liquid crystal display (LCD) is used. The local display shows measured values, fault messages and notice messages. The liquid crystal display of the device can be turned in 90° stages. Depending on the orientation of the device, this makes it easy to operate the device and read the measured values. Functions: ? 8-digit measured value display including sign and decimal point, bar graph for 4 to 20 mA as current display. ? Diagnostic functions (fault and warning message etc.)

Measured value display Value
F

F
Main line Information line Bargraph

Symbol Unit

P01-Mxxxxxxx-07-xx-xx-en-002

Operating keys and elements located on the electronic insert

? ?

Zero Span

Display

?
on off
damping SW / Alarm min
SW / ? SW / P2=High

? ?

Zero Span

Display

?
on off

delta p only

on
1 2 3 4 5

damping

on
1

off

off

damping SW / Alarm min

SW / ? SW / P2=High

? ?? ?
P01-Mxxxxxxx-19-xx-xx-xx-001

?
P01-Mxxxxxxx-19-xx-xx-xx-010

HART electronic insert 1 2 3 4 5 6 7 DIP switch for locking/unlocking parameters relevant to the measured value DIP switch for switching damping on/off DIP switch for alarm current SW / Alarm Min (3.6 mA) DIP switch only for Deltabar M Slot for optional local display Green LED to indicate successful operation Operating keys for lower range value (zero), upper range value (span), position zero adjustment or reset

Analog electronic insert 1 2 3 4 Operating keys for lower range value (zero), upper range value (span), position zero adjustment or reset Green LED to indicate successful operation Slot for optional local display DIP switch for switching damping on/off

70

damping

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

9 10
Zero
1 2 3 4 5

Display

?
on off
SW HW Address

? ?
TM

Zero

Display

?
on off
damping simulation SW / ? SW / P2=High delta p only

damp not used off:SW delta p on:? only on:P2=High off:SW

FOUNDATION

on off

on
1 2 3 4 5

?

?
1 2 3 4 5

on off

off

SW / ? SW / P2=High

? ? ? ??
P01-Mxxxxxxx-19-xx-xx-xx-013

? ? ? ??
P01-Mxxxxxxx-19-xx-xx-xx-014

PROFIBUS PA electronic insert 1 DIP switch for locking/unlocking parameters relevant to the measured value 2 DIP switch for switching damping on/off 3/4/5 Not used 6 DIP-switch for hardware address 7 DIP-switch for bus address SW / HW 8 Slot for optional local display 9 Operating key for position zero adjustment (Zero) or reset 10 Green LED to indicate successful operation

FOUNDATION Fieldbus electronic insert 1 2 3 4/5 6 7 8 DIP switch for locking/unlocking parameters relevant to the measured value DIP switch for switching damping on/off DIP-switch for simulation mode Not used Slot for optional local display Green LED to indicate successful operation Operating key for position zero adjustment (Zero) or reset

Onsite operation
Function Operation without display with operating keys and DIP-switches on the electronic insert Analog electronics Position adjustment (zero point correction) Setting lower range value and upper range value reference pressure present at the device Device reset Locking and unlocking parameters relevant to the measured value Value acceptance indicated by the green LED Switching damping on and off X X X -X X HART X X X X X X PROFIBUS PA X -X X X X FOUNDATION Fieldbus X -X X X X

Function Analog electronics Position adjustment (zero point correction) Setting lower range value and upper range value reference pressure present at the device Device reset Locking and unlocking parameters relevant to the measured value Value acceptance indicated by the green LED Switching damping on and off -------

Operation via display (option) HART X X X X -X PROFIBUS PA X X X X -X FOUNDATION Fieldbus X X X X -X

Endress+Hauser

damping Simulation SW / ? SW / P2=High

damping

71

Cerabar M PMC51, PMP51, PMP55

Remote operation

All software parameters are accessible depending on the position of the write protection switch on the device. HART Remote operation via: ? FieldCare (see "Hardware and software for onsite and remote operation" section → ? 73 ff) with Commubox FXA195 (see "Hardware and software for onsite and remote operation" section → ? 73 ff) ? Field Xpert. Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520. Field Xpert also works as a stand-alone device for asset management applications. For details refer to BA00060S/00/ EN. ? Field Communicator 375 handheld terminal see "Hardware and software for onsite and remote operation" section → ? 73). PROFIBUS PA Remote operation via: ? FieldCare (see "Hardware and software for onsite and remote operation" section → ? 73 ff) – Profiboard: For connecting a PC to PROFIBUS – Proficard: For connecting a laptop to PROFIBUS FOUNDATION Fieldbus Remote operation via: ? FieldCare (see "Hardware and software for onsite and remote operation" → ? 73 ff) – NI PCMCIA-FBUS series 2 to connect a laptop to FF. ? Use an FF-configuration program for example NI-FBUS Configurator, to – connect devices with "FOUNDATION Fieldbus signal" into an FF-network – set FF-specific parameters Operation with NI-FBUS Configurator: The NI-FBUS Configurator is an easy-to-use graphical environment for creating linkages, loops, and a schedule based on the fieldbus concepts. You can use the NI-FBUS Configurator to configure a fieldbus network as follows: – Set block and device tags – Set device addresses – Create and edit function block control strategies (function block applications) – Configure vendor-defined function and transducer blocks – Create and edit schedules – Read and write to function block control strategies (function block applications) – Invoke Device Description (DD) methods – Display DD menus – Download a configuration – Verify a configuration and compare it to a saved configuration – Monitor a downloaded configuration – Replace a virtual device by a real device – Save and print a configuration ? Handheld terminal Field Communicator 375 (see "Hardware and software for onsite and remote operation" section → ? 73 ff) Note! For further information please contact your local Endress+Hauser Sales Center.

72

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Hardware and software for onsite and remote operation

Commubox FXA195 For intrinsically safe HART communication with FieldCare via the USB interface. For details refer to TI00404F/00/EN. Field Communicator 375 With a handheld terminal, all the parameters can be configured anywhere along the bus line via menu operation (HART and FOUNDATION Fieldbus). FieldCare FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. FieldCare supports the following functions: ? Configuration of transmitters in offline and online mode ? Loading and saving device data (upload/download) ? Documentation of the measuring point Connection options: ? HART via Commubox FXA195 and the USB port on a computer ? PROFIBUS PA via segment coupler and PROFIBUS interface card ? FOUNDATION Fieldbus via NI interface card For further information ? www.endress.com

Endress+Hauser

73

Cerabar M PMC51, PMP51, PMP55

Planning instructions for diaphragm seal systems
Note! The performance and the permitted applications for a diaphragm seal system depend on the process isolating diaphragm used, the filling oil, the coupling, the design and the process and ambient conditions at the place of operation. To help you select suitable diaphragm seal systems for your individual application, Endress+Hauser provides a free "Applicator Sizing Diaphragm Seal" selection tool. This tool is available online at "www.endress.com/applicator", or is available offline on a CD.

Applicator Sizing Diaphragm Seal PMP55-en

For further details, or for information on an optimum diaphragm seal solution, please contact your local Endress+Hauser Sales Center. Applications Diaphragm seal systems should be used if the process and the device need to be separated. Diaphragm seal systems offer clear advantages in the following instances: ? In the case of extreme process temperatures ? For aggressive media ? If extreme measuring point cleaning is necessary, or in the event of very damp mounting locations ? If the measuring point is exposed to severe vibrations ? For mounting locations that are difficult to access Diaphragm seals separate the measuring system from the process. A diaphragm seal system consists of: ? A diaphragm seal ? A capillary tube or a temperature isolator if necessary ? Fill fluid ? A pressure transmitter The process pressure acts via the process isolating diaphragm of a diaphragm seal on the liquid-filled system, which transfers the process pressure to the sensor of the pressure transmitter. Endress+Hauser delivers all diaphragm seal systems as welded versions. The system is hermetically sealed, which ensures greater reliability. The diaphragm seal determines the application range of the system on the basis of ? The diameter of the process isolating diaphragm ? The process isolating diaphragm: stiffness and material ? The design (oil volume)

Function and design

74

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Diameter of the process isolating diaphragm The greater the diameter of the process isolating diaphragm (less stiff), the smaller the temperature effect on the measurement result. Stiffness of the process isolating diaphragm The stiffness depends on the diameter of the process isolating diaphragm, the material, any existing coating, the thickness of the process isolating diaphragm and the shape. The thickness of the process isolating diaphragm and the shape are determined by the design. The stiffness of a process isolating diaphragm of a diaphragm seal influences the temperature application range and the measuring error caused by temperature effects. Capillary Capillaries with an internal diameter of 1 mm (0.04 in) are used as standard. As a result of its length and internal diameter, the capillary tube influences the thermal change, the ambient temperature application range and the response time of a diaphragm seal system. Filling oil When selecting the filling oil, the medium temperature and ambient temperature, as well as the process pressure, are of crucial importance. Observe the temperatures and pressures during commissioning and cleaning. A further selection criterion is the compatibility of the filling oil with the requirements of the medium. For example, only filling oils that do not present a health hazard are used in the food industry, e.g. vegetable oil or silicone oil. → See also the following section "Diaphragm seal filling oils". The filling oil used influences the thermal change, the temperature application range of a diaphragm seal system and the response time. A temperature change results in a volume change in the filling oil. The volume change depends on the thermal expansion coefficient of the filling oil and on the volume of the fill fluid at calibration temperature (constant in the range: +21 to +33°C (+70 to 91°F)). For example, the filling oil expands in the event of a temperature increase. The additional volume presses against the process isolating diaphragm of a diaphragm seal. The stiffer a process isolating diaphragm is, the greater its return force, which counteracts a volume change and acts together with the process pressure on the measuring cell, thus shifting the zero point. Pressure transmitter The pressure transmitter influences the temperature application range, the thermal change and the response time as a result of its volume change. The volume change is the volume that has to be shifted in order to pass through the complete measuring range. Pressure transmitters from Endress+Hauser are optimized with regard to minimum volume change. Diaphragm seal filling oils
Ver sion1 Filling oil Permissible temperature range 2 at 0.05 bar (0.725 psi) ≤ pabs ≤ 1 bar (14.5 psi) –40 to +180°C (–40 to +356°F) –40 to +80°C (–40 to +176°F) –10 to +120°C (+14 to +248°F) –10 to +200°C (+14 to +392°F) –70 to +80°C (–94 to +176°F) Permissible Density Viscosity temperature range2 at [g/cm3] / [mm?/s] / [cSt] pabs ≥ 1 bar (14.5 psi) [SGU] at 25°C (77°F) –40 to +250°C (–40 to +482°F) –40 to +175°C (–40 to +347°F) –10 to +200°C (+14 to +392°F) –10 to +400°C (+14 to +752°F) –70 to +180°C (–94 to +356°F) 0.96 1.87 0.94 1.07 100 27 9.5 37 Thermal expansion coefficient 3 [1/K] 0.00096 0.000876 0.00101 0.0007 Note

1 2 4 5

Silicone oil Inert oil Vegetable oil Hightemperature oil 4 Low-temperat ure oil

Suitable for foods FDA 21 CFR 175.105 For ultrapure gas and oxygen applications Suitable for foods FDA 21 CFR 172.856 High temperatures

6

0.92

4.4

0.00108

Low temperatures

1) 2) 3) 4)

Version for feature 180 in the order code (→ ? 89 ff) Observe temperature limits of the device (→ ? 30) and of the system (→ ? 74). Please refer to the "Applicator Sizing Diaphragm Seal" tool for the thermal change of the diaphragm seal and other important technical features. When simultaneously applying the diaphragms seal at high process temperatures and low absolute pressures, Endress+Hauser recommends the vacuum service (Feature 570 "Service" version "HG").

Endress+Hauser

75

Cerabar M PMC51, PMP51, PMP55

Operating temperature range

The operating temperature range of a diaphragm seal system depends on the fill fluid, capillary length and internal diameter, process temperature and oil volume of the diaphragm seal. The range of application can be extended by using a fill fluid with a smaller expansion coefficient and a shorter capillary. Diaphragm seal systems ? Endress+Hauser offer flushing rings as accessory to clean process isolating diaphragms without taking the transmitters out of process. For further information please contact your local Endress+Hauser Sales Center. ? A diaphragm seal together with the transmitter form a closed, calibrated system, which is filled through openings in the diaphragm seal and in the transmitter's measurement system. These openings are sealed and must not be opened. ? In the case of devices with diaphragm seals and capillaries, the zero point shift caused by the hydrostatic pressure of the filling liquid column in the capillaries must be taken into account when selecting the measuring cell. If a measuring cell with a small measuring range is selected, a position adjustment can cause range violation. ? For devices with a temperature isolator or capillary, a suitable fastening device (mounting bracket) is recommended. ? When using diaphragm seal systems with a capillary, sufficient strain relief must be ensured in order to prevent the capillary bending down (bending radius ≥ 100 mm (3.94 in)). Capillary In order to obtain more precise measurement results and to avoid a defect in the device, mount the capillaries as follows: ? Vibration-free (in order to avoid additional pressure fluctuations) ? Not in the vicinity of heating or cooling lines ? Insulate if the ambient temperature is below or above the reference temperature ? With a bending radius of ≥ 100 mm (3.94 in). Vacuum applications For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the diaphragm seal. This prevents vacuum loading of the diaphragm seal caused by the presence of fill fluid in the capillary. When the pressure transmitter is mounted above the diaphragm seal, the maximum height difference H1 in accordance with the illustration below must not be exceeded. The maximum height difference depends on the density of the filling oil and the smallest ever pressure that is permitted to occur at the diaphragm seal (empty container), see illustration below right. When simultaneously applying the diaphragm seal systems at high process temperatures and low absolute pressures, Endress+Hauser recommends the vacuum service (Feature 570 "Service" version "HG").

Installation instructions

12.0 Low temperature oil Height difference H1 [m] 10.0
8.0

Vegetable oil Silicone oil

6.0 4.0 2.0
0.0

H1

High temperature oil Inert oil

50 100 200

300

400

500

600

700

800

900 1000

Pressure at diaphragm seal [mbarabs]
P01-PMx5xxxx-11-xx-xx-xx-006 P01-PMP75xxx-05-xx-xx-xx-011

Installation above the diaphragm seal

Maximum installation height above the diaphragm seal for vacuum applications

76

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Thermal insulation The PMP55 may only be insulated up to a certain height. The maximum permitted insulation height is indicated on the devices and applies to an insulation material with a heat conductivity ≤ 0.04 W/(m x K) and to the maximum permitted ambient and process temperature. The data were determined under the most critical application "quiescent air".

TU

l ? 0.04 W m?K

TP
P01-PMx5xxxx-11-xx-xx-en-010

Maximum permitted insulation height, here indicated on a PMP55 with a flange

Mounting with temperature isolator Endress+Hauser recommends the use of temperature isolators in the event of constant extreme medium temperatures which lead to the maximum permissible electronics temperature of +85°C (+185°F) being exceeded. Depending on the filling oil used, diaphragm seal systems with temperature isolators can be used for maximum temperatures of up to 260 °C (+500 °F). → For the temperature application limits, see → ? 75, "Diaphragm seal filling oils" section. To minimize the influence of rising heat, Endress+Hauser recommends the device be mounted horizontally or with the housing pointing downwards. The additional installation height also brings about a maximum zero point shift of 21 mbar (0.315 psi) due to the hydrostatic column in the temperature isolator. You can correct this zero point shift at the device.

max. 115
P01-PMx5xxxx-11-xx-xx-xx-001

PMP55 with temperature isolator

Endress+Hauser

77

Cerabar M PMC51, PMP51, PMP55

Certificates and approvals
CE mark The device meets the legal requirements of the relevant EC directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. ? ? ? ? ? ATEX IECEx FM CSA Also combinations of different approvals

Ex approvals

All explosion protection data are given in separate documentation which is available upon request. The Ex documentation is supplied as standard with all devices approved for use in explosion hazardous areas. → ? 95 ff, "Safety Instructions" and "Installation/Control Drawings" sections. Suitability for hygienic processes The Cerabar M is suitable for use in hygienic processes. Overview of suitable process connections → ? 32 ff. Many versions meet the requirements of 3A-Sanitary Standard No. 74 and are certified by the EHEDG. Suitable fittings and seals must be used for hygienic design in accordance with 3A and EHEDG specifications. Note! Gap-free connections can be cleaned without residue using the usual cleaning methods. Pharma (CoC) Certificate of Compliance (CoC) (according to ASME BPE-2007) See "Ordering information", → ? 79 ff, feature 590 "Additional Option:", option"LW". CRN approvals Some device versions have CRN approval. For a CRN-approved device, a CRN-approved process connection (→ ? 32 ff, "Process connection") has to be ordered with a CSA approval (→ ? 79 ff, feature 10 "Approval"). PMP55 devices with a capillary are not CRN-approved. These devices are fitted with a separate plate bearing the registration number 0F10525.5C. The devices PMC51, PMP51 and PMP55 correspond to Article 3 (3) of the EC directive 97/23/EC (Pressure Equipment Directive) and have been designed and manufactured according to good engineering practice. The following also applies: – PMP51/PMP55 with threaded connection and internal process isolating diaphragm PN > 200: Suitable for stable gases in group 1, category I – PMP55 with pipe diaphragm seal ≥ 1.5"/PN40: Suitable for stable gases in group 1, category II – PMP55 with separators PN400: Suitable for stable gases in group 1, category I Drinking water approval Standards and guidelines NSF 61 approval DIN EN 60770 (IEC 60770): Transmitters for use in industrial process control systems Part 1: Methods for inspection and routine testing DIN 16086: Electrical pressure measuring instruments, pressure sensors, pressure transmitters, pressure measuring instruments, concepts, specifications on data sheets EN 61326 series: EMC product family standard for electrical equipment for measurement, control and laboratory use.

February 2010

TYPE EL

74 -

Pressure Equipment Directive (PED)

78

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Ordering information
PMC51 This overview does not mark options which are mutually exclusive.
10 Approval:
AA BA BD BE BF BG B1 8C For non-hazardous areas ATEX II 1/2G Ex ia IIC T6 ATEX II 3G Ex nA IIC T6 ATEX II 2G Ex ia IIC T6 ATEX II 1/2D Ex ia IIIC ATEX II 3G Ex ic IIC T6 ATEX II 1/2G Ex ia IIC T6 + ATEX II 1/2D Ex iaD ATEX II Ex ia + FM/CSA IS ATEX II 1/2G Ex ia IIC T6+ FM/CSA IS Cl.I Div. 1 Gr. A-D FM/CSA: zone0,1,2 IEC Ex ia IIC T6 Ga/Gb IEC Ex ic IIC T6 Gc IEC Ex ia IIIC Da/ Db IEC Ex ia IIC T6 Ga/Gb+Ex ia IIIC Da/Db NEPSI Ex ia IIC T6 CSA C/US IS Cl.I,II,III Div.1 Gr. A-G, CSA C/US IS Cl.I Div.2 Gr. A-D, Ex ia, C: Zone 0, 1, 2/US: Zone 0, 1, 2, 20, 21, 22 CSA General Purpose FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia FM NI Cl.I Div.2 Gr.A-D FM IS: Zone 0,1,2,20,21,22/FM NI: Zone 2 FM NI Cl.I Div.2 Gr.A-D Special version

IA IE IF I1 NA CA CD FA

FD 99

20

Output:
1 2 3 4 9 4-20mA Analog 4-20mA HART PROFIBUS PA FOUNDATION Fieldbus Special version

30

Display, operation:
1 2 9 LCD, push buttons on display electronics W/o LCD, push buttons on electronics Special version

40

Housing:
I J Q R S Y F31 aluminum F31 aluminum, glass window F15 Stainless Steel Hygiene F15 Stainless Steel Hygiene, glass window F15 Stainless Steel Hygiene, plastic window Special version

50

Electrical connection:
A B C D I M P S V Y Gland M20, IP66/68 NEMA4X/6P Thread M20, IP66/68 NEMA4X/6P Thread G1/2, IP66/68 NEMA4X/6P Thread NPT1/2, IP66/68 NEMA4X/6P Connector M12, IP66/67, NEMA4X/6P Connector 7/8", IP66/68, NEMA4X/6P Connector Han7D, 90deg, IP65 PE Cable 5m, IP66/68 NEMA4X/6P + pressure compensation via cable Valve connector ISO4400 M16, IP64 Special version

Endress+Hauser

79

Cerabar M PMC51, PMP51, PMP55

PMC51 (continued)

70

Sensor range:
1C 100mbar/10kPa/1.5psi relative, 1mH2O/3ftH2O/40inH2O Overload: 4bar/400kPa/60psi 250mbar/25kPa/3.75psi relative, 2.5mH2O/7.5ftH2O/100inH2O Overload: 5bar/500kPa/75psi 400mbar/40kPa/6psi relative, 4mH2O/13ftH2O/160inH2O Overload: 8bar/800kPa/120psi 1bar/100kPa/15psi relative, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi relative, 20mH2O/67ftH2O/800inH2O Overload: 18bar/1.8MPa/270psi 4bar/400kPa/60psi relative, 40mH2O/133ftH2O/1600inH2O Overload: 25bar/2.5MPa/375psi 10bar/1MPa/150psi relative, 100mH2O/333ftH2O/4000inH2O Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi relative, 400mH2O/1334ftH2O/16000inH2O Overload: 60bar/6MPa/900psi 100mbar/10kPa/1.5psi abs, 1mH2O/3ftH2O/40inH2O Overload: 4bar/400kPa/60psi 250mbar/25kPa/3.75psi abs, 2.5mH2O/7.5ftH2O/100inH2O Overload: 5bar/500kPa/75psi 400mbar/40kPa/6psi abs, 4mH2O/13ftH2O/160inH2O Overload: 8bar/800kPa/120psi 1bar/100kPa/15psi abs, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi abs, 20mH2O/67ftH2O/800inH2O abs Overload: 18bar/1.8MPa/270psi 4bar/400kPa/60psi abs, 40mH2O/133ftH2O/1600inH2O abs Overload: 25bar/2.5MPa/375psi 10bar/1MPa/150psi abs, 100mH2O/333ftH2O/4000inH2O abs Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi abs, 400mH2O/1334ftH2O/16000inH2O abs Overload: 60bar/6MPa/900psi Special version

1E

1F

1H

1K

1M

1P

1S

2C

2E

2F

2H

2K

2M

2P

2S

99

80

Reference accuracy:
D G Y Platinum Standard Special version

90

Calibration; Unit:
A B C D E F J K Y Sensor range; % Sensor range; mbar/bar Sensor range; kPa/MPa Sensor range; mm/mH2O Sensor range; inH2O/ftH2O Sensor range; psi Customized pressure; see additional spec. Customized level; see additional spec. Special version

80

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMC51 (continued)

110

Process connection:
ANSI flanges ACJ 1" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AEJ 1-1/2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AFF 2" 150lbs RF, PVDF, flange ANSI B16.5 AFJ 2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AFN 2" 150lbs, ECTFE>316/316L, flange ANSI B16.5 AGF 3" 150lbs RF, PVDF, flange ANSI B16.5 (CRN) AGJ 3" 150lbs RF, 316/316L, flange ANSI B16.5 AGN 3" 150lbs, ECTFE>316/316L, flange ANSI B16.5 AHJ 4" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AHN 4" 150lbs, ECTFE>316/316L, flange ANSI B16.5 ANJ 1" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) AQJ 1-1/2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ARJ 2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ASJ 3" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ATJ 4" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) EN flanges CNJ DN25 PN10-40 B1, 316L, flange EN1092-1 CPJ DN32 PN10-40 B1, 316L, flange EN1092-1 CQJ DN40 PN10-40 B1, 316L, flange EN1092-1 CXJ DN50 PN10-40 B1, 316L, flange EN1092-1 CFF DN50 PN10/16 B1, PVDF, flange EN1092-1 CEF DN40 PN10/16 B1, PVDF, flange EN1092-1 CRP DN50 PN25/40, ECTFE>316L, flange EN1092-1 CZJ DN80 PN10-40 B1, 316L, flange EN1092-1 CSP DN80 PN25/40, ECTFE>316L, flange EN1092-1 JIS flanges KFJ 10K 50 RF, 316L, flange JIS B2220 KGJ 10K 80 RF, 316L, flange JIS B2220 KHJ 10K 100 RF, 316L, flange JIS B2220 Threaded connection GCC Thread ISO228 G1/2, AlloyC (CRN) GCF Thread ISO228 G1/2, PVDF GCJ Thread ISO228 G1/2, 316L (CRN) GLC Thread ISO228 G1/2 G1/4 female, AlloyC (CRN) GLJ Thread ISO228 G1/2 G1/4 female, 316L (CRN) GMC Thread ISO228 G1/2 hole 11.4mm, AlloyC (CRN) GMJ Thread ISO228 G1/2 hole 11.4mm, 316L (CRN) GOJ Thread JIS B0203 R1/2 male, 316L GNJ Thread JIS B0202 G1/2 male, 316L GVJ Thread ISO228 G1-1/2, 316L, flush-mounted (CRN) GWJ Thread ISO228 G2, 316L, flush-mounted (CRN) G4J Thread DIN13 M44x1.25, 316L, flush-mounted Threaded connection as per ANSI RJF Thread ANSI MNPT1/2 hole 3mm, PVDF (CRN) RKC Thread ANSI MNPT 1/2 hole, 11.4mm, Alloy C (CRN) RKJ Thread ANSI MNPT1/2 hole 11.4mm, 316L (CRN) RLC Thread ANSI MNPT1/2 FNPT1/4, AlloyC (CRN) RLJ Thread ANSI MNPT1/2 FNPT1/4, 316L (CRN) R1C Thread ANSI FNPT 1/2, Alloy C (CRN) R1J Thread ANSI FNPT 1/2, 316L (CRN) U7J Thread ANSI MNPT1-1/2, 316L, flush-mounted (CRN) U8J Thread ANSI MNPT2, 316L, flush-mounted (CRN)

Endress+Hauser

81

Cerabar M PMC51, PMP51, PMP55

110

Process connection:
Hygienic process connections MRJ DIN11851 DN50 PN25 cap-nut, 316L, EHEDG1), 3A2) with seal FDA MZJ DIN11851 DN40 PN25 cap-nut, 316L, EHEDG1), 3A2) with seal FDA NCJ DIN11864-1 A DN40 PN16 pipe DIN11866-A, threaded adapter, 316L, EHEDG1), 3A2) with seal FDA NDJ DIN11864-1 A DN50 PN16 pipe DIN11866-A, threaded adapter, 316L, EHEDG1), 3A2) with seal FDA TQJ Varivent F pipe DN25-32 PN40, 316L, EHEDG1), 3A2) with seal FDA TRJ Varivent N pipe DN40-162 PN40, 316L, EHEDG1), 3A2) with seal FDA S4J NEUMO BioControl D50 PN16, 316L, EHEDG1), 3A2) with seal FDA TIJ DRD DN50 65mm PN25, 316L TMJ APV Inline DN50 PN40, 316L, 3A with seal FDA UPJ Universaladapter 44mm 316L, incl. silicone molded seal, EHEDG1), 3A2) with seal FDA UNJ Universaladapter 44mm 316L, EPDM molded seal, EHEDG1) TDJ Tri-Clamp ISO2852 DN40-51 (2"), 316L, DIN32676 DN50, EHEDG1), 3A with seal FDA (CRN) TFJ Tri-Clamp ISO2852 DN76.1 (3"), 316L, EHEDG1), 3A with seal FDA (CRN) YYY Special version

1) 2)

Für die hygienegerechte Auslegung entsprechend EHEDG, ist die Verwendung geeigneter Fittings und Dichtungen zu beachten. Für die hygienegerechte Auslegung entsprechend 3A, ist die Verwendung geeigneter Fittings und Dichtungen zu beachten. Seal:
A B G F H J K L M N P S Y FKM Viton FKM Viton, FDA, 3A Class I, USP Class VI HNBR, FDA, 3A Class I, KTW, AFNOR, BAM NBR NBR, Low temperature EPDM, FDA EPDM, FDA, 3A Class II, USP Class VI, DVGW, KTW, W270, WRAS, ACS, NSF61 FFKM Kalrez 6375 FFKM Kalrez 7075 FFKM Kalrez 6221, FDA, USP Class VI Fluoroprene XP40, FDA, USP Class VI, 3A Class I VMQ Silicone, FDA Special version

190

82

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMC51 (continued)

Additional ordering information (optional)
500 Additional Operating language:
AA AB AC AD AE AF AK AL English German French Spanish Italian Dutch Chinese simplified Japanese

550

Calibration:
F1 F2 Factory calibration certificate, 5-point DKD/DAkkS calibration certificate 10-point

570

Service:
HA HB HC IA IB I9 Oil and grease removed 1) Cleaned for oxygen service 1) Cleaned from PWIS (PIWS = paint wetting impairment substances) 1) Configured min alarm current Configured HART Burst Mode PV Special version 1) Only device, not accessory or enclosed accessory

580

Test, certificate:
JA JB KB KD KE K9 EN10204-3.1 process connection material, inspection certificate NACE MR0175 process connection EN10204-3.1 material process conn. +Ra, Ra= surface roughness, dimensional check, inspection certificate EN10204-3.1 helium leak test, inspection certificate EN10204-3.1 pressure test, inspection certificate Special version,

590 600

Other approvals:
LW CoC-ASME BPE (CoC = Certificate of Compliance)

Separate housing:
MA MB MC MH Cable PE, 2m/80in + housing mounting bracket, wall/pipe, 304 Cable PE, 5m/200in + housing mounting bracket, wall/pipe, 304 Cable PE, 10m/400in + housing mounting bracket, wall/pipe, 304 Cable FEP, 5m/200in IP69K + housing mounting bracket, wall/pipe, 304

610 620

Accessory mounted:
NA Overvoltage protection

Accessory enclosed
PA P2 Mounting bracket, wall/pipe, 304 Shutoff valve (PZAV), see additional spec -R1A1 PZAV-R1A1 Shutoff valve, G1/2, C22.8 -R1A2 PZAV-R1A2 Shutoff valve, G1/2, 316Ti -R1D1 PZAV-R1D1 Shutoff valve, NPT1/2, C22.8 -R1D2 PZAV-R1D2 Shutoff valve, NPT1/2, 316Ti -B1A2 PZAV-B1A2 Shutoff valve, G1/2, 316Ti, 3.1 -B1D2 PZAV-B1D2 Shutoff valve, NPT1/2, 316Ti, 3.1 Siphon (PZW), see additional spec -RA21 PZW-RA21 Siphon G1/2 vertical, C22.8 (O-shape) -RA22 PZW-RA22 Siphon G1/2 vertical, 316Ti (O-shape) -RC11 PZW-RC11 Siphon G1/2 x weld. horiz. C22.8 (U-shape) -RD11 PZW-RD11 Siphon NPT1/2 x weld. horiz. C22.8 (U-shape) -BB22 PZW-BB22 Siphon NPT1/2 vertical, 316Ti, 3.1 (O-shape) -BA22 PZW-BA22 Siphon NPT1/2x weld.vert.316Ti 3.1 (O-shape) Welding neck G1-1/2, 316L Welding neck G1-1/2, 316L, 3.1, EN10204-3.1 material, inspection certificate Weld-in tool adapter G1-1/2, brass Weld-in flange DRD DN50 65mm, 316L Weld-in fl. DRD DN50 65mm, 316L 3.1 EN10204-3.1 material, inspection certificate Weld-in tool flange DRD DN50 65mm, Brass Weld-in adapter Uni D65, 316L Weld-in adapter Uni D65, 316L, 3.1 EN10204-3.1 material, inspection certificate Weld-in tool adapter Uni D65/D85, Brass Weld-in adapter Uni D85, 316L Weld-in adapter Uni D85, 316L, 3.1 EN10204-3.1 material, inspection certificate

P4

QJ QK QL QP QR QS QT QU Q1 Q2 Q3

Endress+Hauser

83

Cerabar M PMC51, PMP51, PMP55

620

Accessory enclosed
RA RB RC RD RE RF RH R1 R2 R3 R4 R5 R6 R7 RL RM RN R9 Adapter Uni > DIN11851 DN40, 316L, slotted-nut Adapter Uni > DIN11851 DN50, 316L, slotted-nut Adapter Uni > DRD DN50 65mm, 316L Adapter Uni > Clamp 2", 316L Adapter Uni > Clamp 3", 316L Adapter Uni > Varivent N, 316L Adapter Uni > Cherry Burell 2", 316L Adapter Uni > DIN11851 DN40, 316L, 3.1, slotted-nut, EN10204-3.1 material, inspection certificate Adapter Uni > DIN11851 DN50, 316L, 3.1, slotted-nut, EN10204-3.1 material, inspection certificate Adapter Uni > DRD DN50 65mm, 316L, 3.1 EN10204-3.1 material, inspection certificate Adapter Uni > Clamp 2", 316L, 3.1 EN10204-3.1 material, inspection certificate Adapter Uni > Clamp 3", 316L, 3.1 EN10204-3.1 material, inspection certificate Adapter Uni > Varivent, 316L, 3.1 EN10204-3.1 material, inspection certificate Adapter Uni > Cherry Burell, 316L, 3.1 EN10204-3.1 material, inspection certificate Plug-in jack M12 Plug-in jack M12, 90deg Plug-in jack M12, 90deg+5m cable Special version, TSP-no. to be spec.

850 895

Firmware version:
78 01.00.zz, HART, DevRev01

Identification:
Z1 Z2 Measuring point (TAG), see additional spec. Bus address, see additional spec.

84

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP51

This overview does not mark options which are mutually exclusive.
10 Approval:
AA BA BB BC BD BE BG B1 B2 8A For non-hazardous areas ATEX II 1/2G Ex ia IIC T6 ATEX II 1/2D Ex t IIIC ATEX II 2G Ex d IIC T6 ATEX II 3G Ex nA IIC T6 ATEX II 2G Ex ia IIC T6 ATEX II 3G Ex ic IIC T6 ATEX II 1/2G Ex ia IIC T6 + ATEX II 1/2D Ex iaD ATEX II 1/2G Ex ia IIC T6 + ATEX II 2G Ex d IIC T6 ATEX II Ex ia/Ex d + FM/CSA IS + XP ATEX II 1/2G Ex ia IIC T6+ ATEX II 2G Ex d IIC T6+ FM/CSA IS + XP Cl.I, II Div.1 Gr. A-G/B-G, zone 1,2 FM/CSA IS + XP Cl.I, II Div.1 Gr.A-D/B-G FM IS/FM XP Cl.I, II Div.1 Gr.A-G+ CSA IS/XP Cl.I, II Div.1 Gr.A-G, zone 1,2 IEC Ex ia IIC T6 Ga/Gb IEC Ex d IIC T6 Gb IEC Ex t IIIC Da/Db IEC Ex ic IIC T6 Gc IEC Ex ia IIC T6 Ga/Gb+Ex ia IIIC Da/Db NEPSI Ex ia IIC T6 NEPSI Ex d IIC T6 CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, CSA C/US IS Cl.I Div.2 Gr.2 Gr.A-D, Ex ia, zone 0,1,2,20,21,22 CSA C/US XP Cl.I, II Div.1 Gr.B-G, Ex d (Conduit seal not required), zone 1,2 CSA C/US Cl.II, III Div.1 Gr.E-G, US: Zone 21,22 CSA General Purpose CSA C/US IS/XP Cl.I, II Div.1 Gr.A-G/B-G, Zone 1,2 FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia FM NI Cl.I Div.2 Gr.A-D FM IS: Zone 0,1,2,20,21,22/FM NI: Zone 2 FM XP Cl.I, II Div.1 Gr.A-D, AEx d (Factory sealed) zone 1,2 FM DIP Cl.II, III Div.1 Gr.A-D Zone 21,22 FM NI Cl.I Div.2 Gr.A-D, Zone 2 FM IS/XP Cl.I, II Div.1 Gr.A-G, Zone 1,2 Special version

8B

IA IB ID IE I1 NA NB CA CB CC CD C1 FA

FB FC FD F1 99

20

Output:
1 2 3 4 9 4-20mA Analog 4-20mA HART PROFIBUS PA FOUNDATION Fieldbus Special version

30

Display, operation:
1 2 9 LCD, keys on display/electronics Without LCD, keys on electronics Special version

40

Housing:
I J Q R S Y F31 aluminum F31 aluminum, glass window F15 Stainless Steel Hygiene F15 Stainless Steel Hygiene, glass window F15 Stainless Steel Hygiene, plastic window Special version

50

Electrical connection:
A B C D I M P S V Y Gland M20, IP66/68 NEMA4X/6P Thread M20, IP66/68 NEMA4X/6P Thread G1/2, IP66/68 NEMA4X/6P Thread NPT1/2, IP66/68 NEMA4X/6P Connector M12, IP66/67, NEMA4X/6P Connector 7/8", IP66/68, NEMA4X/6P Connector Han7D, 90deg, IP65 PE Cable 5m, IP66/68 NEMA4X/6P + pressure compensation via cable Valve connector ISO4400 M16, IP64 Special version

Endress+Hauser

85

Cerabar M PMC51, PMP51, PMP55

PMP51 (continued)

70

Sensor range:
1F 400mbar/40kPa/6psi relative, 4mH2O/13ftH2O/160inH2O Overload: 6bar/600kPa/90psi 1bar/100kPa/15psi relative, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi relative, 20mH2O/67ftH2O/800inH2O Overload: 20bar/2MPa/300psi 4bar/400kPa/60psi relative, 40mH2O/133ftH2O/1600inH2O Overload: 28bar/2.8MPa/420psi 10bar/1MPa/150psi relative, 100mH2O/333ftH2O/4000inH2O Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi relative, 400mH2O/1334ftH2O/16000inH2O Overload: 160bar/16MPa/2400psi 100bar/10MPa/1500psi relative, 1000mH2O/3330ftH2O/40000inH2O Overload: 400bar/40MPa/6000psi 400bar/40MPa/6000psi relative, 4000mH2O/13340ftH2O/160000inH2O Overload: 600bar/60MPa/9000psi 400mbar/40kPa/6psi abs, 4mH2O/13ftH2O/160inH2O Overload: 6bar/600kPa/90psi 1bar/100kPa/15psi abs, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi abs, 20mH2O/67ftH2O/800inH2O Overload: 10bar/1MPa/150psi 4bar/400kPa/60psi abs, 40mH2O/133ftH2O/1600inH2O abs Overload: 28bar/2.8MPa/420psi 10bar/1MPa/150psi abs, 100mH2O/333ftH2O/4000inH2O abs Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi abs, 400mH2O/1334ftH2O/16000inH2O abs Overload: 160bar/16MPa/2400psi 100bar/10MPa/1500psi abs, 1000mH2O/3330ftH2O/40000inH2O abs Overload: 400bar/40MPa/6000psi 400bar/40MPa/6000psi abs, 4000mH2O/13340ftH2O/160000inH2O abs Overload: 600bar/60MPa/9000psi Special version

1H

1K

1M

1P

1S

1U

1W

2F

2H

2K

2M

2P

2S

2U

2W

99

80

Reference accuracy:
D G Y Platinum Standard Special version

90

Calibration; Unit:
A B C D E F J K Y Sensor range; % Sensor range; mbar/bar Sensor range; kPa/MPa Sensor range; mm/mH2O Sensor range; inH2O/ftH2O Sensor range; psi Customized pressure; see additional spec. Customized level; see additional spec. Special version

86

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP51 (continued)

110

Process connection:
ANSI flanges AEJ 1-1/2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AFJ 2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AGJ 3" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AHJ 4" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) ANJ 1" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) AQJ 1-1/2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ARJ 2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ASJ 3" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ATJ 4" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) EN flanges CNJ DN25 PN10-40 B1, 316L, flange EN1092-1 CPJ DN32 PN10-40 B1, 316L, flange EN1092-1 CQJ DN40 PN10-40 B1, 316L, flange EN1092-1 CXJ DN50 PN25/40 B1, 316L flange EN1092-1 CZJ DN80 PN25/40 B1, 316L, flange EN1092-1 Threaded connection GCC Thread ISO228 G1/2, AlloyC GCJ Thread ISO228 G1/2, 316L GLC Thread ISO228 G1/2 G1/4 female, AlloyC GLJ Thread ISO228 G1/2 G1/4 female, 316L GMC Thread ISO228 G1/2 hole 11.4mm, AlloyC GMJ Thread ISO228 G1/2 hole 11.4mm, 316L GRC Thread ISO228 G1/2, AlloyC, flush-mounted GRJ Thread ISO228 G1/2, 316L, flush-mounted GTJ Thread ISO228 G1, 316L, flush-mounted GVJ Thread ISO228 G1-1/2, 316L, flush-mounted GWJ Thread ISO228 G2, 316L, flush-mounted G0J Thread ISO228 G1/2 seal O-ring, fm= flush-mounted, 316L, adapter 52002643 G1J Thread DIN13 M20x1.5, 316L Threaded connection as per ANSI RKC Thread ANSI MNPT1/2 hole 11.4mm, AlloyC (CRN) RKJ Thread ANSI MNPT1/2 hole 11.4mm, 316L (CRN) RLC Thread ANSI MNPT1/2 FNPT1/4, AlloyC (CRN) RLJ Thread ANSI MNPT1/2 FNPT1/4, 316L (CRN) R1C Thread ANSI FNPT 1/2, Alloy C (CRN) R1J Thread ANSI FNPT 1/2, 316L (CRN) U5J Thread ANSI MNPT1, 316L, flush-mounted (CRN) U7J Thread ANSI MNPT1-1/2, 316L, flush-mounted (CRN) U8J Thread ANSI MNPT2, 316L, flush-mounted (CRN) XSJ Prepared for diaphragm seal mount, 316L (CRN) YYY Special version

170

Material of the process isolating diaphragm:
A B M Y 316L AlloyC Rhodium>gold>316L Special version

180

Fill fluid:
1 2 3 9 Silicone oil Inert oil Synthetic oil, FDA Special version

Additional ordering information (optional)
500 Additional Operating language:
AA AB AC AD AE AF AK AL English German French Spanish Italian Dutch Chinese simplified Japanese

Endress+Hauser

87

Cerabar M PMC51, PMP51, PMP55

PMP51 (continued)

550

Calibration:
F1 F2 Factory calibration certificate, 5-point DKD/DAkkS calibration certificate 10-point

570

Service:
HA HB HC IA IB I9 Oil and grease removed 1) Cleaned for oxygen service 1) Cleaned from PWIS (PIWS = paint wetting impairment substances) 1) Configured min alarm current Configured HART Burst Mode PV Special version 1) Only device, not accessory or enclosed accessory

580

Test, certificate:
JA JB JF KB KD KE KG K9 EN10204-3.1 wetted material, inspection certificate NACE MR0175 wetted EN10204-3.1 AD2000 material wetted parts, excepting process membrane inspection certificate EN10204-3.1 wetted material + Ra, Ra= surface roughness, dimensional check, inspection certificate EN10204-3.1 helium leak test, inspection certificate EN10204-3.1 pressure test, inspection certificate EN10204-3.1 PMI test* (PMI = positive material identification), inspection certificate * Meter body and process isolating diaphragm not included. Special version

590

Other approvals:
LW LR CoC-ASME BPE (CoC = Certificate of Compliance) NSF potable water approval

600

Separate housing:
MA MB MC MH Cable PE, 2m/80in + housing mounting bracket, wall/pipe, 304 Cable PE, 5m/200in + housing mounting bracket, wall/pipe, 304 Cable PE, 10m/400in + housing mounting bracket, wall/pipe, 304 Cable FEP, 5m/200in IP69K + housing mounting bracket, wall/pipe, 304

610 620

Accessory mounted:
NA Overvoltage protection

Accessory enclosed
PA P2 Mounting bracket, wall/pipe, 304 Shutoff valve (PZAV), see additional spec -R1A1 PZAV-R1A1 Shutoff valve, G1/2, C22.8 (O-shape) -R1A2 PZAV-R1A2 Shutoff valve, G1/2, 316Ti (O-shape) -R1D1 PZAV-R1D1 Shutoff valve, NPT1/2, C22.8 (U-shape) -R1D2 PZAV-R1D2 Shutoff valve, NPT1/2, 316Ti (U-shape) -B1A2 PZAV-B1A2 Shutoff valve, G1/2, 316Ti, 3.1 (O-shape) -B1D2 PZAV-B1D2 Shutoff valve, NPT1/2, 316Ti, 3.1 (O-shape) Siphon (PZW), see additional spec -RA21 PZW-RA21 Siphon G1/2 vertical, C22.8 -RA22 PZW-RA22 Siphon G1/2 vertical, 316Ti -RC11 PZW-RC11 Siphon G1/2 x weld. horiz. C22.8 -RD11 PZW-RD11 Siphon NPT1/2 x weld. horiz. C22.8 -BB22 PZW-BB22 Siphon NPT1/2 vertical, 316Ti, 3.1 -BA22 PZW-BA22 Siphon NPT1/2x weld.vert.316Ti 3.1 Welding neck G1/2, 316L, Welding neck G1/2, 316L, 3.1, EN10204-3.1 material, inspection certificate Weld-in tool adapter G1/2, brass Weld-in tool adapter G1, brass, metal sealing taper Welding neck G1-1/2, 316L Welding neck G1-1/2, 316L, 3.1, EN10204-3.1 material, inspection certificate Weld-in tool adapter G1-1/2, brass Plug-in jack M12 Plug-in jack M12, 90deg Plug-in jack M12, 90deg+5m cable

P4

QA QB QC QG QJ QK QL RL RM RN

850 895

Firmware version:
78 01.00.zz, HART, DevRev01

Identification:
Z1 Z2 Measuring point (TAG), see additional spec. Bus address, see additional spec.

88

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP55

This overview does not mark options which are mutually exclusive.
10 Approval:
AA BA BB BC BD BE BG B1 B2 8A For non-hazardous areas ATEX II 1/2G Ex ia IIC T6 ATEX II 1/2D Ex t IIIC ATEX II 2G Ex d IIC T6 ATEX II 3G Ex nA IIC T6 ATEX II 2G Ex ia IIC T6 ATEX II 3G Ex ic IIC T6 ATEX II 1/2G Ex ia IIC T6 + ATEX II 1/2D Ex iaD ATEX II 1/2G Ex ia IIC T6 + ATEX II 2G Ex d IIC T6 ATEX II Ex ia/Ex d + FM/CSA IS + XP ATEX II 1/2G Ex ia IIC T6+ ATEX II 2G Ex d IIC T6+ FM/CSA IS + XP Cl.I, II Div.1 Gr. A-G/B-G, zone 1,2 FM/CSA IS + XP Cl.I, II Div.1 Gr.A-D/B-G FM IS/FM XP Cl.I, II Div.1 Gr.A-G+ CSA IS/XP Cl.I, II Div.1 Gr.A-G, Zone 1,2 IEC Ex ia IIC T6 Ga/Gb IEC Ex d IIC T6 Gb IEC Ex t IIIC Da/Db IEC Ex ic IIC T6 Gc IEC Ex ia IIC T6 Ga/Gb+Ex ia IIIC Da/Db NEPSI Ex ia IIC T6 NEPSI Ex d IIC T6 CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, CSA C/US IS Cl.I Div.2 Gr.2 Gr.A-D, Ex ia, zone 0,1,2,20,21,22 CSA C/US CP Cl.I, II Div.1 Gr.B-G, Ex d (factory sealed) zone 1,2 CSA C/US Cl.II, III Div.1 Gr.E-G, Zone 21,22 CSA General Purpose CSA C/US IS/XP CL.I, II Div.1 Gr.A-G/B-G, Zone 1,2 FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia FM NI Cl.I Div.2 Gr.A-D FM IS: Zone 0,1,2,20,21,22/FM NI: Zone 2 FM XP Cl.I, II Div.1 Gr.A-G, AEx d (factory sealed) zone 1,2 FM DIP Cl.II, III Div.1 Gr.A-G, zone 21,22 FM NI Cl.I Div.2 Gr.A-D, Zone 2 FM IS/XP Cl.I, II Div.1 Gr.A-G, Zone 1,2 Special version

8B

IA IB ID IE I1 NA NB CA CB CC CD C1 FA

FB FC FD F1 99

20

Output:
1 2 3 4 9 4-20mA Analog 4-20mA HART PROFIBUS PA FOUNDATION Fieldbus Special version

30

Display, operation:
1 2 9 LCD, keys on display/electronics Without LCD, keys on electronics Special version

40

Housing:
I J Q R S Y F31 aluminum F31 aluminum, glass window F15 Stainless Steel Hygiene F15 Stainless Steel Hygiene, glass window F15 Stainless Steel Hygiene, plastic window Special version

50

Electrical connection:
A B C D I M P S V Y Gland M20, IP66/68 NEMA4X/6P Thread M20, IP66/68 NEMA4X/6P Thread G1/2, IP66/68 NEMA4X/6P Thread NPT1/2, IP66/68 NEMA4X/6P Connector M12, IP66/67, NEMA4X/6P Connector 7/8", IP66/68, NEMA4X/6P Connector Han7D, 90deg, IP65 PE Cable 5m, IP66/68 NEMA4X/6P + pressure compensation via cable Valve connector ISO4400 M16, IP64 Special version

Endress+Hauser

89

Cerabar M PMC51, PMP51, PMP55

PMP55 (continued)

70

Sensor range:
1F 400mbar/40kPa/6psi relative, 4mH2O/13ftH2O/160inH2O Overload: 6bar/600kPa/90psi 1bar/100kPa/15psi relative, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi relative, 20mH2O/67ftH2O/800inH2O Overload: 20bar/2MPa/300psi 4bar/400kPa/60psi relative, 40mH2O/133ftH2O/1600inH2O Overload: 28bar/2.8MPa/420psi 10bar/1MPa/150psi relative, 100mH2O/333ftH2O/4000inH2O Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi relative, 400mH2O/1334ftH2O/16000inH2O Overload: 160bar/16MPa/2400psi 100bar/10MPa/1500psi relative, 1000mH2O/3330ftH2O/40000inH2O Overload: 400bar/40MPa/6000psi 400bar/40MPa/6000psi relative, 4000mH2O/13340ftH2O/160000inH2O Overload: 600bar/60MPa/9000psi 400mbar/40kPa/6psi abs, 4mH2O/13ftH2O/160inH2O Overload: 6bar/600kPa/90psi 1bar/100kPa/15psi abs, 10mH2O/33ftH2O/400inH2O Overload: 10bar/1MPa/150psi 2bar/200kPa/30psi abs, 20mH2O/67ftH2O/800inH2O abs Overload: 20bar/2MPa/300psi 4bar/400kPa/60psi abs, 40mH2O/133ftH2O/1600inH2O abs Overload: 28bar/2.8MPa/420psi 10bar/1MPa/150psi abs, 100mH2O/333ftH2O/4000inH2O abs Overload: 40bar/4MPa/600psi 40bar/4MPa/600psi abs, 400mH2O/1334ftH2O/16000inH2O abs Overload: 160bar/16MPa/2400psi 100bar/10MPa/1500psi abs, 1000mH2O/3330ftH2O/40000inH2O abs Overload: 400bar/40MPa/6000psi 400bar/40MPa/6000psi abs, 4000mH2O/13340ftH2O/160000inH2O abs Overload: 600bar/60MPa/9000psi Special version

1H

1K

1M

1P

1S

1U

1W

2F

2H

2K

2M

2P

2S

2U

2W

99

80

Reference accuracy:
D G Y Platinum Standard Special version

90

Calibration; Unit:
A B C D E F J K Y Sensor range; % Sensor range; mbar/bar Sensor range; kPa/MPa Sensor range; mm/mH2O Sensor range; inH2O/ftH2O Sensor range; psi Customized pressure; see additional spec. Customized level; see additional spec. Special version

90

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP55 (continued)

110

Process connection:
ANSI flanges ACJ 1" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AEJ 1-1/2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AFJ 2" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AGJ 3" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) AHJ 4" 150lbs RF, 316/316L, flange ANSI B16.5 (CRN) ANJ 1" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) AQJ 1-1/2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ARJ 2" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ASJ 3" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) ATJ 4" 300lbs RF, 316/316L, flange ANSI B16.5 (CRN) A0J 1" 400/600lbs RF, 316/316L, flange ANSI B16.5 (CRN) A1J 2" 400/600lbs RF, 316/316L, flange ANSI B16.5 (CRN) A2J 1" 900/1500lbs RF, 316/316L, flange ANSI B16.5 (CRN) A3J 2" 900/1500lbs RF, 316/316L, flange ANSI B16.5 (CRN) A4J 1" 2500lbs RF, 316/316L, flange ANSI B16.5 (CRN) A5J 2" 2500lbs RF, 316/316L, flange ANSI B16.5 (CRN) FMJ 2" 150lbs RF, 316/316L, 2/4/6/8" extended diaphragm seal, flange ANSI B16.5, see additional spec. (CRN) FNJ 3" 150lbs RF, 316/316L, 2/4/6/8" extended diaphragm seal, flange ANSI B16.5, see additional spec. (CRN) FOJ 4" 150lbs RF, 316/316L, 2/4/6/8" extended diaphragm seal, flange ANSI B16.5, see additional spec. (CRN) FWJ 3" 300lbs RF, 316/316L, 2/4/6/8" extended diaphragm seal, flange ANSI B16.5, see additional spec. (CRN) FXJ 4" 300lbs RF, 316/316L, 2/4/6/8" extended diaphragm seal, flange ANSI B16.5, see additional spec. (CRN) EN flanges CNJ DN25 PN10-40 B1, 316L, flange EN1092-1 CPJ DN32 PN10-40 B1, 316L, flange EN1092-1 CQJ DN40 PN10-40 B1, 316L, flange EN1092-1 CXJ DN50 PN10-40 B1, 316L, flange EN1092-1 CZJ DN80 PN10-40 B1, 316L, flange EN1092-1 JIS flanges KCJ 10K 25 RF, 316L, flange JIS B2220 KEJ 10K 40 RF, 316L, flange JIS B2220 KFJ 10K 50 RF, 316L, flange JIS B2220 KGJ 10K 80 RF, 316L, flange JIS B2220 KHJ 10K 100 RF, 316L, flange JIS B2220 DIN flanges QIJ DN25 PN63-160 E, 316L, flange DIN2501 QJJ DN25 PN250 E, 316L, flange DIN2501 QMJ DN50 PN250 E, 316L, flange DIN2501 QOJ DN50 PN100-160 E, 316L, flange DIN2501 QSJ DN25 PN400 E, 316L, flange DIN2501 QVJ DN50 PN400 E, 316L, flange DIN2501 FDJ DN50 PN10-40 B1, 316L, 50/100/200mm extended diaphragm seal, flange EN1092-1, see additional spec. FEJ DN80 PN10-40 B1, 316L, 50/100/200mm extended diaphragm seal, flange EN1092-1, see additional spec. PDJ DN50 PN63 B2, 316L, flange EN1092-1 PPJ DN80 PN100 B2, 316L, flange EN1092-1 PQJ DN100 PN100 B2, 316L, flange EN1092-1 Threaded connection GTC Thread ISO228 G1, AlloyC, flush-mounted GTJ Thread ISO228 G1, 316L, flush-mounted GVC Thread ISO228 G1-1/2, AlloyC, fm= flush-mounted GVJ Thread ISO228 G1-1/2, 316L, flush-mounted GWC Thread ISO228 G2, AlloyC, flush-mounted GWJ Thread ISO228 G2, 316L, flush-mounted UBJ Thread ISO228 G1/2, PN160.316L, separator, EN837, welded UCJ Thread ANSI MNPT1/2,PN160.316L,separator, welded (CRN) UDJ Thread ISO228 G1/2, 316L, separator, EN837, threaded UEJ Thread ANSI MNPT1/2, 316L, separator, threaded UGJ Thread FNPT1/2, PN250, 316L, separator, threaded UHJ Thread FNPT1, PN250, 316L, separator, threaded U5C Thread ANSI MNPT1, AlloyC, flush-mounted (CRN) U5J Thread ANSI MNPT1, 316L, flush-mounted (CRN) U7C Thread ANSI MNPT1-1/2, AlloyC, fm=flush-mounted (CRN) U7J Thread ANSI MNPT1-1/2, 316L, flush-mounted (CRN) U8C Thread ANSI MNPT2, AlloyC, flush-mounted (CRN) U8J Thread ANSI MNPT2, 316L, flush-mounted (CRN)

Endress+Hauser

91

Cerabar M PMC51, PMP51, PMP55

PMP55 (continued)

110

Process connection:
Diaphragm seal cell structure UIJ Pancake (Cell) DN 50 PN 16-400, AISI 316L UJJ Pancake (Cell) DN 80 PN 16-400, AISI 316L UKJ Pancake (Cell) DN 100 PN 16-400, AISI 316L ULJ Pancake (Cell) 2" 150-2500 lbs, AISI 316L UMJ Pancake (Cell) 3" 150-2500 lbs, AISI 316L URJ Pancake (Cell) 4" 150-2500 lbs, AISI 316L Pipe diaphragm seal SIJ Tri-Clamp ISO2852 DN10 (3/4") RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal (CRN) SJJ Tri-Clamp ISO2852 DN16 (3/4") RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal (CRN) SBJ Tri-Clamp ISO2852 DN25 (1") RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal (CRN) SCJ Tri-Clamp ISO2852 DN38 (1-1/2") RDM, EHEDG, 3A, 316L, PED Cat.II, RDM = pipe diaphragm seal (CRN) 3.1 material + pressure test PED Cat.II SDJ Tri-Clamp ISO2852 DN51 (2") RDM, 316L, EHEDG, 3A, PED Cat.II, RDM = pipe diaphragm seal (CRN) 3.1 material + pressure test PED Cat.II SSJ DIN11851 DN25 PN40, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter STJ DIN11851 DN32 PN40, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter SUJ DIN11851 DN40 PN40, RDM, 316L, EHEDG, 3A, 3.1 material + pressure test PED Cat.II, RDM = pipe diaphragm seal, threaded adapter SZJ DIN11851 DN50 PN25, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter S4J NEUMO BioControl D50 PN16, 316L, EHEDG VAJ DIN11864-1 A DN25 PN40, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter VCJ DIN11864-1 A DN40 PN40, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter VDJ DIN11864-1 A DN50 PN25, RDM, 316L, EHEDG, 3A, RDM = pipe diaphragm seal, threaded adapter Hygienic process connections MIJ DIN11851 DN32 PN40 cap-nut, 316L, EHEDG, 3A MRJ DIN11851 DN50 PN25 cap-nut, 316L, EHEDG, 3A MSJ DIN11851 DN65 PN25 cap-nut, 316L, EHEDG, 3A MTJ DIN11851 DN80 PN25 cap-nut, 316L, EHEDG, 3A MZJ DIN11851 DN40 PN40 cap-nut, 316L, EHEDG, 3A NKJ DIN11851 DN50 PN25 threaded adapter, 316L, EHEDG, 3A NLJ DIN11851 DN65 PN25 threaded adapter, 316L, EHEDG, 3A NMJ DIN11851 DN80 PN25 threaded adapter, 316L, EHEDG, 3A NCJ DIN11864-1 A DN40 PN16 tube DIN11866-A, threaded connection, 316L, EHEDG, 3A NDJ DIN11864-1 A DN50 PN16 tube DIN11866-A, threaded connection, 316L, EHEDG, 3A NFJ DIN11864-2 A DN32 PN16 tube DIN11866-A, 316L, EHEDG, 3A NXJ DIN11864-2 A DN40 PN16 tube DIN11866-A, 316L, EHEDG, 3A NZJ DIN11864-2 A DN50 PN16 tube DIN11866-A, 316L, EHEDG, 3A S4J NEUMO BioControl D50 PN16, 316L, EHEDG TCJ Tri-Clamp ISO2852 DN25 (1"), 316L, DIN32676 DN25, EHEDG, 3A, ASME-BPE (CRN) TJJ Tri-Clamp ISO2852 DN38 (1-1/2"), 316L, DIN32676 DN40, EHEDG, 3A, ASME-BPE (CRN) TDJ Tri-Clamp ISO2852 DN51 (2"), 316L, DIN32676 DN50, EHEDG, 3A, ASME-BPE (CRN) TFJ Tri-Clamp ISO2852 DN76.1 (3"), 316L, EHEDG, 3A, ASME-BPE (CRN) TIJ DRD DN50 65mm PN25, 316L TQJ Varivent F pipe DN25-32 PN40, 316L, EHEDG, 3A TRJ Varivent N pipe DN40-162 PN40, 316L, EHEDG, 3A UPJ Universal adapter 44mm 316L, 3A, EHEDG, incl. silicone molded seal T0J APV-RJT 1" PN40, 316L T1J APV-RJT 1-1/2" PN40, 316L T2J APV-RJT 2" PN40, 316L T3J APV-ISS 1" PN40, 316L T4J APV-ISS 1-1/2" PN40, 316L T5J APV-ISS 2" PN40, 316L T6J SMS 1” PN25, 316L, EHEDG, 3A T7J SMS 1-1/2” PN25, 316L, EHEDG, 3A TXJ SMS 2" PN25, 316L, EHEDG, 3A YYY Special version

170

Material of the process isolating diaphragm:
A B C D M R S Y 316L AlloyC Monel Tantalum Rhodium>gold>316L 0.09mm PTFE>316L, not for vacuum 0.25mm PTFE>316L, not for vacuum Special version

92

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

PMP55 (continued)

180

Fill fluid:
1 2 4 5 6 9 Silicone oil Inert oil Vegetable oil, FDA High-temperature oil Low-temperature oil Special version

200

Diaphragm seal connection:
A B D E Y Direct Temperature isolator ..... m capillary ..... ft capillary Special version

Additional ordering information (optional)
500 Additional Operating language:
AA AB AC AD AE AF AK AL English German French Spanish Italian Dutch Chinese simplified Japanese

550

Calibration:
F1 F2 Factory calibration certificate, 5-point DKD/DAkkS calibration certificate 10-point

570

Service:
HA HB HC HG HK IA IB I9 Oil and grease removed 1) Cleaned for oxygen service 1) Cleaned from PWIS (PIWS = paint wetting impairment substances) 1) Diaphragm seal vacuum service Surface quality Ra<0.38um electropolished (wetted) Configured min alarm current Configured HART Burst Mode PV Special version 1) Only device, not accessory or enclosed accessory

580

Test, certificate:
JA JB JF KB KD KE KF KG K9 EN10204-3.1 wetted material, inspection certificate NACE MR0175 wetted EN10204-3.1 AD2000 material wetted parts, excepting process membrane inspection certificate EN10204-3.1 wetted material + Ra, (Ra= surface roughness), dimensional check, inspection certificate EN10204-3.1 helium leak test, inspection certificate EN10204-3.1 pressure test, inspection certificate EN10204-3.1 measurement Delta ferrite content, inspection certificate EN10204-3.1 PMI test* (PMI = positive material identification), inspection certificate * Meter body and process isolating diaphragm not included. Special version

590 600

Other approvals:
LW CoC-ASME BPE (CoC = Certificate of Compliance)

Separate housing:
MA MB MC MH Cable PE, 2m/80in + housing mounting bracket, wall/pipe, 304 Cable PE, 5m/200in + housing mounting bracket, wall/pipe, 304 Cable PE, 10m/400in + housing mounting bracket, wall/pipe, 304 Cable FEP, 5m/200in IP69K + housing mounting bracket, wall/pipe, 304

610

Accessory mounted:
NA Overvoltage protection

Endress+Hauser

93

Cerabar M PMC51, PMP51, PMP55

PMP55 (continued)

620

Accessory enclosed
PA P2 Mounting bracket, wall/pipe, 304 Shutoff valve (PZAV), see additional spec -R1A1 PZAV-R1A1 Shutoff valve, G1/2, C22.8 (O-shape) -R1A2 PZAV-R1A2 Shutoff valve, G1/2, 316Ti (O-shape) -R1D1 PZAV-R1D1 Shutoff valve, NPT1/2, C22.8 (U-shape) -R1D2 PZAV-R1D2 Shutoff valve, NPT1/2, 316Ti (U-shape) -B1A2 PZAV-B1A2 Shutoff valve, G1/2, 316Ti, 3.1 (O-shape) -B1D2 PZAV-B1D2 Shutoff valve, NPT1/2, 316Ti, 3.1 (O-shape) Siphon (PZW), see additional spec -RA21 PZW-RA21 Siphon G1/2 vertical, C22.8 -RA22 PZW-RA22 Siphon G1/2 vertical, 316Ti -RC11 PZW-RC11 Siphon G1/2 x weld. horiz. C22.8 -RD11 PZW-RD11 Siphon NPT1/2 x weld. horiz. C22.8 -BB22 PZW-BB22 Siphon NPT1/2 vertical, 316Ti, 3.1 -BA22 PZW-BA22 Siphon NPT1/2x weld.vert.316Ti 3.1 Welding neck G1/2, 316L, Welding neck G1/2, 316L, 3.1, EN10204-3.1 material, inspection certificate Weld-in tool adapter G1/2, brass Welding neck G1-1/2, 316L Welding neck G1-1/2, 316L, 3.1, EN10204-3.1 material, inspection certificate Weld-in tool adapter G1-1/2, brass Welding flange DRD DN50 65mm, 316L Welding fl. DRD DN50 65mm, 316L 3.1, EN10204-3.1 material, inspection certificate Weld-in tool flange DRD DN50 65mm, brass Plug-in jack M12 Plug-in jack M12, 90deg Plug-in jack M12, 90deg+5m cable

P4

QA QB QC QJ QK QL QP QR QS RL RM RN

850 895

Firmware version:
78 01.00.zz, HART, DevRev01

Identification:
Z1 Z2 Measuring point (TAG), see additional spec. Bus address, see additional spec.

94

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Documentation
Technical Information ? EMC test procedures TI00241F/00/EN ? Deltabar M: TI00434P/00/EN ? Deltapilot M: TI00437P/00/EN ? ? ? ? ? ? ? ? 4 to 20 mA Analog: BA00385P/00/EN 4 to 20 mA HART: BA00382P/00/EN PROFIBUS PA: BA00383P/00/EN FOUNDATION Fieldbus: BA00384P/00/EN 4 to 20 mA Analog: KA01036P/00/EN 4 to 20 mA HART: KA01030P/00/EN PROFIBUS PA: KA01031P/00/EN FOUNDATION Fieldbus: KA01032P/00/EN

Operating Instructions

Brief Operating Instructions

Safety Instructions
Authorities Version in the order code BA BB Approval Category Type Housing F31 Ex ia IIC Ex t IIC II 1/2 G II 1/2 D PMC51, PMP51, PMP55 PMP51, PMP55 X X F15 X X – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART – PROFIBUS PA – FOUNDATION Fieldbus – 4 to 20 mA HART – PROFIBUS PA – FOUNDATION Fieldbus – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART – 4...20 mA HART – XA00464P/00 – XA00466P/00 Electronics Documentation

BC

Ex d

II 2 G

PMP51, PMP55

X

---

– XA00467P/00

BD ATEX

Ex nA

II 3 G

PMC51, PMP51, PMP55

X

X

– XA00469P/00

BE BF BG B1 B2 8A

Ex ia IIC Ex ia IIC Ex ic IIC Ex ia Ex ia IIIC Ex ia IIC Ex d IIC Ex ia IIC

II 2 G II 1/2 D II 3 G II 1/2 G II 1/2 D II 2 G II 1/2 G II 2 G II 1/2 G

PMC51, PMP51, PMP55 PMC51 PMC51, PMP51, PMP55 PMC51, PMP51, PMP55 PMP51, PMP55 PMP51, PMP55

X X X X X X

X X X X X ---

– XA00464P/00 – XA00465P/00 – XA00489P/00 – XA00468P/00 – XA00468P/00 – XA00504P/00

Authorities

Version in the order code IA

Approval

EPL

Type

Housing F31 F15 X

Electronics

Documentation

Ex ia IIC

Ga/Gb

PMC51, PMP51, PMP55

X

– 4 to 20 mA HART – 4 to 20 mA HART – PROFIBUS PA – FOUNDATION Fieldbus – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART – 4 to 20 mA HART

– XA00470P/00

IB

Ex d IIC

Gb

PMP51, PMP55

X

---

– XA00471P/00

IECEx

ID IE IF I1

Ex t IIIC Ex ic Ex ia IIIC Ex ia IIC Ex ia IIIC

Da/Db Gc Da/Db Ga/Gb Da/Db

PMP51, PMP55 PMC51, PMP51, PMP55 PMC51 PMC51, PMP51, PMP55

X X X X

X X X X

– XA00472P/00 – XA00488P/00 – XA00487P/00 – XA00473P/00

Endress+Hauser

95

Cerabar M PMC51, PMP51, PMP55

Authorities Version in the order code NEPSI NEPSI NA NB

Approval

Housing F31 F15 X ---

Electronics

Documentation

Ex ia IIC Ex d IIC

X X

– 4 to 20 mA HART – 4 to 20 mA HART

– XA00533P/00 – XA00515P/00

Installation/Control Drawings
Authorit Version in ies the order code Approval Type Housing F31 FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia FM NI Cl.I Div.2 Gr.A-D FM IS: Zone 0,1,2,20,21,22/FM NI: Zone 2 FM XP Cl.I, II Div.1 Gr.A-D, AEx d (Factory sealed) Zone 1,2 F15 – 4...20 mA HART – PROFIBUS PA, FOUNDATION Fieldbus – 4...20 mA HART – PROFIBUS PA – FOUNDATION Fieldbus – 4 to 20 mA HART – 4 to 20 mA HART – 4...20 mA HART – PROFIBUS PA, FOUNDATION Fieldbus – 4 to 20 mA HART – 4 to 20 mA HART – 4...20 mA HART – PROFIBUS PA, FOUNDATION Fieldbus – 4 to 20 mA HART – XA00563P/00 – XA00564P/00 Electronics Documentation

FA

PMC51, PMP51, PMP55

X

X

FB FM

PMP51, PMP55 X ---

--

FC F1

FM DIP Cl.II, III Div.1 Gr.A-D Zone 21,22 FM IS/XP Cl.I, II Div.1 Gr.A-G, Zone 1,2 C/US IS Cl.I,II,III Div.1 Gr.A-G, C/US IS Cl.I Div.2 Gr.A-D, Ex ia CSA C/US CP Cl.I, II Div.1 Gr.B-G, Ex d (factory sealed) Zone 1,2 CSA C/US Cl.II, III Div.1 Gr.E-G, Zone 21,22 CSA C/US IS/XP CL.I, II Div.1 Gr.A-G/B-G, Zone 1,2

PMP51, PMP55 PMP51, PMP55

X X

X

– In preparation – XA00567P/00 – XA00556P/00 – XA00558P/00

CA

PMC51, PMP51, PMP55

X

X

CB CSA CC C1

PMP51, PMP55 PMP51, PMP55 PMP51, PMP55

X X

--X

– ZD00249P/00 – In preparation – XA00577P/00 – XA00561P/00

X

---

FM CSA

8B

FM/CSA IS + XP Cl.I, II Div.1 Gr.A-D/B-G FM IS/FM XP Cl.I, II Div.1 Gr.A-G+ CSA IS/XP Cl.I, II Div.1 Gr.A-G, Zone 1,2

PMP55 X --– In preparation

96

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Accessories
Shutoff valve
G1/2 1/2 NPT

105

100

? 63

1/2 NPT

79

G1/2

20

79
P01-xMx5xxxx-06-xx-xx-xx-001

Max. working pressure [bar (psi)]

Connection thread [d] G1/2

Material C22.8 (1.0460) 316Ti (1.4571)

Version in the order code 1) R1A1 R1A2, B1A2 R1D1 R1D2, B1D2

400 (5800) C22.8 (1.0460) NPT1/2 316Ti (1.4571) 1) See also → ? 79 ff, feature 620, "Accessory enclosed", version "P2".

Siphon
1 G1/2 SW27 1/2NPT 2 SW27

G1/2

1/2NPT

95

130

? 20

56

145

275

?

? 63

56

G1/2
P01-PMx5xxxx-06-xx-xx-xx-002

110

Nr Max. Betriebsdruck [bar (psi)] 1

Max. operating temperature °C (°F) in front of the siphon (process side)

Connection thread [d] Material 1.0345 G1/2

Version in the order code 1) RA21

2

? 104 (1508) ? 120 (1740) ? 160 (2320)

? 400 (752) ? 300 (572) ? 120 (248)

316Ti (1.4571) RA22, BA22 NPT1/2 G1/2 NPT1/2 316Ti (1.4571) BB22 1.0345 1.0345 RC11 RD11

1)

See also → ? 79 ff, feature 620, "Accessory enclosed", version "P4".

Endress+Hauser

97

Cerabar M PMC51, PMP51, PMP55

Welding necks and Weld-in tool flanges Mounting bracket for wall and pipe mounting M12 connector

See technical Information TI00426F/00.

→ ? 25 ff

→ ? 18 ff

98

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Configuration data sheet (HART, PROFIBUS PA, FOUNDATION Fieldbus electronics)
Level The following configuration data sheet has to be filled in and included with the order if the version "K - Customized level" has been selected in feature 90 "Calibration; Unit" in the product structure.

Pressure Engineering Unit mbar bar psi mmHg
2

Output Unit (Scaled unit) % m dm cm mm inch ft l hl m
3

mmH2O mH2O ftH2O inH2O Pa kPa MPa

gal Igal ft 3 in
3

kg t lb

kgf/cm

Empty pressure (a) Low pressure value (empty) [pres. eng. unit] Full pressure (b) High pressure value (full) [pres. eng. unit] Display Information 1st Value Display Measured Value (PV)

Empty calibration (a) Low level value (empty) [Scaled Unit] Full calibration (b) High level value (full) [Scaled Unit]
Example

2nd Value Display none (factory setting) Pressure Current [mA] Temperature Measured value (%)

300 mbar 3m

(b)

Damping Damping: ____ sec (Default 2 sec)

0 mbar 0m

(a)

P01-PMX5xxxx-16-xx-xx-en-000

Endress+Hauser

99

Cerabar M PMC51, PMP51, PMP55

Pressure

The following configuration data sheet has to be filled in and included with the order if the version "J - Customized pressure" has been selected in feature 90 "Calibration; Unit" in the product structure.

Pressure Engineerung Unit mbar bar psi mmH2O mH2O ftH2O inH2O mmHg
2

Pa kPa MPa

kgf/cm

Calibration Range / Output
Low range value (LRV):_____________________ [pressure engineering unit) Upper range value (URV):_____________________ [pressure engineering unit)

Display Information
1st Value Display Main Value 2nd Value display none (default) Pressure Current [mA] Temperature Measured value (%)
1)

Damping Damping: ____ sec (Default 2 sec)
1)

Depending on sensor and comunication variant
P01-xxxxxxxx-16-xx-xx-en-001

Note! Smallest span (factory calibration) → ? 8 ff.

100

Endress+Hauser

Cerabar M PMC51, PMP51, PMP55

Configuration data sheet (analog electronics)
Pressure The following configuration data sheet has to be filled in and included with the order if the version "J - Customized pressure" has been selected in feature 90 "Calibration; Unit" in the product structure.

Pressure Engineerung Unit mbar bar psi mmH2O mH2O ftH2O inH2O mmHg
2

Pa kPa MPa

kgf/cm

Calibration Range / Output
Low range value (LRV):_____________________ [pressure engineering unit) Upper range value (URV):_____________________ [pressure engineering unit)

Display Information 1st Value Display Main Value

?none

2nd Value display (default, not editable)

Damping Damping: 2 sec (default, not editable)

P01-xxxxxxxx-16-xx-xx-en-002

Note! Smallest span (factory calibration) → ? 8 ff.

Endress+Hauser

101

Cerabar M PMC51, PMP51, PMP55

Instruments International
Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel.+41 61 715 81 00 Fax+41 61 715 25 00 www.endress.com info@ii.endress.com

TI00436P/00/EN/15.11 No. 71134874 CCS/FM+SGML 6.0

71134874