The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.1

The Fukushima Daiichi Incident
1. 2. 3. 4. 5. Plant Design Accident Progression Radiological releases

Spent fuel pools Sources of Information

Matthias Braun PEPA4-G, AREVA–NP GmbH Matthias.Braun@AREVA.com
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.2

The Fukushima Daiichi Incident
1. Plant Design
Fukushima Daiichi (Plant I)
? Unit I - GE Mark I BWR (439 MW), Operating since 1971
? Unit II-IV - GE Mark I BWR (760 MW), Operating since 1974

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.3

The Fukushima Daiichi Incident
Building structure
? Concrete Building ? Steel-framed Service Floor

1. Plant Design
Containment
? Pear-shaped Dry-Well
en.wikipedia.org/wiki/Browns_Ferry_Nuclear_Power_Plant

? Torus-shaped Wet-Well

nucleartourist.com
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.4

The Fukushima Daiichi Incident
1. Plant Design
Service Floor

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.5

The Fukushima Daiichi Incident
1. Plant Design
Lifting the Containment closure head

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.6

The Fukushima Daiichi Incident
1. Plant Design
Reactor Service Floor (Steel Construction) Concrete Reactor Building (secondary Containment)

Spend Fuel Pool

Fresh Steam line
Main Feedwater

Reactor Core Reactor Pressure Vessel Containment (Dry well)

Containment (Wet Well) / Condensation Chamber
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.7

The Fukushima Daiichi Incident
2. Accident progression

11.3.2011 14:46 - Earthquake
? Magnitude 9 ? Power grid in northern Japan fails

? Reactors itself are mainly undamaged

SCRAM
? Power generation due to Fission of Uranium stops
? Heat generation due to radioactive Decay of Fission Products
? After Scram ? After 1 Day ? After 5 Days ~6% ~1% ~0.5%

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.8

The Fukushima Daiichi Incident
2. Accident progression
Containment Isolation
? Closing of all non-safety related Penetrations of the containment
? Cuts off Machine hall ? If containment isolation succeeds, a large early release of fission products is highly unlikely

Diesel generators start
? Emergency Core cooling systems are supplied

Plant is in a stable save state

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.9

The Fukushima Daiichi Incident
2. Accident progression
11.3. 15:41 Tsunami hits the plant
? Plant Design for Tsunami height of up to 6.5m ? Actual Tsunami height >7m ? Flooding of
? Diesel Generators and/or ? Essential service water building cooling the generators

Station Blackout
? Common cause failure of the power supply ? Only Batteries are still available ? Failure of all but one Emergency core cooling systems

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.10

The Fukushima Daiichi Incident
2. Accident progression
Reactor Core Isolation Pump still available
? Steam from the Reactor drives a Turbine ? Steam gets condensed in the Wet-Well ? Turbine drives a Pump ? Water from the Wet-Well gets pumped in Reactor ? Necessary:
? Battery power ? Temperature in the wet-well must be below 100° C

As there is no heat removal from the building, the Core isolation pump cant work infinitely

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.11

The Fukushima Daiichi Incident
2. Accident progression
Reactor Isolation pump stops
? 11.3. 16:36 in Unit 1 (Batteries empty) ? 14.3. 13:25 in Unit 2 (Pump failure)

? 13.3. 2:44 in Unit 3 (Batteries empty)

Decay Heat produces still steam in Reactor pressure Vessel
? Pressure rising

Opening the steam relieve valves
? Discharge Steam into the Wet-Well

Descending of the Liquid Level in the Reactor pressure vessel
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.12

The Fukushima Daiichi Incident
2. Accident progression
Reactor Isolation pump stops
? 11.3. 16:36 in Unit 1 (Batteries empty) ? 14.3. 13:25 in Unit 2 (Pump failure)

? 13.3. 2:44 in Unit 3 (Batteries empty)

Decay Heat produces still steam in Reactor pressure Vessel
? Pressure rising

Opening the steam relieve valves
? Discharge Steam into the Wet-Well

Descending of the Liquid Level in the Reactor pressure vessel
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.13

The Fukushima Daiichi Incident
2. Accident progression
Reactor Isolation pump stops
? 11.3. 16:36 in Unit 1 (Batteries empty) ? 14.3. 13:25 in Unit 2 (Pump failure)

? 13.3. 2:44 in Unit 3 (Batteries empty)

Decay Heat produces still steam in Reactor pressure Vessel
? Pressure rising

Opening the steam relieve valves
? Discharge Steam into the Wet-Well

Descending of the Liquid Level in the Reactor pressure vessel
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.14

The Fukushima Daiichi Incident
2. Accident progression
Reactor Isolation pump stops
? 11.3. 16:36 in Unit 1 (Batteries empty) ? 14.3. 13:25 in Unit 2 (Pump failure)

? 13.3. 2:44 in Unit 3 (Batteries empty)

Decay Heat produces still steam in Reactor pressure Vessel
? Pressure rising

Opening the steam relieve valves
? Discharge Steam into the Wet-Well

Descending of the Liquid Level in the Reactor pressure vessel
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.15

The Fukushima Daiichi Incident
2. Accident progression
Reactor Isolation pump stops
? 11.3. 16:36 in Unit 1 (Batteries empty) ? 14.3. 13:25 in Unit 2 (Pump failure)

? 13.3. 2:44 in Unit 3 (Batteries empty)

Decay Heat produces still steam in Reactor pressure Vessel
? Pressure rising

Opening the steam relieve valves
? Discharge Steam into the Wet-Well

Descending of the Liquid Level in the Reactor pressure vessel
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.16

The Fukushima Daiichi Incident
2. Accident progression
Measured, and here referenced Liquid level is the collapsed level. The actual liquid level lies higher due to the steam bubbles in the liquid ~50% of the core exposed
? Cladding temperatures rise, but still no significant core damage

~2/3 of the core exposed
? Cladding temperature exceeds ~900° C ? Balooning / Breaking of the cladding ? Release of fission products form the fuel rod gaps
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.17

The Fukushima Daiichi Incident
2. Accident progression

~3/4 of the core exposed
? Cladding exceeds ~1200° C ? Zirconium in the cladding starts to burn under Steam atmosphere ? Zr + 2H20 ->ZrO2 + 2H2 ? Exothermal reaction further heats the core ? Generation of hydrogen
? Unit 1: 300-600kg ? Unit 2/3: 300-1000kg

? Hydrogen gets pushed via the wet-well, the wet-well vacuum breakers into the dry-well

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.18

The Fukushima Daiichi Incident
2. Accident progression
at ~1800° C [Unit 1,2,3]
? Melting of the Cladding ? Melting of the steel structures

at ~2500° C

[Block 1,2]

? Breaking of the fuel rods

? debris bed inside the core

at ~2700° C

[Block 1]

? Melting of Uranium-Zirconium eutectics

Restoration of the water supply stops accident in all 3 Units
? Unit 1: 12.3. 20:20 (27h w.o. water)

? Unit 2: 14.3. 20:33 (7h w.o. water)
? Unit 3: 13.3. 9:38 (7h w.o. water)

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.19

The Fukushima Daiichi Incident
2. Accident progression
Release of fission products during melt down
? Xenon, Cesium, Iodine,… ? Uranium/Plutonium remain in core ? Fission products condensate to airborne Aerosols

Discharge through valves into water of the condensation chamber
? Pool scrubbing binds a fraction of Aerosols in the water

Xenon and remaining aerosols enter the Dry-Well
? Deposition of aerosols on surfaces further decontaminates air

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.20

The Fukushima Daiichi Incident
2. Accident progression
Containment
? Last barrier between Fission Products and Environment ? Wall thickness ~3cm ? Design Pressure 4-5bar

Actual pressure up to 8 bars
? Normal inert gas filling (Nitrogen) ? Hydrogen from core oxidation ? Boiling condensation chamber (like a pressure cooker)

Depressurization of the containment
? Unit 1: 12.3. 4:00

? Unit 2: 13.3 00:00
? Unit 3: 13.3. 8.41

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.21

The Fukushima Daiichi Incident
2. Accident progression
Positive und negative Aspects of depressurizing the containment
? Removes Energy from the Reactor building (only way left) ? Reducing the pressure to ~4 bar

? Release of small amounts of Aerosols (Iodine, Cesium ~0.1%)
? Release of all noble gases ? Release of Hydrogen

Gas is released into the reactor service floor
? Hydrogen is flammable

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.22

The Fukushima Daiichi Incident
2. Accident progression
Unit 1 und 3
? Hydrogen burn inside the reactor service floor ? Destruction of the steel-frame roof ? Reinforced concrete reactor building seems undamaged ? Spectacular but minor safety relevant

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.23

The Fukushima Daiichi Incident
2. Accident progression
Unit 2
? Hydrogen burn inside the reactor building ? Probably damage to the condensation chamber (highly contaminated water) ? Uncontrolled release of gas from the containment ? Release of fission products ? Temporal evacuation of the plant ? High local dose rates on the plant site due to wreckage hinder further recovery work

No clear information's why Unit 2 behaved differently

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.24

The Fukushima Daiichi Incident
2. Accident progression
Current status of the Reactors
? Core Damage in Unit 1,2, 3 ? Building damage due to various burns Unit 1-4 ? Reactor pressure vessels flooded in all Units with mobile pumps ? At least containment in Unit 1 flooded

Further cooling of the Reactors by releasing steam to the atmosphere Only small further releases of fission products can be expected

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.25

The Fukushima Daiichi Incident
3. Radiological releases

Directly on the plant site
? Before Explosion in Unit Block 2
? Below 2mSv / h ? Mainly due to released radioactive noble gases ? Measuring posts on west side. Maybe too small values measured due to wind

? After Explosion in Unit 2 (Damage of the Containment)
? ? ? ? ? Temporal peak values 12mSv / h (Origin not entirely clear) Local peak values on site up to 400mSv /h (wreckage / fragments?) Currently stable dose on site at 5mSv /h Inside the buildings a lot more

? Limiting time of exposure of the workers necessary

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.26

The Fukushima Daiichi Incident
3. Radiological releases

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.27

The Fukushima Daiichi Incident
3. Radiological releases
Outside the Plant site
? As reactor building mostly intact => reduced release of Aerosols (not Chernobyl-like) ? Fission product release in steam => fast Aerosol grows, large fraction falls down in the proximity of the plant ? Main contribution to the radioactive dose outside plant are the radioactive noble gases ? Carried / distributed by the wind, decreasing dose with time ? No ?Fall-out“ of the noble gases, so no local high contamination of soil

~20km around the plant
? Evacuations were adequate ? Measured dose up to 0.3mSv/h for short times ? Maybe destruction of crops / dairy products this year ? Probably no permanent evacuation of land necessary

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.28

The Fukushima Daiichi Incident
3. Radiological releases

GRS.de

~50km around the plant
? Control of Crop / Dairy products
? Usage of Iodine pills (Caution, pills can interfere with heart medicine)

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.29

The Fukushima Daiichi Incident
4. Spend fuel pools
Spend fuel stored in Pool on Reactor service floor
? Due to maintenance in Unit 4 entire core stored in Fuel pool ? Dry-out of the pools
? Unit 4: in 10 days ? Unit 1-3,5,6 in few weeks

? Leakage of the pools due to Earthquake?

Consequences
? Core melt ?on fresh air “ ? Nearly no retention of fission products

? Large release

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.30

The Fukushima Daiichi Incident
4. Spend fuel pools
Spend fuel stored in Pool on Reactor service floor
? Due to maintenance in Unit 4 entire core stored in Fuel pool ? Dry-out of the pools
? Unit 4: in 10 days ? Unit 1-3,5,6 in few weeks

? Leakage of the pools due to Earthquake?

Consequences
? Core melt ?on fresh air “ ? Nearly no retention of fission products

? Large release

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.31

The Fukushima Daiichi Incident
4. Spend fuel pools
Spend fuel stored in Pool on Reactor service floor
? Due to maintenance in Unit 4 entire core stored in Fuel pool ? Dry-out of the pools
? Unit 4: in 10 days ? Unit 1-3,5,6 in few weeks

? Leakage of the pools due to Earthquake?

Consequences
? Core melt ?on fresh air “ ? Nearly no retention of fission products

? Large release

It is currently unclear if release from fuel pool already happened
The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.32

The Fukushima Daiichi Incident
5. Sources of Information

Good sources of Information
? Gesellschaft für Reaktorsicherheit [GRS.de]
? Up to date ? Radiological measurements published ? German translation of japanese/englisch web pages

? Japan Atomic Industrial Forum [jaif.or.jp/english/]
? Current Status of the plants ? Measurement values of the reactors (pressure liquid level)

? Tokyo Electric Power Company [Tepco.co.jp]
? Status of the recovery work ? Casualties

May too few information are released by TEPCO, the operator of the plant

The Fukushima Daiichi Incident – Dr. Matthias Braun - 23 July 2013 - p.33


相关文章:
福岛核电站爆炸事故分析
福岛核电站爆炸事故分析_军事/政治_人文社科_专业资料。福岛核电站爆炸事故分析福岛核电站爆炸事故分析及对我国发展核电的思考 1、事故背景北京时间 2011 年 3 月 ...
日本福岛核电站事故简介与分析
日本福岛核电站事故简介与分析北京时间 2011 年 3 月 11 日 13 时 46 分,日本发生 9.0 级地震并引发高达 10 米的强烈海啸,导致东京电力公司下属的福岛核...
日本福岛核电站事故分析看法
福岛核电站事故分析及看法福岛核电站简介及事故发生过程 福岛核电站简介及事故发生过程福岛核电站简介福岛核电站是目前世界上最大的核电站,由福岛一站、福岛二站组成...
日本核电事故分析报告
日本福岛核电站事故分析报告近几天因日本福岛核电站多个反应堆因地震而出现运转故障, 导致部分放射性物质泄漏 蔓延, 对日本本土和周边国家形成了较大的影响, 就...
福岛核电站事故分析
福岛核电站事故分析 感谢供稿:银河双子星 银河双子星(原子物理博士后、旅日留学生) 银河双子星 福岛核电站结构 福岛核电站属于沸水反应堆(简称 BWR,Boiling Water Reac...
日本福岛核电站事故初步分析
日本福岛核电站事故初步分析_兵器/核科学_工程科技_专业资料。日本福岛核电站事故初步分析 2011 年 3 月 11 日下午,日本东部海域发生里氏 9.0 级大地震,并引发...
福岛事故分析
38页 免费 日本福岛核电站事故分析看... 4页 5财富值 日本福岛第一核电站1号机事... 2页 1财富值 从福岛核事故看危害分析 3页 免费喜欢...
日本福岛第一核电站及其事故详解
日本福岛第一核电站及其事故详解_能源/化工_工程科技_专业资料。日本福岛第一核电站及其在2011年3月11日地震中发生的事故详细描述。日本...
福岛核电站事故总结
二、福岛核电站事故分析 1、福岛核电站事故后果 截至 3 月 16 日下午, 福岛第一核电站 6 座反应堆及福岛第二核电站 4 座反应堆现状如 下: 福岛第一核电站...
福岛核事故分析-英文
福岛核事故分析-英文_英语学习_外语学习_教育专区。How Is Japan's Nuclear ...福岛核事故原因分析 6页 1下载券 日本福岛核电站事故初步... 9页 5下载券...
更多相关标签:
福岛核电站事故分析 | 福岛核电站事故 | 日本福岛核电站事故 | 福岛核电站事故影响 | 福岛第一核电站事故 | 福岛核电站事故原因 | 2011年福岛核电站事故 | 福岛核电站事故纪录片 |